Notifier NOTI-FIRE-NET Скачать руководство пользователя страница 11

NFPA Style 4 Configurations

NOTI•FIRE•NET™  PN 50257:E  7/5/01

11

NRT

 

NRT requirements consist of an NRTT-M17W, NRTT-M17F, NRTT-M17WF, NRTT-M21W, 
NRTT-M21F, or NRTT-M21WF: each consists of a computer with wire and/or fiber 
configuration, a MON-17B or MON-21 monitor, and a PCLB-4.

NCS

 

NCS requirements consist of an NCS-M17W, NCS-M17F, NCS-M17WF, NCS-M19W, 
NCS-M19F, or NCS-M19WF:  each consists of a computer with wire and/or fiber 
configuration, a MON-19, and the PCLB-5.

INA

 

INA requirements consist of the MIB-W, or MIB-F, or MIB-WF.  These requirements include 
the ADP-4RM and the ABF-4 with AKS-1, or CAB-3, or ABS-4D and MPS-24A or MPS-24B 
with batteries.

AFP-200 and AFP-300/AFP-400

 

Fire panel requirements consist of the AFP-200 or AFP-300/AFP-400, which includes the 
motherboard, power supply, cabinet, and NAM-232W or NAM-232F.

AM2020/AFP1010

AM2020/AFP1010 requirements consist of the BE-2020N/1010N and SIB-NET.  These 
requirements include the MPS-24A and LIB-200, LIB-200A, or LIB-400, CAB-3 (A,B,C, or 
D).  When employing the SIB-NET, a MIB-W, MIB-WF, or MIB-F is required.  The 
SIB-2048A may also be used as a 

NOTI•FIRE•NET™

 interface with the NAM-232.

Initiating Devices

Initiating device requirements consist of the monitor modules, manual pull stations, heat 
detectors, and intelligent detectors.

NFPA 72 Local Fire Alarm Systems

A control module is installed on Signal Loop Circuit (SLC) 1 in every AM2020/AFP1010 
network and set to module address 96.  Refer to AM2020/AFP1010 documentation for a more 
detailed account of this installation.

NFPA 72 Central Station and Proprietary Fire Alarm Systems Protected Premises Units

A NIB-96 network interface board connected to a non-networked AM2020/AFP1010 receiving 
unit.

NFPA Style 4 Configurations

NOTI•FIRE•NET™

 is capable of communicating using an NFPA Style 4 SLC (refer to Figure 

4).  Under this style of operation, a single open, wire-to-wire short, wire-to-wire short and open, 
wire-to-wire short and ground, or open and ground results in fragmentation of the network.  A 
single ground does not affect communication, but is detected.  Each fragment of the network 

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание NOTI-FIRE-NET

Страница 1: ...Document 50257 E 7 5 01 Rev E PN 50257 E ECN 01 146 NOTI FIRE NET Manual Technical Manuals Online http www tech man com firealarmresources com...

Страница 2: ...proper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined le...

Страница 3: ...ct AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the e...

Страница 4: ...ons 13 Configuration Definitions 13 Characteristic Impedance In a Point to Point Configuration 14 Characteristic Impedance In a Bus Configuration 15 Terminating Point To Point and Bus Configurations 1...

Страница 5: ...ons port The network has the ability to send acknowledge signal silence drill and reset commands to the AFP 200 or AFP 300 AFP 400 AFP 200 or AFP 300 AFP 400 zones may be used to activate other networ...

Страница 6: ...s onto the NRT NET card to complete the network interface Each NRT or NCS requires a network node address The Repeaters RPT boost data signals between network nodes extending communication distances T...

Страница 7: ...a fiber optic segment The following paragraphs detail each procedure Twisted Pair Circuits The length of cable for each segment in the system must fall within the range specified in Table 2 If the dis...

Страница 8: ...100 Low 1200 2000 N A BRAND REX 93782 01 16 AWG 1 Pair Shielded Contact Manufacturer High 1 1400 1 100 Low 1200 2000 N A Genesis GJ 854020514 14 AWG 1 Pair Shielded FPLP NEC Article 760 High 1 400 1 1...

Страница 9: ...t Number and Number of Gauges Conductors Manufacturer s Specifications Data Threshold All Nodes And Or Repeaters On A Cable Segment Permissible Single Twisted Pair Range In Feet For Each Cable Segment...

Страница 10: ...ave to travel from one end of the network to the other end refer to Figure 2 The length is influenced by the total number of MIB NAM 232 RPT devices and medium along the circuit path Refer to Figure 3...

Страница 11: ...A B C or D When employing the SIB NET a MIB W MIB WF or MIB F is required The SIB 2048A may also be used as a NOTI FIRE NET interface with the NAM 232 Initiating Devices Initiating device requirement...

Страница 12: ...to the right of the break However the fragment to the right of the break can receive information from the fragment to the left of the break Figure 5 Fiber Optic Style 4 System Break Note A wire to wi...

Страница 13: ...optic cable or mixed media wire and fiber Figure 6 Style 7 Configurations Configuration Definitions The following configurations are defined Point To Point Configuration A point to point wiring config...

Страница 14: ...r network with more than two nodes Terminating resistors are only needed for the first and last nodes of the bus configuration all other terminating resistors must be removed In a bus configuration mo...

Страница 15: ...upport point to point connections to the remaining buildings in the system Figure 9 Combination Wiring Terminating Point To Point and Bus Configurations Both point to point and bus configurations requ...

Страница 16: ...R70 These point to point circuit segments are terminated at each node repeater A bus circuit spans multiple nodes repeaters with a terminating resistor at each end of the circuit segment A point to po...

Страница 17: ...rations for point to point and bus wire configurations In the examples that follow the MIB WF or NAM 232W may be used in place of the MIB W Point To Point Configuration In a point to point configurati...

Страница 18: ...s through switch SW3 is ON allowing the left node to provide ground fault detection for the two point to point wire connections on the left and right of the repeater The Port A switch on the right MIB...

Страница 19: ...etection along the bus The primary difference is that one node can provide ground fault detection for multiple nodes along the bus refer to EXAMPLE 1 and 2 Note Refer to the Network Adaptor Module NAM...

Страница 20: ...ft separate ground fault detection circuits must be fed through The node second from the right continues to provide ground fault detection up to the RPT W Port B and must be an AFP 200 AFP 300 AFP 400...

Страница 21: ...ng with the supplied tie wrap at each end of the cylinder 4 If used repeat for the remaining twisted pair s on a MIB W second port Figure 19 Installation of the Ferrite Cylinder on the NRT NCS Install...

Страница 22: ...22 NOTI FIRE NET PN 50257 E 7 5 01 Notes Technical Manuals Online http www tech man com firealarmresources com...

Страница 23: ...ting constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in a...

Страница 24: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www notifier com Technical Manuals Online http www tech man com firealarmresources com...

Отзывы: