Power Supply Unit

 

 

HLS PS Series

 

 

HLSPS25-XP and HLSPS50-XP

 

 
 
 

 

 
 
 
 
 
 

User manual

 

 

 
 

 
 
 
 
 
 
 
 
 
 

Information in this document is subject to change without notice

 

8 APRIL 2010 

MN-DT-1305I_B 

Содержание HLSPS25-XP

Страница 1: ...Power Supply Unit HLS PS Series HLSPS25 XP and HLSPS50 XP User manual Information in this document is subject to change without notice 8 APRIL 2010 MN DT 1305I_B...

Страница 2: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 2...

Страница 3: ...HLS PS for damage 4 1 2 Pre installation check list 5 1 3 Transient protection 5 1 4 Cleaning 5 1 5 Back Box HLS PS fixing 6 2 Functions and indicators 7 2 1 HLS PS25 and HLS PS50 characteristics 8 2...

Страница 4: ...lity of any supplied order items follow the procedure bellow 1 If after removing the HLS PS Series a visual inspection reveals that it has been damaged you MUST NOT continue with the installation but...

Страница 5: ...may operate erratically or can be damaged if subjected to lightning induced transients This equipment contains transient protection devices Although no system is immune from lightning transients and i...

Страница 6: ...y in the required position against the wall and mark the position of the fixing holes while ensuring the panel is level The drawing below shows the position of the fixing holes at the back box Do NOT...

Страница 7: ...ions and indicators FRONT PANEL 1 2 FUS BAT FAULT LOW BAT NO BAT BAT TEST BAT CH BAT DIS IN ALARM 321087 CPU MAX LEGEND ON FAULT MAIN SUPPLY FAULT BATTERY FAULT BATTERY CHARGER FAULT OUTPUT 1 FAULT OU...

Страница 8: ...tandard module control which supervises the entire power supply HLS PS25 and HLS PS50 power supplies provide 2 5 Amp and 5 Amp respectively and 300mA to 600mA of them are dedicated to charge batteries...

Страница 9: ...control unit Any fault has a delay of 30 seconds from the fault signal to fault relay confirmation except when there is a mains AC loss which will be indicated after an 8 minute delay to avoid faults...

Страница 10: ...arm input to disable momentarily the battery charger and be able to supply 300 600mA from battery load to the outputs For this it is necessary to link both IN ALARM terminals by means of a jumper or s...

Страница 11: ...n case batteries fail a Battery fault will be reported The HLS PS Series will supervise automatically the battery each 3 hours If the battery load is in normal condition the fault signal will disappea...

Страница 12: ...e fault relay signal and the FAULT led do not activate until the power supply fault remains for more than 8 minutes BATTERY FAULT Led Battery is not detected by the Control Unit or the battery voltage...

Страница 13: ...will not be earth fault supervision Earth fault solution Make sure that there are no links between Earth and Output 1 and 2 y OVERLOAD Led Indicates that the equipment exceeds the maximum current 5 A...

Страница 14: ...g both terminals with a jumper or short circuit this input allows the battery charger momentary disablement in order to provide extra 300 600 mA to the outputs Battery load current 300 mA 7 Amp hour 6...