Notifier NOTI-FIRE-NET Скачать руководство пользователя страница 3

Precau-Lg.p65    01/18/2000

WARNING 

Several different sources of power can be con-

nected to the fire alarm control panel.  Disconnect all sources
of power before servicing.  Control unit and associated equip-
ment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.

CAUTION - 

System Reacceptance Test after Software

Changes.  To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific soft-
ware.  Reacceptance testing is required after any change, ad-
dition or deletion of system components, or after any modifica-
tion, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvert-
ently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 de-
vices, must also be tested and proper system operation veri-
fied.

This system  

meets NFPA requirements for operation at

0-49° C/32-120° F

 

 and at a relative humidity of 85% RH (non-

condensing) at 30°

 

C/86° F.  However, the useful life of the

system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity.  Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nomi-
nal room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate

 for all initiating and

indicating device loops.  Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices,

 this system may

operate erratically or can be damaged when subjected to light-
ning-induced transients.  Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.  

Overhead or outside

aerial wiring is not recommended, due to an increased sus-
ceptibility to nearby lightning strikes.  Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.

Disconnect AC power and batteries

 prior to removing or in-

serting circuit boards.  Failure to do so can damage circuits.

Remove all electronic assemblies

 prior to any drilling, filing,

reaming, or punching of the enclosure.  When possible, make
all cable entries from the sides or rear.  Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, and printed circuit board location.

Do not tighten screw terminals

 more than 9 in-lbs.

Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.

Though designed to last many years, 

system components

can fail at any time.  This system contains static-sensitive
components.  Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are re-
moved from the body.  Use static-suppressive packaging
to protect electronic assemblies removed from the unit.

Follow the instructions

 in the installation, operating, and

programming manuals.  These instructions must be followed
to avoid damage to the control panel and associated
equipment.  FACP operation and reliability depend upon
proper installation by authorized personnel.

Adherence to the following will aid in problem-free
installation with long-term reliability:

WARNING:

 This equipment generates, uses, and can

radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications.  It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment.  Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.

Canadian Requirements

This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.

FCC Warning

Installation Precautions

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание NOTI-FIRE-NET

Страница 1: ...Document 50257 E 7 5 01 Rev E PN 50257 E ECN 01 146 NOTI FIRE NET Manual Technical Manuals Online http www tech man com firealarmresources com...

Страница 2: ...proper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined le...

Страница 3: ...ct AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the e...

Страница 4: ...ons 13 Configuration Definitions 13 Characteristic Impedance In a Point to Point Configuration 14 Characteristic Impedance In a Bus Configuration 15 Terminating Point To Point and Bus Configurations 1...

Страница 5: ...ons port The network has the ability to send acknowledge signal silence drill and reset commands to the AFP 200 or AFP 300 AFP 400 AFP 200 or AFP 300 AFP 400 zones may be used to activate other networ...

Страница 6: ...s onto the NRT NET card to complete the network interface Each NRT or NCS requires a network node address The Repeaters RPT boost data signals between network nodes extending communication distances T...

Страница 7: ...a fiber optic segment The following paragraphs detail each procedure Twisted Pair Circuits The length of cable for each segment in the system must fall within the range specified in Table 2 If the dis...

Страница 8: ...100 Low 1200 2000 N A BRAND REX 93782 01 16 AWG 1 Pair Shielded Contact Manufacturer High 1 1400 1 100 Low 1200 2000 N A Genesis GJ 854020514 14 AWG 1 Pair Shielded FPLP NEC Article 760 High 1 400 1 1...

Страница 9: ...t Number and Number of Gauges Conductors Manufacturer s Specifications Data Threshold All Nodes And Or Repeaters On A Cable Segment Permissible Single Twisted Pair Range In Feet For Each Cable Segment...

Страница 10: ...ave to travel from one end of the network to the other end refer to Figure 2 The length is influenced by the total number of MIB NAM 232 RPT devices and medium along the circuit path Refer to Figure 3...

Страница 11: ...A B C or D When employing the SIB NET a MIB W MIB WF or MIB F is required The SIB 2048A may also be used as a NOTI FIRE NET interface with the NAM 232 Initiating Devices Initiating device requirement...

Страница 12: ...to the right of the break However the fragment to the right of the break can receive information from the fragment to the left of the break Figure 5 Fiber Optic Style 4 System Break Note A wire to wi...

Страница 13: ...optic cable or mixed media wire and fiber Figure 6 Style 7 Configurations Configuration Definitions The following configurations are defined Point To Point Configuration A point to point wiring config...

Страница 14: ...r network with more than two nodes Terminating resistors are only needed for the first and last nodes of the bus configuration all other terminating resistors must be removed In a bus configuration mo...

Страница 15: ...upport point to point connections to the remaining buildings in the system Figure 9 Combination Wiring Terminating Point To Point and Bus Configurations Both point to point and bus configurations requ...

Страница 16: ...R70 These point to point circuit segments are terminated at each node repeater A bus circuit spans multiple nodes repeaters with a terminating resistor at each end of the circuit segment A point to po...

Страница 17: ...rations for point to point and bus wire configurations In the examples that follow the MIB WF or NAM 232W may be used in place of the MIB W Point To Point Configuration In a point to point configurati...

Страница 18: ...s through switch SW3 is ON allowing the left node to provide ground fault detection for the two point to point wire connections on the left and right of the repeater The Port A switch on the right MIB...

Страница 19: ...etection along the bus The primary difference is that one node can provide ground fault detection for multiple nodes along the bus refer to EXAMPLE 1 and 2 Note Refer to the Network Adaptor Module NAM...

Страница 20: ...ft separate ground fault detection circuits must be fed through The node second from the right continues to provide ground fault detection up to the RPT W Port B and must be an AFP 200 AFP 300 AFP 400...

Страница 21: ...ng with the supplied tie wrap at each end of the cylinder 4 If used repeat for the remaining twisted pair s on a MIB W second port Figure 19 Installation of the Ferrite Cylinder on the NRT NCS Install...

Страница 22: ...22 NOTI FIRE NET PN 50257 E 7 5 01 Notes Technical Manuals Online http www tech man com firealarmresources com...

Страница 23: ...ting constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in a...

Страница 24: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www notifier com Technical Manuals Online http www tech man com firealarmresources com...

Отзывы: