Novus N1500LC Скачать руководство пользователя страница 4

N1500LC Indicator 

 

NOVUS AUTOMATION 

4/7 

Input signal connection 

It is important that they are very well connected, the sensor wires 

must be well fixed in the terminals of the rear panel. 

 

 

 

Figure 5

 - Voltage connection 

Figure 6

 - Current connection 

Load Cell Connection using the indicator power supply 

 

 

Figure 6a

 – Load Cell 

Digital Input (Dig In) 

To use the Digital Input, a switch must be connected to respective 

terminals (dry contact), as shown in 

Figure 7

 

 

Figure 7

 – Using the Digital Input 

Analog output (4-20 mA OUTPUT) 

The analog output may be 0-20mA or 4-20mA, selected in the 

configuration. The output is available at terminals 29 and 30, as 

requested in the purchase order. 

OPERATION 

For best results, this indicator requires correct basic setting of 

parameters or a definition for parameters displayed. It is necessary to 

define, for example: Type of input (0-20 mA, 4-20 mA, etc.), range 

display, alarm set point, alarm function, etc. 
To make configuration easier, the parameters are divided in five 

levels (or groups): 

Level 

Access 

1- Work 

Free access 

2- Alarms 

Reserved access 

3- Special Functions 

4- Input Setting 

5- Customized Linearization 

6- Calibration 

7- Automatic Calibration 

Table 4

 - Parameters Levels 

The work cycle has free access. All other levels  require a certain 

combination of key strokes to be accessed. The combination is:

 

 

 and 

 keys pressed simultaneously 

Once within a cycle, just press 

 

to move to the subsequent 

parameters of this cycle. At the end of each cycle the display will go 

back to the work cycle. 
At the desired parameter, just press the buttons 

  or 

  to 

promote the desired changes. These changes are saved into 

protected memory and given as valid when we move to the next 

parameter. 

After 25 seconds with no key pressed the indicator will return to the 

Measurement screen at work cycle. 

PROGRAMMING THE INDICATOR 

WORK LEVEL 

This is the first level. At power up the indicator will display the Process 

Variable (PV). The alarm triggering points are also displayed at this level 

(alarm Setpoints). To advance in this level simply press 

.

 

SCREEN 

PARAMETER DESCRIPTION 

8.8.8.8.8. 

Screen Measures

  -  Shows the variable measured 

according to the limits defined in the “

in.LoL

” and 

in.kiL

” screens. 

Should any failure occur, the indicator will display an 

error message. 

Al.ref 

Differential alarm reference value

 - This screen is 

shown only when there is an alarm programmed with 

differential function. This value is used as a 

reference for differential alarms triggering. 

Sp.al1 
Sp.al2 
Sp.al3 
Sp.al4 

Alarms Set Points 1, 2, 3 and 4

-  Defines the 

operation point of each alarm programmed with “

Lo

” 

or “

ki

” functions. 

Note: For alarms programmed with differential 

functions, the alarm SP value cannot be changed, 

and the “

diF

” message is displayed. The value of 

differential SP (deviation) is defined in the Alarms 

Cycle. 

NOTE

:  The SP adjustment parameters are 

presented only if the corresponding alarm function is 

configured. 

ALARM LEVEL 

fV.al1 
fV.al2 
fV.al3 
fV.al4

 

Alarm Function

 - Defines the alarm functions: 1, 2, 

3 or 4, as defined in item 4.1. 

oFF

  : Alarm off 

Err

  : Broken or Shorted Sensor 

Lo

 

: Low value 

ki

 

: High value 

DiFL

  : Differential low 

DiFH

  : Differential high 

DiF f

 : Differential outside the range 

DiF d

 : Differential within range 

Ky.al1 
Ky.al2 
Ky.al3 
ky.al4

 

Alarm Hysteresis

 

Defines the difference between the value at which 

the alarm is turned on and the value at which it is 

turned off. 

Bl.al1 
Bl.al2 
Bl.al3 
bl.al4

 

Initial Blocking Function

 

It makes possible to prevent alarms activation at the 

process start, when all the system is powered. See 

item 4.3. 

Al1t1 
Al1t2 
Al2t1 
Al2t2 
Al3t1 
Al3t2 
Al4t1 
Al4t2 

Alarm Timer Function

 

Sreens that define time T1 and T2, in seconds, 

shown in 

Table 3

. They allow the user to delay the 

alarm triggering, to activate alarms momentarily or 

sequentially. 
To disable timer function, just set zero for T1 and T2. 

Содержание N1500LC

Страница 1: ...utomatic zero functions Digital input Optionally can have Process Variable PV retransmission in 0 20 mA ou 4 20 mA RS485 MODBUS RTU serial communication 3rd and 4th alarm relays The front panel is sho...

Страница 2: ...with value 0 zero The Warning LEDs associated with the alarm always light up when the alarm condition occurs regardless of the current state of the output relay which may be de energized momentarily...

Страница 3: ...to adopt the Custom Linearization option This feature combines the input signal to 30 user defined line segments setting two points for each segment a start and end and the respective display values T...

Страница 4: ...HE INDICATOR WORK LEVEL This is the first level At power up the indicator will display the Process Variable PV The alarm triggering points are also displayed at this level alarm Setpoints To advance i...

Страница 5: ...et also obey these limits In lol Input Low Limit Determines the minimum limit for input signals The band created can be ascending or descending characteristic in relation to the input signal behavior...

Страница 6: ...erly configured the instrument may show false error messages particularly those related to the type of input selected SPECIAL RECOMMENDATIONS Should the indicator be repaired some special handling car...

Страница 7: ...e the serial communication interface Communication Baud Rate bavd parameter and Communication Address adres parameter SPECIFICATIONS DIMENSIONS 48 x 96 x 92 mm 1 8 DIN Approximate weight 250 g PANEL C...

Отзывы: