NovaLynx Corporation________________________________________________________________________________
200-WS-21-A
Page 7
February 2021
4.2.3
CLEAR Button
The CLEAR button performs the following actions:
1.
If the user is in an editable field, the field will be set to the lowest possible value.
2.
If the user is viewing the Max Wind Speed, the recorded value will be erased.
3.
If the unit is alarming, all delay counters will be cleared.
4.2.4
GO Button
Press GO from any menu to return to
operating mode.
If the unit is already in operating mode,
press GO to pause the system and disable
all alarms.
IMPORTANT:
Whenever the controller is turned on it is in Operating Mode and the alarms are
active. If the system was in Paused Mode before a power failure, it will restart in Operating Mode
when power is restored.
4.3
Program Alarm Thresholds
To begin, navigate to the Wind Alarms menu:
1.
Press GO until the display shows the operating mode screen (see GO Button, above).
2.
Press MENU to bring up one of the three sub-menu displays.
3.
Press UP or DOWN to reach the Wind Alarms sub-menu.
Wind Alarms(mph)
1: 25 2: 50
Wind Alarms(mph)
1: 25 2: 50
Wind Alarms(mph)
1: 25 2: 50
MENU
MENU
MENU
MENU
Wind Alarms Menu
Program channel #1
Program channel #2
4.
Press MENU again. A blinking block cursor will appear on the Channel #1 value.
Press UP or DOWN to change the wind speed threshold.
5.
Press MENU again. The blinking block cursor will move to Channel #2.
Press UP or DOWN to change the value.
6.
Press MENU again to complete programming the Wind Alarms.
7.
Press GO to return to the operating mode screen.
4.4
Program Alarm Delays
To begin, navigate to the Alarm Delays menu:
1.
Press GO until the display shows the operating mode screen (see GO Button, above).
2.
Press MENU to bring up one of the three sub-menu displays.
3.
Press UP or DOWN to reach the Alarm Delays sub-menu.
Wind: 0.0 (mph)
1: 25 2: 50
GO
System Paused
GO to resume
Operating Mode
Paused Mode
Alarm Delays (s)
ON: 5 OFF: 5