7. Testing functionality 

and operational readi-
ness

ACL fans should be tested every six 
months with respect to functionality and 
operational readiness provided the fan is 
started at least once a day by means of a 
time switch.

7.1 Periodic inspection

ACL fans must always be maintained in 
proper operating condition. To ensure 
satisfactory operation and long service 
life, the fans should be inspected every 
six months.

Inspection should include:

• Measurement of power consumption. 
• Measurement of fan housing vibra-

tion. 

• Control of fixation bolt torque and, if 

necessary, readjustment. 

• Visual inspection of fan housing, im-

peller and electrical connection. 

• Cleaning

– with compressed air inside
– with water outside

It is recommended that a log be kept of 
all values and observations.

8. Sound

The sound generated by the fans de-
pends on installation and operating con-
ditions, and general data on sound emis-
sion is therefore unavailable.

For further details, please refer to our 
catalogue material or computer pro-
grams designed to calculate specific 
sound emissions.

9. Declaration of con-

formity

In accordance with the European Ma-
chinery Directive 2006/42/EC, Annex II 
A.

Manufacturer:Novenco A/S
Address:

Industrivej 22
DK-4700 Naestved

We hereby declare that axial flow fans, 
type ACL 400-900, 

a

fulfil the requirements contained in 
the following Directives on the condi-
tion that the product is installed in ac-
cordance with the installation instruc-
tions. If the product has been altered 
in any way, the declaration no longer 
applies.

Directives

EC Machinery Directive 2006/42/

EC

EMC Directive 2004/108/EC

LVD 2006/95/EC

b

have been manufactured in accord-
ance with the following harmonised 
standards.

Applied standards

EN ISO 12100-1:

Safety of machinery – Part 1

EN ISO 12100-2 + 12100-2/A1:

Safety of machinery – Part 2

EN ISO 13857:

Safety of machinery – Safety dis-
tances

EN 60204-1:

Safety of machinery – Electrical 
equipment of machines – Part 1: 
General Requirements

On the proviso that Novenco installation 
instructions have been followed.

Naestved, 1.4.2010

Steen Hansen
R&D manager
Novenco A/S

Figure 6.  Electrical connection through fan housing

Electric cable

Electric cable

Metal lead-through

Metal lead-through
(relief)

(relief)

Nut

Nut

Содержание Novax

Страница 1: ...nts Novax ACL fans are supplied on pallets or skids enabling fork lifttransport The forks must be positioned beneath the base The unit must be set down as slow ly as possible on a soft surface Impacts vibrations and falls may cause imbal ance and deformation or damage to mo tor bearings 3 Storage Novax fans can withstand outdoor stor age for up to one month providing the packaging is intact After ...

Страница 2: ...them Push fan along cross supports towards panel until end plate and panel are in close contact Horizontally centre fan in relation to hole in panel Screw mount securely to cross supports Check position of fan in relation to hole in panel and adjust if necessary Check that end plate is in close contact with panel Secure fan in position with screws through guides and rails and through rails and bas...

Страница 3: ...abnormal sound oc curs 3 Check that the vibration level is nor mal Atoperatingspeed fanvibration must not exceed 7 mm s rms meas ured radially at two points with 90 offset and at the free shaft end of the motor Otherwise the fan must be re balanced Operation at vibration levels higher than 18 mm s rms is inadvisable if vi bration dampers have been used See ISO 2954 Requirements for instru ments fo...

Страница 4: ...ry adjusted using a special tool fixture to provide the out put required by the customer order on delivery If a different output is required it is pos sible to alter blade pitch This requires knowledge of the motor load and the max permissible blade pitch in relation to the motor rating in case of blade pitch increase Please contact Novenco before any such adjustment of blade pitch Special tools f...

Страница 5: ... to our catalogue material or computer pro grams designed to calculate specific sound emissions 9 Declaration of con formity In accordance with the European Ma chinery Directive 2006 42 EC Annex II A Manufacturer Novenco A S Address Industrivej 22 DK 4700 Naestved We hereby declare that axial flow fans type ACL 400 900 a fulfil the requirements contained in the following Directives on the condi ti...

Отзывы: