NOVENCO Novax Скачать руководство пользователя страница 4

4

 

03).
Remove impeller using puller secured in 
the two threaded puller holes in the hub 
boss (pos. 05).

Loosen bolts in motor shell (pos. 06). Mo-
tor (pos. 11) and motor flange (pos. 10) 
can then be removed.

When dismantling the fan, be careful not 
to expose individual parts to impacts or 
other forces that might damage the mo-
tor bearings or other fan parts.

6.6 Fitting the motor

After servicing is complete the motor 
must be refitted. Check that the motor 
flange (pos. 10) is correctly positioned 
and that the motor shaft is concentrically 
positioned in the fan housing before 
tightening the bolts (pos. 06).

Refit impeller (pos. 04) on motor shaft 
using puller secured in threaded hole on 
motor shaft. Tighten impeller hub 
against motor shaft collar. 

Check that blade tip clearance is equal 
around the entire circumference of the 
housing. If this is not the case, adjust mo-
tor position in suspension system.

Then refit hub cover (pos. 03), centre disc 
(pos. 02) and centre screw (pos. 01). It is 
recommended that lock washers and 

lock nuts be replaced when reassembling 
the fan. Finally, reconnect motor cable 
(pos. 12) to motor.

The fan must then be reinstalled against 
the panel as previously described in sec-
tion 4. Installation.

To restart the fan, follow the procedure 
described in section 5. Start-up.

6.7 Blade adjustment

The blade pitch is factory adjusted using 
a special tool (fixture) to provide the out-
put required by the customer/order on 
delivery.

If a different output is required, it is pos-
sible to alter blade pitch. This requires 
knowledge of the motor load and the 
max. permissible blade pitch in relation 
to the motor rating (in case of blade pitch 
increase).

Please contact Novenco before any such 
adjustment of blade pitch. Special tools 
for blade pitch adjustment and instruc-
tions for impeller balancing are available 
from Novenco.

A brochure describing the blade pitch 
tool and its use is available on request.

6.8 Fault finding

Possible operating faults are described in 
the following.

Insufficient output

• Blocked air supply on inlet side

– Damper  closed
– Duct blocked
– Supply fan (if any) stopped
– Motor defective
– Motor cut out

• Incorrect direction of impeller rota-

tion

Noise/vibration

• Bearings in electric motor defective
• Impeller out of balance
• Impeller worn/damaged
• Bolts/components loose
• Impeller blades have different pitch
• Fan operating in "stall" mode. This 

may damage the system and should 
be remedied immediately, see "Insuf-
ficient output”.

Sizes

Min.

Average

H

u

b

 d

iam

ete

r

23

0,

 330

 and 38

0

400

0.6

1.2

500

0.5

1.4

560

0.6

1.5

630

0.6

1.7

710

0.7

2.0

800

0.8

2.2

900

0.9

2.5

Table 3.  Blade tip clearance [mm]

Figure 5.  Exploded drawing of ACL fan

01: Centre screw
02: Centre disc
03: Hub cover
04: Impeller
05: Hub boss
06: Screw for motor shell
07: Washer for motor shell
08: Motor shell
09: Fan housing
10: Motor flange
11: Motor
12: Motor cable
13: Metal lead-through

Содержание Novax

Страница 1: ...nts Novax ACL fans are supplied on pallets or skids enabling fork lifttransport The forks must be positioned beneath the base The unit must be set down as slow ly as possible on a soft surface Impacts vibrations and falls may cause imbal ance and deformation or damage to mo tor bearings 3 Storage Novax fans can withstand outdoor stor age for up to one month providing the packaging is intact After ...

Страница 2: ...them Push fan along cross supports towards panel until end plate and panel are in close contact Horizontally centre fan in relation to hole in panel Screw mount securely to cross supports Check position of fan in relation to hole in panel and adjust if necessary Check that end plate is in close contact with panel Secure fan in position with screws through guides and rails and through rails and bas...

Страница 3: ...abnormal sound oc curs 3 Check that the vibration level is nor mal Atoperatingspeed fanvibration must not exceed 7 mm s rms meas ured radially at two points with 90 offset and at the free shaft end of the motor Otherwise the fan must be re balanced Operation at vibration levels higher than 18 mm s rms is inadvisable if vi bration dampers have been used See ISO 2954 Requirements for instru ments fo...

Страница 4: ...ry adjusted using a special tool fixture to provide the out put required by the customer order on delivery If a different output is required it is pos sible to alter blade pitch This requires knowledge of the motor load and the max permissible blade pitch in relation to the motor rating in case of blade pitch increase Please contact Novenco before any such adjustment of blade pitch Special tools f...

Страница 5: ... to our catalogue material or computer pro grams designed to calculate specific sound emissions 9 Declaration of con formity In accordance with the European Ma chinery Directive 2006 42 EC Annex II A Manufacturer Novenco A S Address Industrivej 22 DK 4700 Naestved We hereby declare that axial flow fans type ACL 400 900 a fulfil the requirements contained in the following Directives on the condi ti...

Отзывы: