N1500LC Indicator 

 

NOVUS AUTOMATION 

2/7 

ALARMS 

The indicator has 2 alarm outputs in the basic version and up to 4 

alarms outputs optionally.  

TYPE 

PROMPT 

ACTION 

Disabled 

Off

 

Alarm disabled 

Open Semsor (

i

nput 

Err

or

ierr

 

Alarm will go ON if sensor breaks 

 High Alarm 

(

Lo

w

Lo

 

Alarm SP

PV

 

High Alarm 

(

Hi

gh

Ki

 

Alarm SP

PV

 

Differential Low 

(

diff

erential

 

Lo

w

Dif.lo

 

 

PV

 

ALreF 

ALreF  + Deviation 

 

Differential High 

(

diff

erential

 

Hi

gh

Dif.ki

 

 

PV

 

ALrEF + Deviation

 

ALrEF 

 

Differential out of 

range 

(

dif

erencial 

F

ora) 

Dif f

 

 

PV

 

ALrEF + Deviation

 

ALrEF 

ALrEF - Deviation

 

 

Differential within 

range 

(

diff

erential 

With

in) 

Dif d 

 

PV

 

ALrEF + Deviation

 

ALrEF 

ALrEF - Deviation

 

 

Table 2

 - Alarm basic functions 

Each alarm has a Warning Light in the front panel that shows when it 

was activated. 

Alarm Functions 

The alarms can be set to operate in six  different  modes:  Open 

Sensor, Low alarm, High alarm, Differential low, Differential High or 

Differential (Band).  These modes are shown in 

Table 2

  and 

described below.  

Open Sensor  

The alarm is triggered whenever the sensor breaks or is badly 

connected or broken. 

Low Alarm 

The alarm relay is triggered whenever the measured value is 

below

 

the alarm set point. 

High Alarm 

The alarm relay is triggered whenever the measured value is 

above

 

the alarm set point. 

Differential (or Band) out of range 

For Differential alarm it is necessary to define two parameters: 

Differential Alarm Reference Value (

ALrEF

) and Alarm Differential 

Setpoint (Deviation). 
The Differential out of range alarm occurs when the measured value 

is outside the range defined by: 

(

ALrEF

 - Deviation) 

and 

(

ALrEF

 + Deviation) 

Differential (or Band) within range 

Same as previous, but acting within the range defined above. 

Differential Low 

Triggered whenever the measured value is 

below

 the set point by: 

(

ALrEF

 - Deviation) 

Differential High 

Triggered whenever the measured value is 

above

 the set point by: 

(

ALrEF

 + Deviation) 

Alarm Timer 

The N1500LC allows programming of the Time Setting of Alarms, 

being able to set delays in alarm condition; send a single pulse at the 

time of trigger; or allow the generation of sequential pulses. 

Table 3

 shows these advanced functions. Times T1 and T2 can be 

programmed from 0 to 6500 seconds and are defined when setting 

up the device. For alarms with no time delays, set T1 and T2 with 

value 0 (zero). 
The Warning LEDs associated with the alarm always light up when 

the alarm condition occurs, regardless of the current state of the 

output relay, which may be de-energized momentarily due to a time 

delay. 

Advanced 

Function 

T1 

T2 

ACTION 

Normal 

Operation 

Alarm Event

Alarm

Output

 

Delayed 

1 s to 

6500 s 

Alarm Event

Alarm

Output

T2

 

Pulse 

1 s to 

6500 s 

Alarm Event

Alarm

Output

T1

 

Oscillator 

1 s to 

6500 s 

1 to 6500 

Alarm Event

Alarm

Output

T1

T2

T1

 

Table 3

 - Timer Alarm Functions 

Initial Block Alarm 

The initial blocking option inhibits the alarm from being recognized if 

an alarm condition is present when the controller is first energized. 

The alarm will be triggered only after the occurrence of a non alarm 

condition followed by a new occurrence for the alarm.  The initial 

blocking is disabled for the sensor break alarm function. 

SPECIAL FUNCTIONS 

SPECIAL FUNCTION KEY AND DIGITAL INPUT 

The 

  key  (special function key) in the frontal panel of the 

controller as well as the Digital Input may be assigned different 

functions that will be chosen by the user during the setup.  The 

possible functions are: 

zero

 – Zero Function  

Available only for the 

 key. It resets the scale. This function is 

used to eliminate the influence of interference or small deviations in 

the zero of a scale. Reset is only accomplished if the value shown in 

the scale is within 2% of the end of scale. Zero is not lost if the scale 

is turned off. 

Note

: This function can be performed automatically using the 

parameters 

En

 

A.z

 

and 

A.Z.rAn

Lo

 – Displays Minimum 

Set the 

 key, to at the first tap, displays the 

minimum (Low)

 value 

the indicator measured since the last reset. On the second tap to show 

the maximum (High) measured by the indicator since the last reset. On 

the third ring, returns to normal display. Press the button for more than 5 

seconds to reset, and the minimum and maximum values will be 

erased, starting a new cycle. 

xi

 – Displays Maximum 

Displays the 

maximum (High)

  value the indicator measured since 

the last reset

.

 

Pkold

 – Maximum value 

The indicator will automatically work in the 

Peak Hold

  mode 

whenever the 

 

key or the Digital Input are programmed as 

PkoLd

”. 

This mode of operation mode the indicator always shows the 

maximum value measured, since the last time the 

  key or the 

Digital Input were pressed. 
Each activation of the 

 key or digital input triggers a new Peak 

Hold cycle, reinitializing the reading of the display to the current value 

of the measure. 

Содержание N1500LC

Страница 1: ...utomatic zero functions Digital input Optionally can have Process Variable PV retransmission in 0 20 mA ou 4 20 mA RS485 MODBUS RTU serial communication 3rd and 4th alarm relays The front panel is sho...

Страница 2: ...with value 0 zero The Warning LEDs associated with the alarm always light up when the alarm condition occurs regardless of the current state of the output relay which may be de energized momentarily...

Страница 3: ...to adopt the Custom Linearization option This feature combines the input signal to 30 user defined line segments setting two points for each segment a start and end and the respective display values T...

Страница 4: ...HE INDICATOR WORK LEVEL This is the first level At power up the indicator will display the Process Variable PV The alarm triggering points are also displayed at this level alarm Setpoints To advance i...

Страница 5: ...et also obey these limits In lol Input Low Limit Determines the minimum limit for input signals The band created can be ascending or descending characteristic in relation to the input signal behavior...

Страница 6: ...erly configured the instrument may show false error messages particularly those related to the type of input selected SPECIAL RECOMMENDATIONS Should the indicator be repaired some special handling car...

Страница 7: ...e the serial communication interface Communication Baud Rate bavd parameter and Communication Address adres parameter SPECIFICATIONS DIMENSIONS 48 x 96 x 92 mm 1 8 DIN Approximate weight 250 g PANEL C...

Отзывы: