4.4 Duct connection (alterna-

tive)

ACL fans are prepared for circular duct 
connections on the outlet side.

The duct may need to be adapted prior to 
connection, e.g. the outlet side may need 
to be shortened to make room for the dif-
fuser.
If the existing duct has a different diam-
eter than the diffuser, an adapter must be 
fitted. 

Systems with high vibration levels or ex-
acting performance requirements must 
be provided with expansion joints be-
tween the fan and duct. The fan should 
not be used to support the duct. 

4.5 Electrical connection

Electrical connection must be made by 
an authorised electrician in accordance 
with current legislation. Power should 
be connected direct to the frequency con-
verter. See figure 6. Connections should 
be made in accordance with frequency 
converter wiring diagrams. Note that the 
fan cable is screened. It must be connect-
ed in such a way that the screen remains 
unbroken. 

If an external frequency converter is to be 
used, its interference filter must meet 
current requirements and regulations. 

After connecting the fan, check that the 
direction of impeller rotation complies 
with the arrow plate on the fan housing. 

Alternatively, the fan can be installed 
without frequency converter. In such sit-
uations, the fan should be connected via 
a terminal box or plug socket. Note! A 
switch must be installed in the immedi-
ate vicinity of the fan. 

5. Start-up

5.1 Before start-up

Before start-up, check that the fan has 
been installed correctly. The section in 
which the fan is installed and the adjoin-
ing duct should be checked and cleaned 
of dirt, foreign matter and tools before 
the fan is started. 

Also ensure that the electrical connec-
tions fulfil applicable requirements, that 
any protective grilles on the fan outlet 
side are correctly fitted, and that the di-
rection of impeller rotation complies 
with the arrow plate (check by briefly 
starting the fan).

5.2 Motors with 

Δ

/Y starter

The relay must be set to the calculated 
time.

5.3 Start-up procedure

Staring the fan

1

Start the fan

2

Check that no abnormal sound oc-
curs.

3

Check that the vibration level is nor-
mal. At operating speed, fan vibration 
must not exceed 7 mm/s rms meas-
ured radially at two points with 90° 
offset and at the free shaft end of the 
motor. Otherwise, the fan must be re-
balanced.
Operation at vibration levels higher 
than 18 mm/s rms is inadvisable if vi-
bration dampers have been used. See 

ISO 2954 – Requirements for instru-
ments for measuring vibration severity

.

4

After thirty minutes of operation, 
check that the fan operates normally.

6. Maintenance

6.1 Safeguards prior to inspec-

tion and maintenance

Before inspecting or servicing the fan, it 
must be switched off and disconnected 
from the electrical system. Safeguards 
must be taken to prevent the fan from re-
starting unintentionally.

6.2 Fan housing

As standard, the fan housing requires no 
maintenance other than cleaning.

If the housing is painted, the surface 
should be checked regularly and re-
paired where necessary.

6.3 Impeller

The impeller (rotor unit) is supplied with 
blade pitch factory adjusted to the re-
quired operating conditions (pressure 
and air flow) and actual fan speed. To en-
sure vibration-free operation, the impel-
ler has been carefully balanced in this po-
sition.

Vibration during operation is usually 
caused by dust or dirt accumulating on 
the hub and blades, and can normally be 
corrected by cleaning. Should this not be 
the case, technical assistance should be 
called in immediately as continued vi-
bration will shorten the service life of the 
blades and motor bearings.

6.4 Motor

Normally, only the motor bearings re-
quire maintenance. This should be per-
formed as described in the maintenance 
instructions for electric motors.

6.5 Detaching the motor

Before detaching the motor, disconnect 
the power supply to the fan. 

Remove rod from top of end plate. Loos-
en mount from cross supports and pull 
fan housing away from panel until mo-
tor is free of panel opening.
Now loosen mount from rails on base. 
Remove entire assembly (fan housing 
plus mount) from rails and lay aside on 
an even surface. 

Remove motor cable (pos. 12) from mo-
tor.
Remove impeller centre screw (pos. 01), 
centre disc (pos. 02) and hub cover (pos. 

Figure 3.  Fitting the sealing strip

Figure 4.  Fully installed diffuser

Содержание Novax

Страница 1: ...nts Novax ACL fans are supplied on pallets or skids enabling fork lifttransport The forks must be positioned beneath the base The unit must be set down as slow ly as possible on a soft surface Impacts vibrations and falls may cause imbal ance and deformation or damage to mo tor bearings 3 Storage Novax fans can withstand outdoor stor age for up to one month providing the packaging is intact After ...

Страница 2: ...them Push fan along cross supports towards panel until end plate and panel are in close contact Horizontally centre fan in relation to hole in panel Screw mount securely to cross supports Check position of fan in relation to hole in panel and adjust if necessary Check that end plate is in close contact with panel Secure fan in position with screws through guides and rails and through rails and bas...

Страница 3: ...abnormal sound oc curs 3 Check that the vibration level is nor mal Atoperatingspeed fanvibration must not exceed 7 mm s rms meas ured radially at two points with 90 offset and at the free shaft end of the motor Otherwise the fan must be re balanced Operation at vibration levels higher than 18 mm s rms is inadvisable if vi bration dampers have been used See ISO 2954 Requirements for instru ments fo...

Страница 4: ...ry adjusted using a special tool fixture to provide the out put required by the customer order on delivery If a different output is required it is pos sible to alter blade pitch This requires knowledge of the motor load and the max permissible blade pitch in relation to the motor rating in case of blade pitch increase Please contact Novenco before any such adjustment of blade pitch Special tools f...

Страница 5: ... to our catalogue material or computer pro grams designed to calculate specific sound emissions 9 Declaration of con formity In accordance with the European Ma chinery Directive 2006 42 EC Annex II A Manufacturer Novenco A S Address Industrivej 22 DK 4700 Naestved We hereby declare that axial flow fans type ACL 400 900 a fulfil the requirements contained in the following Directives on the condi ti...

Отзывы: