Controller N2000  

NOVUS AUTOMATION 

5/11 

 

 

 

Fig. 4a – Connection of 4-20 mA 

Fig. 4b – Connection of 5 Vdc 

 

4-20 mA 

Refer to Fig. 4a. (The controller provides an internal electronic shunt 

for the input current. No changes in the circuit are necessary). 

 

0-5 Vdc: 

Refer to Figure 4b for connecting voltage signals. 

 

4-20 mA: 

The connections for current signals 4-20 mA must be carried-out 

according to Figure 4c

 

 

Fig. 4c - 

4-20 mA transmitter using the N2000  24 Vdc supply

 

 

Remote setpoint 

The remote Setpoint (SP) is enabled by an external digital signal in 

either I/O5  or I/O6, when programmed with the code 

rsp

  (Select 

remote SP input). 
An external resistor shunt of 100 

 is required between the terminals 

19 and 20. 

 

 

Fig. 4d - 

Connection for remote SP 

(0-20 / 4-20 mA) 

DIGITAL OUTPUT 
I/O5 can also be configured as digital output. An example of usage is 

shown in Fig. 5. I/O5 is electrically isolated from the sensor input. 

 

 

Fig. 5 – 

I/O5 with output pulse for SSR.

 

DIGITAL INPUT 
I/O5 and I/O6 can be used as digital inputs, accepting either dry contact 

or NPN open collector signals. Fig. 6 shows a switch driving the I/O5 

digital input. The digital input at I/O6 is driven only by dry contact 

signals. Fig. 7 shows a typical digital input wiring for I/O6. 

 

 

 

Fig. 6 – Digital input at I/O5 

Fig. 7 – Digital input at I/O6 

OPERATION 

The front panel is shown in Fig. 8

 

Fig. 8 - Front panel parts 

Status display/PV: shows the value of PV (Process Variable). When 

in programming mode, shows the parameter name. 
Parameter display/SV: shows the SV (Setpoint Variable) value and 

the value of other parameters of the controller. 
COM Indicator: Flashes when communication messages are sent by 

the controller. 
TUNE Indicator: Lights during the execution of PID automatic tuning. 
MAN Indicator: Lights when the controller is in manual. 
RUN Indicator: Lights when the controller is active, with control and 

alarm outputs enabled. 
OUT Indicator: For relay or pulse control output, reflects the actual 

state of the output. If an analog output is assigned for control, lights 

continuously. 
A1A2A3 and A4 Indicators: Status of the alarms. 

 

  - PROG key: used to walk through the menu cycles 

 

  - BACK key: go back to the previous displayed parameter 

 

  -  INCREASE  and 

 

  -  DECREASE keys: Used to change 

parameter values 

   

  -AUTO/MAN KEY: Shortcut for automatic/manual control 

selection. Alternates the control mode between automatic and 

manual each time the key is pressed. 

 -PROGRAMMABLE FUNCTION KEY: Can be assigned to the 

special functions described for the 

RVN , RSP,  KPRG, 

e

  PR1 

according to Table 2. 
When the controller is turned on, its firmware version is displayed for 

3 seconds, after which the controller starts normal operation. The 

values of PV and SV are displayed and the outputs are enabled. 
Before the controller is ready to be used in a given process, it 

requires some basic configuration, such as: 

 

Input type (T/C, Pt100, 4-20 mA). 

 

Control Setpoint Value (SP). 

 

Control Output Type (relays, 0-20 mA, 4-20 mA). 

 

PID parameters (or hysteresis for ON / OFF control) 

Содержание N2000

Страница 1: ...ing of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 7 setpoint profile programs with ...

Страница 2: ...s opened again Closed Contact Enables execution of the program Opened Contact Interrupts execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed PR 1 Digital input ...

Страница 3: ...ain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual resistor value depends on the desired output voltage span SOFT START The soft start feature avoids abrupt variations in the power delivered to the load regardless of the system power demand This is accomplished by defining a limiting ramp for the control output The output is a...

Страница 4: ...tely disconnected from the input output signals Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must ...

Страница 5: ...alue of PV Process Variable When in programming mode shows the parameter name Parameter display SV shows the SV Setpoint Variable value and the value of other parameters of the controller COM Indicator Flashes when communication messages are sent by the controller TUNE Indicator Lights during the execution of PID automatic tuning MAN Indicator Lights when the controller is in manual RUN Indicator ...

Страница 6: ...ibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password Master Password The Master Password is intended for allowing the user to define a new password in the event of it being forgott...

Страница 7: ...s must be activated during a ramp and soak program segment Alarm function depends on rS setting Table 3 Lp Link Program Link Program number of the next profile program to be linked following the current program 0 do not link to any other program 1 a 7 number of the program to be linked to ALARM CYCLE Fva1 Fva2 Fva3 Fva4 Function Alarm Functions of Alarms Defines the functions for the alarms among ...

Страница 8: ...ed at I O 6 relay 6 Refer to Table 2 for functions f fnc F Key Function Selects the I O function assigned to the front panel key Available functions are off Key not used rvn Start Stop the controller RUN function rSP Select remote setpoint kprg Execute Hold ramp and soak profile PR1 Enable Disable ramp and soak profile 1 aven Enable The Key Enable or disable operation of the key Yes key enabled NO...

Страница 9: ...f the profile If this deviation is exceeded the program will be interrupted until the deviation falls to within the tolerance band Programming 0 zero at this prompt disables the tolerance and the profile execution will not to be halted even if PV does not follow SV time priority as opposed to SV priority The ramp and soak event function is used to activate alarms at any segment of program 1 This a...

Страница 10: ...t provided by the controller ANALOG OUTPUT CALIBRATION 1 Select type 11 or 12 at the I O5 prompt 2 Connect a current meter at the analog output 3 Disable the auto tune and soft start functions 4 Set the output low limit ovLL to 0 0 and the output high limit ovkL to 100 0 5 Select the manual mode at the avto prompt 6 Enable the output at the rvn prompt 7 At the operation cycle set the MV to 0 0 8 A...

Страница 11: ...S PC UL94 V 0 ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN61326 1 A1 1998 EMISSION CISPR11 EN55011 IMMUNITY EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN61000 4 8 and EN61000 4 11 SECURITY EN61010 1 1993 and EN61010 1 A2 1995 UL file E300526 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm PR...

Отзывы: