4.3.4
INPUT CYCLE (
CFG
>>
IN
)
This is the Input Cycle:
Input Cycle
Type
Type
Input type. Allows you to select the input type to be used. See table in
section.
You must configure this parameter first.
fLtr
F
i
lt
e
r
Input filter. The filter is used to improve the stability of the measured signal (PV). Adjustable between 0 and 9999.
At 0, it means that the filter is off. At 9999, it means that the filter is at maximum. The larger the filter, the slower the response of
the measured value.
unit
unit
Allows you to set the temperature unit: Celsius
°
C
or Fahrenheit
°
f
.
Dp.po
d
ecimal
Po
int
Allows you to define the decimal point position in SP and PV values:
0
– No decimal places
0.0
– One decimal place
When configuring the input parameter (
TYPE
) with temperature sensors (J, K, Pt10 etc.), in addition to the integer part of the
measurement, only decimal values (XXX.X) will be displayed.
For linear signals (mA, mV, V), this parameter determines the decimal point position of the measured value (XXXX, XXX.X,
XX.XX, X.XXX).
IN.LL
In
put
L
ow
L
imit
Indication range limits for the selected linear input.
Parameters available for
linear inputs
only (see table in
section).
IN.HL
I
nput
H
igh
L
imit
0ffs
Offs
et
Allows you to adjust the indicated PV value. Default value: 0.
sQRt
Sq
uare
R
oo
t
Square Root Function. Applies the quadratic function on the input signal, within the limits programmed in parameters
SPLL
and
spHL
.
YES
– Enables.
no
– Disables.