background image

N500-05-00                                                                                              2                                                                                              I56-054-09R

WARNING

FSH-751 is 

not 

designed to operate in explosive environments.

Wiring Instructions

All  wiring  must  be  installed  in  compliance  with  the 
National  Electrical  Code,  applicable  local  codes,  and  any 
special requirements of the Authority Having Jurisdiction. 
Proper wire gauges should be used. The installation wires 
should  be  color-coded  to  limit  wiring  mistakes  and  ease 
system troubleshooting. Improper connections will prevent 
a system from responding properly in the event of a fire.

Remove  power  from  the  communication  line  before 
installing detectors.

All  wiring  must  conform  to  applicable  local  codes,  ordi-
nances, and regulations.

1.  Wire the sensor base per the wiring diagram, please see Figure 1.
2.  Set the desired address on the sensor address switches. 

NOTE:

 

Some panels support extended addressing. In order to set the sensor 
above address 99 on compatible systems, carefully remove the stop on 
the upper rotary switch with thumb as shown in Figure 2.

3.  Insert 5-wire connector on mounting base into 5-pin connector on the 

unit. Install the detector into the sensor base. Push the detector into the 
base while turning it clockwise to secure it in place. (Please see Figure 
5 and INSTALLING DETECTOR INTO BASE on page 4 for specific direc-
tions.

4.  After all detectors have been installed, turn on the auxiliary power sup-

ply, then apply power to the control unit and activate the communica-
tion line.

5.  Test  the  detector(s)  as  described  in  the 

TESTING

  section  of  this 

manual.

CAUTION

Dust cover must be removed before the detector can sense smoke. 

Testing

Before testing, notify the proper authorities that the system 
is undergoing maintenance, and will temporarily be out of 
service. Disable the system to prevent unwanted alarms.

All detectors must be tested after installation and periodi-
cally thereafter. Testing methods must satisfy the Authority 
Having  Jurisdiction  (AHJ).  Detectors  offer  maximum  per-
formance when tested and maintained in compliance with 
NFPA 72. 

The sensor can be tested in the following ways:

A. Functional:  Magnet  Test  (P/N  M02-04-01  or  M02-09-

00)

 

     This  detector  can  be  functionally  tested  with  a  test  magnet.  The  test 

magnet electronically simulates smoke in the sensing chamber, testing 
the detector electronics and connections to the control panel.

     1.   Hold the test magnet in the magnet test area as shown in Figure 3.
     2.   The detector should alarm the panel. Two LEDs on the detector are 

controlled  by  the  panel  to  indicate  sensor  status.  Coded  signals, 
transmitted from the panel, can cause the LEDs to blink, latch on, 
or latch off. Refer to the control panel technical documentation for 
detector LED status operation and expected delay to alarm.

B. Smoke Entry: Aerosol Generator

 

     Aerosol generators for smoke entry testing are available from a number 

of  third  party  manufacturers  (e.g.,  Gemini  Scientific).  Following  the 
manufacturer’s instructions, apply aerosol until the panel alarms.

A detector that fails any of these tests should be retested. 
If the detector still fails any test, have its filter replaced (see 
instructions below) and retested. Finally, if the detector con-

Figure 1. Wiring diagram:

NOTIFIER CONTROL PANEL

AUX.

POWER

SUPPLY

+

+

AUX+

AUX–

AUX+

AUX–

2(–)

3(RA)

4(S)

1(+)

1(+)

2(–)

3(RA)

4(S)

N500-05-00                                                                                              3                                                                                              I56-054-09R

A78-1253-06

Figure 2. Rotary decade address switches:

Figure 3. Test magnet position:

Figure 4. Replacing the filter cover:

tinues to fail after replacing the filter, it must be returned for 
repair or replacement.

When  testing  is  complete,  restore  the  system  to  normal 
operation and notify the proper authorities that the system 
is back in operation.

Cleaning

The unique design of the FSH-751 eliminates the need for 
typical detector cleaning. The only maintenance necessary 
is replacing the filter, which is signaled by a trouble condi-
tion at the panel (see below).

The  FSH-751  smoke  detector  has  been  designed  to  maxi-
mize  the  amount  of  time  before  maintenance  is  required. 
The  detector  utilizes  a  replaceable  filter  that  may  become 
clogged  over  time.  The  detector  monitors  itself  to  insure 
that  the  filter  has  not  become  clogged.  Because  environ-
mental conditions can vary significantly, the amount of time 
before maintenance could vary significantly as well. To fully 
understand the maintenance requirements of the FSH-751 in 
its installed location, it is recommended that the following 
test program be conducted.
1. Install the FSH-751 detector in the desired location.

2. Connect the detector to the fire alarm control panel.
3. Maintain  a  record  for  at  least  90  days  of  any  mainte-

nance performed on or required by the detector.

4. At the end of the test period, use the record to develop 

and  schedule  maintenance.  The  FSH-751  should  be 
serviced at regular intervals to insure that the fire alarm 
system provides continuous protection.

Replacing the Filter

IMPORTANT:

                When the filter becomes too clogged to draw adequate air into 

the unit, power is automatically cut from the detector, sending 
a trouble signal to the fire control panel. After 5 minutes, power 
is restored to the detector for 72 hours. After 72 hours, power is 
cut again and the detector will remain off-line until the filter is 
replaced. 

Note: The unit has two filters. The replaceable filter is inside the cover. A 
permanent filter is mounted to the unit.

Alignment marks are 

provided on the cap 

and top of the perma-

nent filter.

www.PDF-Zoo.com

Отзывы: