Installation and maintenance

for Novax fan type ACL

1. Application

2. Handling

2.1 Marking
2.2 Weight
2.3 Transport

3. Storage

4. Installation

4.1 Preparation
4.2 Installing the fan
4.3 Installing the acoustic diffuser (op-

tional)

4.4 Duct connection (alternative)
4.5 Electrical connection

5. Start-up

5.1 Before start-up
5.2 Motors with 

Δ

/Y starter

5.3 Start-up procedure

6. Maintenance

6.1 Safeguards prior to inspection and 

maintenance

6.2 Fan housing
6.3 Impeller
6.4 Motor
6.5 Detaching the motor
6.6 Fitting the motor
6.7 Blade adjustment
6.8 Fault finding

7. Testing functionality and 

operational readiness 

7.1 Periodic inspection

8. Sound

9. Declaration of conformity

1. Application

Novax ACL fans are compact, sturdy ax-
ial flow fans. They are designed for re-
placing existing fans for energy-saving 
reasons. The fans are capable of meeting 
everyday ventilation requirements un-
der normal conditions in all types of 
commercial and industrial buildings.

Please read the relevant sections of these 
instructions carefully before installing 
the product or performing any mainte-
nance. 

2. Handling

2.1 Marking

ACL fans are equipped with nameplate, 
stating Novenco’s name and address 
and providing information on product 
type, e.g. ACL 710/380, serial or order 
number, and fan speed. 

A motor nameplate with relevant motor 
data, including insulation class, is also 
provided.

2.2 Weight

The total weights of ACL axial flow fans 
are shown in table 1.

2.3 Transport

During transport, care must be taken to 
prevent water (e.g. rainwater) from en-
tering the motor or other sensitive com-
ponents.

Novax ACL fans are supplied on pallets 
or skids, enabling fork-lift transport. The 
forks must be positioned beneath the 
base. The unit must be set down as slow-
ly as possible on a soft surface. Impacts, 
vibrations and falls may cause imbal-
ance and deformation or damage to mo-
tor bearings.

3. Storage

Novax fans can withstand outdoor stor-
age for up to one month providing the 
packaging is intact. After removing the 
packaging, fans must be stored in a rain-
proof shelter.

If stored indoors under well-ventilated 
conditions with no risk of condensation, 
storage duration may be extended to six 
months. 

The storage place must not be exposed to 
vibrations, which may damage the mo-
tor bearings. If stored for longer than 
three months, the impeller should be 
turned regularly by hand.

4. Installation

Before installing the ACL fan in the ven-
tilation system, a suitable location must 
be identified and prepared. This will in-
clude removing the existing fan and clos-
ing off any holes capable of allowing 
false air to be sucked into the system. 

Note that it is of the utmost importance 
for the performance and sound level of 
the axial flow fan that the air flow is un-
impeded and free of eddies.
The required direction of air flow must 
also be taken into consideration when 
deciding location. The fan is provided 
with an arrow plate denoting the direc-
tion of air flow through the housing. The 
housing can only face one way. 

Sizes

Motor size

-80

-90

-100

-112

-132

-160

-180

Hub di

am

et

er

23

0,

 33

0 and 38

0

400

65

72

79

500

82

89

96

104

130

560

87

94

100

109

135

170

630

97

104

110

119

145

180

710

107

114

120

129

155

190

800

119

126

132

141

167

202

900

131

138

144

163

179

214

261

Motor type

-80

-90

-100

-112

-132

-160

-180

Motor weight

11

18

25

34

59

94

141

Table 1.  Total fan weights (incl. motor) and weights of motors alone [kg]

Содержание Novax

Страница 1: ...nts Novax ACL fans are supplied on pallets or skids enabling fork lifttransport The forks must be positioned beneath the base The unit must be set down as slow ly as possible on a soft surface Impacts vibrations and falls may cause imbal ance and deformation or damage to mo tor bearings 3 Storage Novax fans can withstand outdoor stor age for up to one month providing the packaging is intact After ...

Страница 2: ...them Push fan along cross supports towards panel until end plate and panel are in close contact Horizontally centre fan in relation to hole in panel Screw mount securely to cross supports Check position of fan in relation to hole in panel and adjust if necessary Check that end plate is in close contact with panel Secure fan in position with screws through guides and rails and through rails and bas...

Страница 3: ...abnormal sound oc curs 3 Check that the vibration level is nor mal Atoperatingspeed fanvibration must not exceed 7 mm s rms meas ured radially at two points with 90 offset and at the free shaft end of the motor Otherwise the fan must be re balanced Operation at vibration levels higher than 18 mm s rms is inadvisable if vi bration dampers have been used See ISO 2954 Requirements for instru ments fo...

Страница 4: ...ry adjusted using a special tool fixture to provide the out put required by the customer order on delivery If a different output is required it is pos sible to alter blade pitch This requires knowledge of the motor load and the max permissible blade pitch in relation to the motor rating in case of blade pitch increase Please contact Novenco before any such adjustment of blade pitch Special tools f...

Страница 5: ... to our catalogue material or computer pro grams designed to calculate specific sound emissions 9 Declaration of con formity In accordance with the European Ma chinery Directive 2006 42 EC Annex II A Manufacturer Novenco A S Address Industrivej 22 DK 4700 Naestved We hereby declare that axial flow fans type ACL 400 900 a fulfil the requirements contained in the following Directives on the condi ti...

Отзывы: