Novus N2000 Скачать руководство пользователя страница 10

Controller N2000  

NOVUS AUTOMATION 

10/11 

AUTO TUNE 

During auto tune the process is controlled in ON/OFF mode at the 

programmed SetPoint (SV). Depending on the process 

characteristics large oscillations above and below SV may occur and 

auto tuning may take several minutes to be concluded. 
The recommended procedure is as follows: 

 

Disable the control output at the 

rvn

 prompt by selecting NO. 

 

Select auto mode operation at the 

Avto

  prompt by selecting 

YES. 

 

Disable the ramp and soak function (select NO) and program a 

new   SV value other than the present PV (close to the desired set 

point). 

 

Enable auto tuning at the 

Atvn

 prompt by selecting YES. 

 

Enable the control output at the 

rvn

 prompt by selecting YES. 

 

The “TUNE” indicator on the display stays lit until the completion 

  of the automatic tuning process. 

 

For control output types relay or pulse, the automatic tuning 

  calculates the longest suitable period (cycle time 

(t

) for the 

  PWM  output. The cycle time period may be reduced if the 

  process experiences some oscillation. When driving a SSR, it’s 

  recommended to set 

(t

 = 1 s. 

 

If the automatic tuning does not result in a satisfactory control, 

  refer to Table 6 for guidelines on how to correct the behavior of 

  the process. 

PARAMETER 

RESPONSE 

SOLUTION 

Proportional Band 

Slow Response 

Decrease 

Large Oscillation 

Increase 

Integral Rate 

Slow Response 

Increase 

Large Oscillation 

Decrease 

Derivative Time 

Slow Response or Instability 

Decrease 

Large Oscillation 

Increase 

Table 6 - Suggestions for manual tuning of PID parameters 

CALIBRATION 

INPUT CALIBRATION 
All inputs are factory calibrated and recalibration should only be done 

by qualified personnel. If you are not familiar with these procedures 

do not attempt to calibrate this instrument. The calibration steps are: 
a)  Select the input type to be calibrated. 
b)  Set the desired upper and lower display limits. 
c)  At the input terminals inject an electrical signal corresponding to 

a  known indication value a little higher than the lower display 

limit. 

d)  Select the 

inL(

 prompt. Through the   and   keys adjust 

PV so that it matches the injected signal. 

e)  Inject a signal that corresponds to a value a little lower than the 

upper limit of the display. 

f)  Select the 

ink(

 prompt. Through the   and   keys adjust 

PV so that it matches the injected signal. 

g)  Repeat steps c) to f) to improve calibration. 
Note: When checking the controller calibration with a Pt100 

simulator, pay attention to the simulator minimum excitation current 

requirement, which may not be compatible with the 0.170 mA 

excitation current provided by the controller.  

ANALOG OUTPUT CALIBRATION 
1)
  Select type 11 or 12 at the I/O5 prompt. 
2)  Connect a current meter at the analog output. 
3)  Disable the auto-tune and soft-start functions. 
4)  Set the output low limit 

ovLL

 to 0.0 % and the output high limit 

ovkL

 to 100.0 %. 

5)  Select the manual mode at the 

avto

 prompt. 

6)  Enable the output at the 

rvn

 prompt. 

7)  At the operation cycle, set the MV to 0.0 %. 
8)  At the output low calibration 

ovLC

 prompt, press the 

 

 and 

 

 

key until the mA meter reads zero mA. Approach this value from 

above. 

9)  Set 100.0 % for the manipulated variable (MV). 
10)  At the output high calibration 

ovkC

 prompt, press the 

 

 and 

 

  key until the mA meter reads 20 mA. Approach this value 

from below. 

11)  Repeat steps 7) to 10) as necessary. 

PROBLEMS WITH THE CONTROLLER 
Connection errors and inadequate programming are the most 

common errors found during the controller operation. A final review 

may avoid loss of time and damages. 
The controller displays some messages to help the user identify 

problems. 

MESSAGE 

PROBLEM 

----

 

Open input. Without sensor or signal. 

Err1 
Err6

 

Configuration or connection problem in the Pt100 

cable 

Other error messages displayed by the controller can account for errors 

in the input connections or type of selected input non-compliant with the 

sensor or signal applied to the input. If errors persist, even after a 

review, contact the manufacturer. Inform also the device serial number. 

