background image

NovaLynx Corporation________________________________________________________________________________ 

 

 

 
200-WS-21-A 

Page 12 

February 2021 

 

7

 

CONNECTIONS 

Please refer to the connection diagram in 

Appendix A

 of this manual.  

The anemometer and AC adapter (200-WS-21P, sold separately) are supplied with connectors that fit 
the ¼" spade terminals on the Wind Alarm circuit board. Extra connectors are provided for connecting 
an earth ground and alarm relay connections. You will need a crimp tool or heavy duty pliers to make 
these connections. You will also need to provide insulated wire for the earth ground and relay 
connections. Stranded wire (14 to 16 AWG) is preferred. 

 

Standard Wire  

 Wire Connector with an 

Connector 

 

 

extra lug for Earth Ground

 

 

7.1

 

Anemometer Connection 

 

Route the anemometer cable through the gland fitting and into the case. Connect the earth ground 
connector with the tab facing down, to make room for the other connections. Attach the red and black 
wires as indicated on the drawing (Appendix A). 

Prepare a suitable length wire with a standard wire connector, and connect it to the lug on the earth 
ground connector. Route the other end of this wire to a good earth ground – an electrical box with an 
earth connection or a metal cold water pipe that actually enters the ground. Failure to provide a ground 
may cause erratic operation and make the system more vulnerable to damage from nearby lightning 
strikes

7.2

 

Power Connection 

 

NOTE:

 It is good practice to program the set points and delays, and then operate the system using the 

visible LEDs and buzzer as alarm indicators for testing the system before connecting the relays to your 
external equipment.  

Route the wiring from the AC Adapter or other power supply through the cable gland and attach the 
positive terminal (marked with red shrink wrap or a white stripe on one lead) to the ACin / DCin 
terminal. Connect the ground wire to the ACin / DCgnd terminal. The power input accepts 12 volts AC 
or DC. 

NovaLynx recommends connecting the AC Adapter to an outlet with a surge suppressor. Power strips 
with surge suppressors are often used to protect computer equipment and are readily available. 

Check your connections to make sure there are no stray wires that could cause a short circuit. Plug in 
your power supply. The green power LED should turn on and the word "Wind:" will be displayed. If you 
see the word " Temp:" instead of "Wind:" then the DIP switches are in the wrong position. Refer to the 
"DIP Switch Settings" section of the manual to correct this situation. 

Содержание 200-WS-21-A

Страница 1: ...DOC 200 WS 21 A UM 20210209 200 WS 21 A User Manual Dual Set Point Wind Alarm Phone 530 823 7185 Email nova novalynx com Website www novalynx com...

Страница 2: ...ions in the case of delicate or sensitive items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packag...

Страница 3: ...2 3 CLEAR Button 7 4 2 4 GO Button 7 4 3 Program Alarm Thresholds 7 4 4 Program Alarm Delays 7 4 5 DIP Switch Settings 8 5 ANEMOMETER INSTALLATION 8 5 1 Anemometer Siting Considerations 8 5 2 Anemomet...

Страница 4: ...ts and the maximum wind speed value are stored in non volatile memory DIP switch settings select the units mph or kph and enable disable the buzzer Programmable Features Alarm Set Point Wind speed thr...

Страница 5: ...connectors supplied Relay specifications Form C SPDT N O and N C Contact rating 3A 24Vdc 115 VAC Alarm ON OFF delay range 0 to 99 seconds Timing accuracy 2 Measurement range 0 to 99 9 Integration int...

Страница 6: ...on Refer to the DIP Switch Settings section of the manual to correct this situation 4 2 Menu Navigation The programming buttons are below the display 4 2 1 MENU Button Press the MENU button One of the...

Страница 7: ...menu 1 Press GO until the display shows the operating mode screen see GO Button above 2 Press MENU to bring up one of the three sub menu displays 3 Press UP or DOWN to reach the Wind Alarms sub menu...

Страница 8: ...per hour MPH Set the switch ON for kilometers per hour KPH 3 The Tu switch sets the temperature units This is not relevant to the wind alarms so it doesn t matter how this switch is set 4 The Si silen...

Страница 9: ...e mounted at the top of a mast the NovaLynx 200 153 Mounting Arm sold separately can be used to mount the sensor to the side The supporting mast or tower should be properly grounded to minimize lightn...

Страница 10: ...sor 1 Tighten the mounting screws if necessary do not strip the threads in the plastic base of the sensor 2 Spin the anemometer cup assembly It should turn freely A drop of light machine oil e g fishi...

Страница 11: ...ns inside the controller box for placing screws It will be necessary to remove the circuit board to access these points After mounting the case to your wall or panel install the small caps that are in...

Страница 12: ...to a good earth ground an electrical box with an earth connection or a metal cold water pipe that actually enters the ground Failure to provide a ground may cause erratic operation and make the syste...

Страница 13: ...ally Be sure you have programmed the Wind Alarm to the settings you desire and the system is operating properly before you connect power to your external devices 8 ALARM FUNCTIONS The Wind Alarm contr...

Страница 14: ...MPER Menu Up Dn Clr Go PROGRAMMING BUTTONS MODE WIND UNITS TEMP UNITS BUZZER WIND MPH DEG F BUZZ TEMP KPH DEG C SILENT ON OFF Wt Wu Tu Si DIP SETTINGS DUAL SET POINT WIND ALARM 200 WS 21A Alarms OFF R...

Отзывы: