~ 4 ~ 

REV-225                                    

                                                                                  

NOVATEK-ELECTRO

 

Number and type of contacts  

1, C/O 

Weight, kg, not more then

 

0,11 

Overall dimensions 

H x B x L, mm 

90х65х36 

Purpose of device 

Control and distribution 
equipment

 

Typical operation 

Continued 

Protection rating of device

 

ІР20 

Electric shock protection class 

II 

Climatic version 

NC3.1 

Allowable soil level

 

III 

Overvoltage category 

II 

Nominal

 

voltage of insulation, V

 

450 

Nominal impulse withstanding voltage, kV

 

2,5 

Connecting plugs cross section of conductors, mm

2

 

– 4 

Tightening torque of terminal screws, N*m 

0,5 

Standard 35 mm DIN rail mounting 
Operating position - arbitrary

 

 

Table

 2

 

– C

haracteristics for the REV-225 output terminals  

 

 

Maximal current at 

U~=250V 

 

Max. power

 

Maximal Current at U

DC

=24V

  

cosφ = 1 

16 А 

4000 V

А 

384 W 

Commutation durability of contacts

 

  mechanical service durability, times, 

not less

 

 

electric durability 

16 

А 250 V АС, times, 

not less

 

1 000 000 

100 000 

 

3. INTENDED USE 
3.1. Preparation for operation 

3.1.1. Preparation for connection: 

 Unpack the product (we recommend to keep the original packing for the entire warranty period of the product 

operation); 

 Check the product for damage after transportation; in case of such damages detection, contact the supplier or 

manufacturer; 

 Carefully study the Operating Manual (

pay special attention to the connection diagram to power the

 

device

); 

 If  you  have  any  questions  regarding  the  installation  of  the  product,  please  contact  the  manufacturer  by 

telephone number indicated at the end of this Operating Manual

 

3.1.2 Device connection 

 

ATTENTION!

 

OUTPUT  CONTACTS  OF  LOAD  RELAY  ARE  NOT  DESIGNED  FOR  LOAD  COMMUTATION  IN  CASE  OF 

SHORT  CIRCUITS.  THEREFORE  THEY  SHOULD  BE  PROTECTED  BY  AUTOMATIC  CIRCUIT  BREAKERS 
(FUSES) WITH TRIPPING CURRENT NOT EXCEEDING 16 A OF CLASS B. 

 

ATTENTION! 

ALL CONNECTIONS MUST BE PERFORMED WHEN THE PRODUCT IS

 DE-ENERGIZED. 

 

Error when performing the installation works may damage the product and connected devices. 

 

To ensure the reliability of electrical connections you should use flexible (stranded) wires with insulation for voltage 
of no less than 450 

V, the ends of which it is necessary to be striped of insulation for 5±0.5 mm and tightened with 

bootlaces. 

The cross-section of the wire for connecting the protected equipment depends on the current (power) of 

the load. For example, at current 10A -  

is not less 1 mm

2

 

Wires fastening should exclude mechanical damage, twisting and abrasion of the wire insulation. 

 

IT  IS  NOT  ALLOWED  TO  LEAVE  EXPOSED  PORTIONS  OF  WIRE  PROTRUDING  BEYOND  THE  TERMINAL 

BLOCK. 

For reliable contact it is necessary to perform tightening of screws of removable terminal block with the force 

specified in Table 1. 

When reducing the tightening torque, the junction point is heated, terminal block may be melted and wire cane burn. If 

you increase the tightening torque, it is possible to have thread failure of terminal block screws or the compression of the 
connected wires. 

To improve operational properties of the device it is recommended to install the fuse or its analogue for 

1 A current in power supply circuit for REV-225. 

 

3.1.2.1

 Connect REV-225 according to the diagram indicated in Fig. 2. 

 

ATTENTION! LOAD TERMINALS ARE DESIGNED FOR MAXIMUM VOLTAGE OF 300 V;  

Содержание REV-225

Страница 1: ...ies with requirements ISO 9001 2008 Dear customer Company NOVATEK ELECTRO LTD thanks you for purchasing our products You will be able to use properly the product after carefully studying the Operating...

Страница 2: ...IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE DEVICE During operation and maintenance the regulatory document requirements must be met namely Regulations for Operation...

Страница 3: ...four buttons Automatic switching to summer winter time Liquid crystal display Operation mode for days off One channel Double module mounted on 35 mm DIN rail 1 1 REV 225 visual appearance and overall...

Страница 4: ...ice connection ATTENTION OUTPUT CONTACTS OF LOAD RELAY ARE NOT DESIGNED FOR LOAD COMMUTATION IN CASE OF SHORT CIRCUITS THEREFORE THEY SHOULD BE PROTECTED BY AUTOMATIC CIRCUIT BREAKERS FUSES WITH TRIPP...

Страница 5: ...Tuesday Sunday Load is ON Load is OFF Automatic mode Manual mode Holiday mode Weekends Sunrise Sunset Winter time Summer time Program setting Figure 3 The appearance of the display MENU button it is...

Страница 6: ...t operated by buttons for 2 minutes device will return to ENGLISH menu and backlight is switched off Pressing any buttons can switch on display and backlight 3 2 3 Main menu To enter the main menu pre...

Страница 7: ...e offset time of sunrise with buttons and press button Offset range is 2h Select the offset time of sunset with and press button Offset range is 2h Exit from the setting by pressing MENU Notes Long pr...

Страница 8: ...s 12 12 Exit from T ZONE the setting by pressing MENU button 3 2 5 Time and date setting Time setting Fig 9 shows the diagram of the time setting For setting time necessary Select menu DAT TIME and pr...

Страница 9: ...ting by pressing MENU button Notes Long press button more then 0 5s increase the numerical value quickly Long press button more then 0 5s decrease the numerical value quickly Summer winter time settin...

Страница 10: ...f holiday with and press button Set the end month of holiday with and press button Set the end day of holiday with and press button return to HOLIDAY menu Exit from the HOLIDAY mode press MENU button...

Страница 11: ...e setting by pressing MENU button 3 2 9 Reset to factory settings Press the four buttons MENU OK simultaneously for 3 seconds to reset automatically The device was restored to factory settings After t...

Страница 12: ...e 1 2 Visually check the integrity of the housing in case of detection of cracks and damages to remove the device from service and send for repair 3 If necessary wipe with cloth the front panel and th...

Отзывы: