background image

Page 2 of 2 — DN-5331 • 08/19/04

Network Adapter Module Fiber (NAM-232F)

LED INDICATORS

• RECON: This yellow LED should remain off at all

times when the network is operating properly. If it
illuminates periodically, check the network media and
thresholds using the MET-1 (Media Evaluation Tool).

• STATB: This yellow LED illuminates when the NAM-

232 is not receiving valid data from NOTI•FIRE•
NET™ on Port “B”.

• RCVDB: This green LED illuminates when the NAM-

232 is receiving data from the NOTI•FIRE•NET™ on
Channel “B” (wire or fiber connection).

• B HI (NAM-232W only): This green LED illuminates

to indicate the NAM-232W Channel “B” is set for
high threshold (N/A on NAM-232F).

• A HI (NAM-232W only): This green LED illuminates

to indicate the NAM-232W Channel “A” is set for
high threshold (N/A on NAM-232F).

• RCVDA: This green LED illuminates when the NAM-

232 is receiving data from the NOTI•FIRE•NET™ on
Channel “A” (wire or fiber connection).

• STATA: This yellow LED illuminates when the NAM-

232 is not receiving valid data from NOTI•FIRE•NET™
on Port “A”.

• PULSE: This green LED illuminates when the NAM-

232 is transmitting data to NOTI•FIRE•NET™.

• TROUBLE: This yellow LED indicates that the NAM-

232 is not functioning.

• TXD:  This green LED indicates when the NAM-232

is transmitting data over the EIA-232 interface to the
AFP-200, AFP-300, AFP-400 FACP.

• RXD: This green LED indicates when the NAM-232

is receiving data over the EIA-232 interface from the
AFP-200, AFP-300, AFP-400 FACP.

NETWORK CONFIGURATION
EXAMPLE

• NFPA Style 4 & 7 network operation.

FEATURES,

 continued

NAM-232F: Network Adapter Module (Fiber)

• Supports fiber optic medium.
• Transmission rate of 312.5 Kbaud.
• DIP switch selectable single-port or dual-port monitoring.
• DIP switch selectable network drill option.
• Data is regenerated at each node.
• Data is immune to all environmental noise.
• Diagnostic LED indicators.
• Optical isolation prevents ground loops.
• High level of data security.
• NFPA Style 4 & 7 network operation.

MOUNTING

The NAM-232 normally mounts inside the back of the control
panel cabinet. The NAM-232 can also mount in the cabinet of
other nodes on the network, provided that the distance be-
tween the NAM-232 and its host node is not greater than 50
feet (15.24 m).

GENERAL NOTES:

1) AFP-200, AFP-300, and AFP-400 lose local CRT capability
when connected to the NAM-232.

2) AFP-200 system loses local printer and CRT capability when
connected to the NAM-232.

5331conf.wmf

5331fibr.wmf

*NOTE, 

NOTI•FIRE•NET

™:

NOTI•FIRE•NET™ version 3.0 network will not support the
ONYX™ Series of products (NFS-640, NFS-3030, NCA, NCS-
W/F-ONYX, or NWS). NOTI•FIRE•NET™ version 4.0 network will
not support the INA, NFS-3030, or NWS. NOTI•FIRE•NET™ ver-
sion 5.0
 network will not support the INA.

*NOTE, NAM-232 FIRMWARE UPGRADE:

The NAM-232 comes from the factory with firmware for a version
3.0 network. To upgrade the NAM-232 for a version 4.0 network,
order NROM-NAM4.0M. To upgrade the NAM-232 for a version
5.0
 network, order NROM-NAM5.0M.