To find out the serial number, press 

 

 for more than 3 seconds.  

The controller also has a visual alarm (the display flashes) when the 

PV value is out of the range set by 

spxl

 and 

spll

SERIAL COMMUNICATION 

The controller can be supplied with an asynchronous RS-485 digital 

communication interface for master-slave connection to a host 

computer (master).  
The controller works as a slave only and all commands are started by 

the computer which sends a request to the slave address. The 

addressed unit sends back the requested reply. 
Broadcast commands (addressed to all controller units in a multidrop 

network) are accepted but no reply is sent back in this case. 

CHARACTERISTICS 

 

Signals compatible with RS-485 standard. MODBUS (RTU) 

Protocol. Two wire connection between 1 master and up to 31 

(addressing up to 247 possible) instruments in bus topology. The 

communication signals are electrically insulated from the rest of 

the device; 

 

Maximum connection distance: 1000 meters. 

 

Time of disconnection for the controller: Maximum 2 ms after last 

byte. 

 

The communication signals are electrically isolated from the rest 

of the instrument, and can be 1200, 2400, 4800, 9600 and 19200 

bps.  

 

Number of data bits: 8, without parity or pair parity.  Number of 

stop bits: 1 

 

Time to start response transmission: up to 100 ms after 

acknowledging the command. 

Содержание N2000

Страница 1: ...ing of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 7 setpoint profile programs with ...

Страница 2: ...s opened again Closed Contact Enables execution of the program Opened Contact Interrupts execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed PR 1 Digital input ...

Страница 3: ...ain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual resistor value depends on the desired output voltage span SOFT START The soft start feature avoids abrupt variations in the power delivered to the load regardless of the system power demand This is accomplished by defining a limiting ramp for the control output The output is a...

Страница 4: ...tely disconnected from the input output signals Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must ...

Страница 5: ...alue of PV Process Variable When in programming mode shows the parameter name Parameter display SV shows the SV Setpoint Variable value and the value of other parameters of the controller COM Indicator Flashes when communication messages are sent by the controller TUNE Indicator Lights during the execution of PID automatic tuning MAN Indicator Lights when the controller is in manual RUN Indicator ...

Страница 6: ...ibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password Master Password The Master Password is intended for allowing the user to define a new password in the event of it being forgott...

Страница 7: ...s must be activated during a ramp and soak program segment Alarm function depends on rS setting Table 3 Lp Link Program Link Program number of the next profile program to be linked following the current program 0 do not link to any other program 1 a 7 number of the program to be linked to ALARM CYCLE Fva1 Fva2 Fva3 Fva4 Function Alarm Functions of Alarms Defines the functions for the alarms among ...

Страница 8: ...ed at I O 6 relay 6 Refer to Table 2 for functions f fnc F Key Function Selects the I O function assigned to the front panel key Available functions are off Key not used rvn Start Stop the controller RUN function rSP Select remote setpoint kprg Execute Hold ramp and soak profile PR1 Enable Disable ramp and soak profile 1 aven Enable The Key Enable or disable operation of the key Yes key enabled NO...

Страница 9: ...f the profile If this deviation is exceeded the program will be interrupted until the deviation falls to within the tolerance band Programming 0 zero at this prompt disables the tolerance and the profile execution will not to be halted even if PV does not follow SV time priority as opposed to SV priority The ramp and soak event function is used to activate alarms at any segment of program 1 This a...

Страница 10: ...t provided by the controller ANALOG OUTPUT CALIBRATION 1 Select type 11 or 12 at the I O5 prompt 2 Connect a current meter at the analog output 3 Disable the auto tune and soft start functions 4 Set the output low limit ovLL to 0 0 and the output high limit ovkL to 100 0 5 Select the manual mode at the avto prompt 6 Enable the output at the rvn prompt 7 At the operation cycle set the MV to 0 0 8 A...

Страница 11: ...S PC UL94 V 0 ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN61326 1 A1 1998 EMISSION CISPR11 EN55011 IMMUNITY EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN61000 4 8 and EN61000 4 11 SECURITY EN61010 1 1993 and EN61010 1 A2 1995 UL file E300526 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm PR...

Отзывы: