Novus N1500LC Скачать руководство пользователя страница 5

N1500LC Indicator 

 

NOVUS AUTOMATION 

5/7 

FUNCTION LEVEL 

f.fvnc 

F Key function 

 

Makes possible to define the F 

key function. Available functions: 

oFF

 -      Key not used. 

kold

 -    Hold PV 

RSt

 -      Resets Maximum and Minimum values 

PkoLd

 - Peak Hold 

XI 

-      Displays maximum

 

LO

  

-        Displays minimum

 

ZERO 

-  Automatic zero 

These functions are described in item 5. 

Dig.in

 

Digital Input Function 

-  Makes possible to define 

the digital input function. Functions available are the 

same as the ones available for the 

key, except for 

the Zero function, replaced by the Tare function. 

oFF - kold - rSt - PkoL -–XI - LO - 
tare 

These functions are described in item 5. 

filtr

 

Input Digital Filter

 - Used to reduce the noise in the 

measured value. Adjustable from 0 to 60. 0 means 

the filter is off and 60 means maximum filtering. The 

filter slows down the response of the measured 

value. 

ofset

 

Displayed offset

  -  Added value to the measured 

value to correct the offset. Expressed in the unit 

configured input type. 

En A.z 

Enables Auto zero

 – Enables the auto-zero function 

of the indication. The indication will turn to zero if the 

input value is within the programmed range in 

A.Zran

 

for 3 seconds.  
Auto-zero occurs when the indication is relatively 

stable. It is used to eliminate the influence of 

interference or 

small

 deviations in the zero of a scale. 

A.Z.rAn 

Maximum level for zero

  –  Maximum level of the 

scale zero deviation, where auto-zero is activated. 

This value can be programmed up to 2% of the end of 

scale. 

Bavd

 

Communication Baud-Rate

  -  Transmission baud 

rate used in serial communication (RS-485) in 

bps

 

and 

kbps

1200, 2400, 4800, 9600, 19200, 38400, 57600, 

115.2. (NONE parity) 1.2P, 2.4P, 4.8P, 9.6P, 19.2P, 

38.4P, 57.6P e 115.2P (with EVEN parity). 

Adres

 

Communication Address

 - A number that identifies 

the instrument in a communication network. 

CONFIGURATION LEVEL 

In.typ

 

 

Input Type

 - Selects the input signal or sensor type 

to be connected to the PV terminals. Refer to 

Table 

1

 for options. 

Changing the input type causes all other parameters 

related to PV and alarms to be changed as well, 

therefore, this parameter shall be the first to be set.

 

Dp.pos

 

Decimal Point Position

 - Determines the position of 

the decimal point in the display. 

scale

 

Parameter that defines the limits of indication of 

entries. 

0

  –  Configurable indication from –  31000 to + 

31000. 

–   Configurable indication from 0 to + 60000. 

2

 –    Configurable indication from 0 to +120000, 

showing only even values. 

The PV values, SP Alarms and Offset also obey 

these limits. 

In.lol

 

Input Low Limit

 - Determines the minimum limit for 

input signals. The band created can be ascending or 

descending characteristic in relation to the input 

signal behavior. 

In.kil

 

Input High Limit

  -  Determines the maximum limit 

for input signals. The band created can be 

ascending or descending characteristic in relation to 

the input signal behavior. 

Ovt.ty

 

Analog Output Type

 - Allows selecting the type of 

signal available on the analog output: 0-20 mA or 4-

20 mA. 

ov.lol 

Output Low Limit 

Low Limit for analog retransmission 

– 

Determines the display value corresponding to an 

electric current of 4 mA (or 0 mA). 

0v.kil 

Output High Limit 

High Limit for analog retransmission 

-  Defines 

the PV value that results in a 20 mA analog output 

current. 

Ovt.er 

Output error

 

Error signaling for 4-20mA output - 

Configure the 

state of the analog output when an error occurs in 

the retransmission (beginning or end of the scale). 

CUSTOMIZED LINEARIZATION LEVEL 

Inp.01 
Inp.30

 

Defines the extreme points of the customized 

linearization. Values must be in the input signal unit.  

Ovt.01 

Ovt.30

 

Defines the proportional indications in respect to 

each segment of the customized linearization. 

Values are in the intended indication unit. 

CALIBRATION LEVEL 

All input and output types are factory calibrated, and we recommend 

not making any calibration procedure. This level should only be 

accessed by experienced personnel.  

If this level is accidentally accessed do not touch the 

 or 

 

keys, go through all the screens until you return to operating cycle 

(operation). 

In..lo(

 

Zero Input Calibration - 

It allows you to calibrate 

the offset of PV. You can increment or decrement 

the desired value tapping the keys 

 and 

In.ki(

 

Span Input Calibration - 

Sets the gain of PV. 

Ov.lo(

 

Zero Calibration for the Analog Output -

 Value for 

the analog output offset (0 or 4 mA). 

Ov.Ki(

 

Analog Output Span Calibration

 – Value for gain 

calibration of the analog output (20mA). 

k.type

 

Hardware Type

 - Parameter to adjust the indicator 

to the type of available hardware. Should not be 

changed by the user, except when a new accessory 

is inserted or removed. 

2 Alarms .............................................. 

code

 

3

 

2 Alarms and 4-20 mA....................... 

code

 

19

 

2  Alarms and RS485 ......................... 

code

 

35

 

2  Alarms and 4-20 mA and RS485.... 

code

 

51

 

4  Alarms ............................................ 

code

 

15

 

4  Alarms and 4-20 mA....................... 

code

 

31

 

4  Alarms and RS485 ......................... 

code

 

47

 

4  Alarms and 4-20 mA and RS485.... 

code

 

63

 

AUTOMATIC CALIBRATION LEVEL 

Specific calibration for weighing systems, where the user himself 

performs the calibration of their system, using two reference weights, 

minimum and maximum, and setting their indication values. 

To access this cycle press and keep pressed 

 

and 

 for 30 

seconds. 

Содержание N1500LC

Страница 1: ...utomatic zero functions Digital input Optionally can have Process Variable PV retransmission in 0 20 mA ou 4 20 mA RS485 MODBUS RTU serial communication 3rd and 4th alarm relays The front panel is sho...

Страница 2: ...with value 0 zero The Warning LEDs associated with the alarm always light up when the alarm condition occurs regardless of the current state of the output relay which may be de energized momentarily...

Страница 3: ...to adopt the Custom Linearization option This feature combines the input signal to 30 user defined line segments setting two points for each segment a start and end and the respective display values T...

Страница 4: ...HE INDICATOR WORK LEVEL This is the first level At power up the indicator will display the Process Variable PV The alarm triggering points are also displayed at this level alarm Setpoints To advance i...

Страница 5: ...et also obey these limits In lol Input Low Limit Determines the minimum limit for input signals The band created can be ascending or descending characteristic in relation to the input signal behavior...

Страница 6: ...erly configured the instrument may show false error messages particularly those related to the type of input selected SPECIAL RECOMMENDATIONS Should the indicator be repaired some special handling car...

Страница 7: ...e the serial communication interface Communication Baud Rate bavd parameter and Communication Address adres parameter SPECIFICATIONS DIMENSIONS 48 x 96 x 92 mm 1 8 DIN Approximate weight 250 g PANEL C...