NovaLynx Corporation_____________________________________________________________________________ 

 

 

200-WS-23 

Page 6 

Oct 2020 

 

5

 

CONNECTIONS 

The installer must provide cable that will connect the transmitter unit to the monitoring equipment. 
Use 4-conductor cable for the 200-WS-23 Wind Speed and Direction transmitter. Use 2-conductor 
cable for the 200-WS-23S Wind Speed Only transmitter. If the cable is shielded, connect the shield at 
the monitoring equipment end only. The wire gage of the cable depends on the length of cable and the 
applied loop voltage. Ensure the applied voltage is at least 8 volts at the transmitter circuit board at full 
scale (20mA) operation. 
 
The transmitter is provided with a green earth grounding wire which must be connected to protect the 
electronic circuitry. If the wire must be extended, use 18 AWG wire. 
 

 

Refer to Appendix A for wiring the 200-WS-23 Wind Speed and Direction transmitter 

 

Refer to Appendix B for wiring the 200-WS-23S Wind Speed Only transmitter 
 

1.

 

Remove the cover of the transmitter unit and set it aside. 

 

2.

 

Insert the wind speed sensor cable into the same gland as the green earth grounding wire. 
Provide some slack so that the wires can be connected without putting strain on the cable. 
Tighten the gland nut. 

3.

 

 Make sure there is a drip loop below the transmitter enclosure so that any moisture on the 
cable will not seep into the enclosure. This is particularly important since the seal around the 
grounding wire and cable will not be watertight. If a watertight seal is required, apply plumber's 
putty (not supplied) to the cable before tightening the gland nut. 

4.

 

Connect the anemometer wires as indicated in Appendix A or Appendix B. 

5.

 

Prepare the output cable by cutting back the outer jacket about 4 inches, then stripping the 
wire ends. Insert the output cable into the remaining gland until the jacket is visible inside the 
enclosure, then tighten the gland nut. Provide a drip loop for this cable also. 

6.

 

Wire the Wind Direction transmitter and record the wire colors 

a.

 

 Terminal 1 is the 8-30 Vdc input (+) 

Wire color _______ 

b.

 

 Terminal 2 is the 4-20 mA Wind Direction signal 

Wire color _______ 

7.

 

Wire the Wind Speed transmitter and record the wire colors 

a.

 

 Terminal 3 is the 8-30 Vdc input (+) 

Wire color _______ 

b.

 

 Terminal 4 is the 4-20 mA Wind Speed signal 

Wire color _______ 

8.

 

Disconnect power from your monitoring equipment before wiring the current loop 
transmitter(s). Ensure that the 4-20 mA channel(s) on the monitoring equipment are 
programmed appropriately. Connect and verify all wiring before restoring power to the 
monitoring equipment.  

9.

 

Secure the cables with cable ties as required to complete the installation. 
 

Содержание 200-WS-23

Страница 1: ...DOC 200 WS 23 UM 20201012 200 WS 23 User Manual Current Loop Wind Sensor 200 WS 23 Wind Speed Direction 200 WS 23S Wind Speed Only Phone 530 823 7185 Email nova novalynx com Website www novalynx com...

Страница 2: ...in the case of delicate or sensitive items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packaging P...

Страница 3: ...CONTENTS 1 FORWARD 4 2 INTRODUCTION 4 3 SPECIFICATIONS 5 4 INSTALLATION 5 5 CONNECTIONS 6 6 CALIBRATION 7 APPENDIX A Wind Speed and Direction Wire Diagram 8 APPENDIX B Wind Speed Only Wire Diagram 9 2...

Страница 4: ...power supply is not needed The driver circuitry is protected in a NEMA enclosure suitable for indoor or outdoor mounting The anemometer is a 200 WS 01B Wind Speed sensor that includes 40 of cable and...

Страница 5: ...200 WS 23S KM 4 20 mA 0 200 kph Loop supply voltage range Connection Operating temperature range NEMA enclosure dimensions Cable to user equipment Measurement range Speed Constant Transducer type Spe...

Страница 6: ...Tighten the gland nut 3 Make sure there is a drip loop below the transmitter enclosure so that any moisture on the cable will not seep into the enclosure This is particularly important since the seal...

Страница 7: ...n of the monitoring equipment Disconnect the 200 WS 23 or 200 WS 23S from the device before doing these tests 1 Use a 4 20 mA signal generator to feed 6 mA into the selected channel on your monitoring...

Страница 8: ...2 3 4 GND WS REF REF EXC WD IMPORTANT CONNECT EARTH GROUND 200 WS 02F GREEN RED BLACK WHITE SHIELD BROWN 8 30 Vdc Wind Direction Signal 8 30 Vdc Wind Speed Signal 4 20 mA Input 8 30 Vdc 1 Signal Out...

Страница 9: ...ogger Power WIRING DIAGRAM 200 WS 23S JDC 9 03 2020 860 0029 01 1 2 3 4 GND WS REF REF EXC WD IMPORTANT CONNECT EARTH GROUND 200 WS 01B RED SHIELD BLACK 8 30 Vdc Wind Speed Signal 4 20 mA Input 8 30 V...

Отзывы: