NOVUS AUTOMATION
46/57
7.3.3
CYCLES
This screen is divided into tabs and allows you to view the features grouped by feature cycles. Information regarding ClickNGo modules can be
viewed in the specific module datasheet.
7.3.3.1
OPERATION
This tab groups all the parameters related to the Operation Cycle of the device:
QuickTune
QuickTune Mobile
Operation tab
•
Control Setpoint:
Allows you to define the control Setpoint, according to the minimum and maximum limits of the configured SP.
•
Manipulated Variable:
Allows you to define the value of the manipulated variable. Range: 0 ~ 100.
•
Enables control and controller outputs:
Allows
you to enable control and outputs.
•
Control Mode:
Allows you to define the control mode of the device: “Manual” or “Automatic” (see
section).
7.3.3.2
CONTROL
This tab groups the parameters related to the Control Cycle (
CFG
>>
CtRL
) of the device (see
section):
QuickTune
QuickTune Mobile
Control tab
•
Auto-Tuning:
Allows you to define the auto-tuning mode: “Off”, “Fast tuning”, “Precise tuning”, “Precise and auto-adaptative tuning”, “New precise
and auto-adaptative tuning”, “New precise and auto-adaptative tuning when
RUN
=
YES
” (see
chapter).
•
Proportional Band:
Allows you to define the proportional band. It refers to the
P
value of the PID control mode, as a percentage of the input
type maximum range.
When set to 0.0, determines the ON/OFF control mode
. Range: 0 ~ 500.
•
Integral Rate:
Allows you to define the integral rate. It refers to the
I
value of the PID control mode, in repetitions per minute (Reset). Available
only when the
Proportional Band
parameter is
≠
0. Range: 0 ~ 99.99 (in seconds).