Controller N2000  

NOVUS AUTOMATION 

7/11 

Xyst 

Hysteresis

 

Control Hysteresis: This parameter is only shown for 

ON / OFF control. 
Displayed only if proportional band = 0. 

Act 

Action

 

Control Action:  

rE

         -Reverse Action usually used for heating. 

Dir

     -Direct Action usually used for cooling.  

bias 

Bias function  -  Allows adding a percentage value 

between  -100 % and +100 %. to the MV control 

output. 
The value 0 (zero) disables the function. 

Ovll 

Output Low 

Limit

 

Minimum  percentage value for MV (Manipulated 

Variable) when in automatic control and PID. Default 

value: 0.0 % 

Ovxl 

Output High 

Limit

 

Maximum percentage value for MV when in 

automatic control and PID. Default value: 100.0% 

Sfst 

Softstart

 

 

SoftStart  Function  –  Time in seconds during which 

the controller limits the MV value progressively from 

0 to 100 %. It is enabled at power up or when the 

control output is activated. If in doubt set zero (zero 

value disables the Soft start function). 

Sp.a1 
Sp.a2 
Sp.a3 
Sp.a4 

Alarm SP: Value that defines the point of activation 

for the programmed alarms with the functions “

Lo

” or 

ki

”. 

For the alarms configured with Differential type 

functions, this parameter defines deviation (band). 
Not used for the other alarm functions. 

RAMP AND SOAK PROFILE PROGRAMMING CYCLE  

Tbas 

Program time 

base

 

Program time base - Defines the time base that will be 

used by all Ramp & Soak programs. 

  Se(   

-Time basis in seconds 

 min

       -Time basis in minutes 

Pr n 

Program 

number

 

Program to be Viewed: Selects the ramp and soak 

profile program to be edited/viewed in the following 

cycle prompts (7 programs available).  

Ptol 

Program 

Tolerance

 

Ramp and Soak Tolerance:  maximum deviation 

between PV and SV. Whenever this deviation is 

exceeded the time counter is halted until deviation 

lowers to within the tolerance. Set zero to disable this 

function. 

Psp0 
Psp7 

Program SP

 

Ramp and Soak Set Points:  (0 to 7): Set of  8 SV 

values which define the ramp and soak profile 

segments.  

Pt1 
Pt7 

Program 

Time

 

Ramp and Soak Segments:  (1 to 7): Set of 7 time 

intervals in minutes for the 7 segments of the ramp 

and soak program. 

Pe1 
Pe7 

Program 

event

 

Ramp and Soak Event: (1 to 7): Set of 7 values that 

define which alarms must be activated during a ramp 

and soak program segment. Alarm function depends 

on “

rS

” setting (Table 3). 

Lp 

Link Program

 

Link Program: number of the next profile program to 

be linked following the current program.  
      0          -do not link to any other program. 

      1 a 7     -number of the program to be linked to. 

 

 

 

 

ALARM CYCLE 

Fva1 
Fva2 
Fva3 
Fva4 

Function 

Alarm

 

Functions of Alarms. Defines the functions for the 

alarms among the options of the Table 3

oFF, iErr, rS, Lo, xi, DiFL, DiFx, DiF

 

bla1 
bla2 
bla3 
bla4 

Blocking 

Alarm

 

This function blocks the alarm at power-up when the 

units is first energized. 
     YES     -enables.  
     NO       -Inhibits this blocking function.  

xya1 
xya2 
xya3 
xya4 

Histeresis of 

Alarm

 

Defines the differential range between the PV value 

at which the alarm is turned on and the value at 

which it is turned off. (In engineering units). 
 

A1t1 
A2t1 
A3t1 
A4t1 

Alarm Time t1

 

Defines the temporization time t1, for the alarms. In 

seconds. 
The value 0 (zero) disables the function. 

A1t2 
A2t2 
A3t2 
A4t2 

Alarm Time t2

 

Defines the temporization time t2 for the alarms time 

functions. In seconds. 
The value 0 (zero) disables the function. 

flsK 

Display flashes in alarm. 

Allows visual signalization of an alarm occurrence by 

flashing the indication of PV in the operation level. The user 

chooses which alarms are to be associated with this 

feature. 

CONFIGURATION CYCLE  

Type 

Type

 

Input Type: Selects the input signal type to be 

connected to the process variable input. Refer to 

Table 1
This is the first parameter to be set. 

fltr 

Digital Input Filter. Used to improve the stability of 

the measured signal (PV). Adjustable between 0 and 

20. In 0 (zero) it means filter turned off and 20 means 

maximum filter. The higher the filter value, the slower 

is the response of the measured value. 

Dppo 

Decimal Point

 

Defines the decimal point position. 

VnIt 

Unit

 

Defines the indication unit in  Celsius “°

(

“ or 

Fahrenheit “°

f

 

This parameter is presented whenever a temperature 

sensor is configured as input. 

Offs 

Offset

 

Sensor Offset:  Offset value to be added to the PV 

reading to compensate sensor error.  
Default value: zero. 

Spll 

Setpoint Low 

Limit

 

Defines the SP lower limit of. 
For the linear analog input types available (0-20 mA, 

4-20 mA, 0-50 mV and 0-5 V), defines the minimum 

PV  indication range, besides limiting the SP 

adjustment. 
Defines lower limit for range retransmission PV and 

SP. 

Содержание N2000

Страница 1: ...ing of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 7 setpoint profile programs with ...

Страница 2: ...s opened again Closed Contact Enables execution of the program Opened Contact Interrupts execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed PR 1 Digital input ...

Страница 3: ...ain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual resistor value depends on the desired output voltage span SOFT START The soft start feature avoids abrupt variations in the power delivered to the load regardless of the system power demand This is accomplished by defining a limiting ramp for the control output The output is a...

Страница 4: ...tely disconnected from the input output signals Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must ...

Страница 5: ...alue of PV Process Variable When in programming mode shows the parameter name Parameter display SV shows the SV Setpoint Variable value and the value of other parameters of the controller COM Indicator Flashes when communication messages are sent by the controller TUNE Indicator Lights during the execution of PID automatic tuning MAN Indicator Lights when the controller is in manual RUN Indicator ...

Страница 6: ...ibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password Master Password The Master Password is intended for allowing the user to define a new password in the event of it being forgott...

Страница 7: ...s must be activated during a ramp and soak program segment Alarm function depends on rS setting Table 3 Lp Link Program Link Program number of the next profile program to be linked following the current program 0 do not link to any other program 1 a 7 number of the program to be linked to ALARM CYCLE Fva1 Fva2 Fva3 Fva4 Function Alarm Functions of Alarms Defines the functions for the alarms among ...

Страница 8: ...ed at I O 6 relay 6 Refer to Table 2 for functions f fnc F Key Function Selects the I O function assigned to the front panel key Available functions are off Key not used rvn Start Stop the controller RUN function rSP Select remote setpoint kprg Execute Hold ramp and soak profile PR1 Enable Disable ramp and soak profile 1 aven Enable The Key Enable or disable operation of the key Yes key enabled NO...

Страница 9: ...f the profile If this deviation is exceeded the program will be interrupted until the deviation falls to within the tolerance band Programming 0 zero at this prompt disables the tolerance and the profile execution will not to be halted even if PV does not follow SV time priority as opposed to SV priority The ramp and soak event function is used to activate alarms at any segment of program 1 This a...

Страница 10: ...t provided by the controller ANALOG OUTPUT CALIBRATION 1 Select type 11 or 12 at the I O5 prompt 2 Connect a current meter at the analog output 3 Disable the auto tune and soft start functions 4 Set the output low limit ovLL to 0 0 and the output high limit ovkL to 100 0 5 Select the manual mode at the avto prompt 6 Enable the output at the rvn prompt 7 At the operation cycle set the MV to 0 0 8 A...

Страница 11: ...S PC UL94 V 0 ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN61326 1 A1 1998 EMISSION CISPR11 EN55011 IMMUNITY EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN61000 4 8 and EN61000 4 11 SECURITY EN61010 1 1993 and EN61010 1 A2 1995 UL file E300526 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm PR...

Отзывы: