Figure 5: Installing detector into base:

1. Grasp  the  housing  with  one  hand  and  the  cover  with 

the other. Turn the cover counterclockwise fully (approx. 
30 degrees) and remove cover by pulling it away from 
detector unit (see Figure 4).  

2. Replace with new filter and cover assembly.

 

The cover 

is keyed so it fits in place only one way. Turn the cover 
clockwise until it stops.

    

NOTE:

  The  base  is  equipped  with  an  optional  tamperproof 

feature which can be used to prevent unintentional removal 
of the unit while replacing the filter.

If a clogged filter was the cause of the trouble condition, 
normal  detector  operation  should  resume  automatically 
within  five  minutes.  If  the  trouble  condition  persists,  the 
detector must be returned for repair or replacement.

Installing Detector Into Base

1. Align the detector at a right angle to the base, with the 

five  wires  and  connectors  adjacent  to  the  connector 
receptacle as shown in Figure 5.

2. Plug the wired connector into the receptacle.
3. Rotate the detector into the base, making sure detector 

and base keyed fit is lined up. Turn the detector clock-
wise until it snaps into place.

IMPORTANT:

  FSH-751  will  only  operate with B710HD/ 

B524FTXE Mounting Base.

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful inter-
ference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note:  This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These 
          limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and 
          can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio 
          communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harm-
          ful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to 
          correct the interference by one or more of the following measures:
           

– Reorient or relocate the receiving antenna.

           

– Increase the separation between the equipment and receiver.

           

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

           

– Consult the dealer or an experienced radio/TV technician for help.

Please refer to insert for the Limitations of Fire Alarm Systems

N500-05-00                                                                                              1                                                                                              I56-054-09R

Notifier, 12 Clintonville Rd., Northford, CT 06472-1653  Phone: (203)484-7161

Before Installing

This detector must be installed in compliance with the con-
trol panel system installation manual. The installation must 
meet the requirements of the Authority Having Jurisdiction 
(AHJ).  Detectors  offer  maximum  performance  when 
installed  in  compliance  with  the  National  Fire  Protection 
Association (NFPA); see NFPA 72. 

General Description

The  FSH-751  Smoke  Detector  uses  a  small  air  intake  fan 
and  a  high  density  replaceable  filter.  Air  and  smoke  are 
drawn into a photoelectric sensing chamber while airborne 
particulate  and  water  mist  are  removed.  The  address-
able-analog  detector  transmits  an  analog  representation 
of  smoke  density  over  a  communication  line  to  a  control 
panel. Rotary decade switches are provided for setting the 
sensor’s address. 

Two LEDs on each sensor light to provide a local, visible 
sensor  indication.  Remote  LED  annunciator  capability  is 
available as an optional accessory (Part No. RA400Z).

Notifier panels offer different features sets across different 
models. As a result, certain features of the FSH-751 may be 
available  on  some  control  panels,  but  not  on  others.  The 
possible features available in the FSH-751, if supported by 
the control unit are:
1. The  panel  controls  the  LED  operation  on  the  sensor. 

Operational  modes  are  RED  blink,  RED  continuous, 
GREEN blink, GREEN continuous, and off.

2. The  remote  output  may  be  synchronized  to  the  LED 

operation or controlled independent of the LEDs.

Please refer to the operation manual for the UL listed con-
trol unit of specific operation of the FSH-751.

 

The FSH-751 smoke detector is intended for use in nor-
mal  environmental  conditions,  where  dust  and  other 
airborne  particulate  are  present  at  elevated  levels. 
These  elevated  levels  tend  to  cause  false  alarms  and 
high  maintenance  in  standard  detectors.  FSH-751  pro-
vides  a  protective  enclosure  for  a  photoelectric  smoke 
detector  chamber  and  allows  smoke  detection  in  areas 
that tended to use exclusively heat detection.
FSH-751  requires  compatible  addressable  communica-
tions  to  function  properly.  Connect  this  detector  to 
listed-compatible control panels only.

Spacing

Notifier  recommends  spacing  detectors  in  compliance 
with  NFPA  72.  In  low  air  flow  applications  with  smooth 
ceilings,  space  detectors  30  feet  apart.  For  specific  infor-
mation  regarding  sensor  spacing,  placement,  and  special 
applications, refer to NFPA 72 or the 

System Smoke Detector 

Application Guide

 available from Notifier.

Duct Applications

FSH-751  is  listed  for  use  in  ducts.  See  Duct  Applications 
Guide  A05-1004  for  details  on  pendant  mount  applica-
tions.

FSH-751 Intelligent Photoelectronic Smoke Detector

Installation and Maintenance Instructions

Specifications 

Operating Voltage Range:                15 to  32 VDC
Detector Current:                            300 

µ

A @ 24 VDC (one communication every 5 sec. with LED enabled)

Auxiliary Power Supply Voltage:      15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.
Auxiliary Power Supply Current –   Peak: 123 mA max.      Average: 27 mA max.

Operating Humidity Range:                            10% to 93% Relative  

Humidity, noncondensing

Operating Temperature Range:                       0° to 50°C (32° to 122°F)
Height:                                                           2.8 inches (43 mm)
Diameter:   6.1 inches (155 mm) installed in B710HD
                                                                      4.0 inches (102 mm) installed in B524FTXE
Weight:      7.3 oz. (207 g)
Compatibility:                                                Backwards compatible with 700 and 500 series products’ protocol                                    Mounting 
Base:                                                             Requires B710HD (U.S.), B524FTXE (Europe)   