background image

APPENDIX B -  AFP-300/AFP-400

PN 50702:B2  4/14/03 

23

Connecting the APS-6R to an MPS-400

Make the following connections as shown in the figure below.

• Connect primary power from 

TB1

 on the APS-6R to MPS-400 

terminal block 

TB1

 (

NEU

 and 

HOT

).

• Connect secondary power from 

TB3

 on the APS-6R to MPS-400 

terminal block 

TB1

 (+ and –).

• Connect trouble input from 

J3

 on the APS-6R to MPS-400 

terminal block 

J4

.

 

Figure 14  Wiring to MPS-400

J2

J9

J3

J1

TB2

JP3

JP2

J4

A

PS-

6R

 to 

M

P

S-

400

.cd

r

To battery backup

+

-

www.PDF-Zoo.com

firealarmresources.com

Содержание APS-6R

Страница 1: ...PN 50702 B2 ECN 03 147 Auxiliary Power Supply APS 6R Instruction Manual Document 50702 4 14 03 Rev B2 www PDF Zoo com firealarmresources com ...

Страница 2: ...es caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitiv...

Страница 3: ...r to any drilling filing reaming or punching of the enclosure When pos sible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 9 in lbs Overtightening may damage threads resulting in reduced terminal contact pressure and difficulty with sc...

Страница 4: ...and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed material Brief description of content you think should be improved or corrected Your suggestion for how to correct improve documentation Send email messages to TechPubs fla whq com Please note this email address is for documentation feedback only If you have any technical issues pleas...

Страница 5: ...S 6R to an AFP 200 Power Supply 21 Appendix B AFP 300 AFP 400 22 Mounting an APS 6R in a CAB 400AA Backbox 22 Connecting the APS 6R to an MPS 400 23 Appendix C AFC 600 24 Mounting an APS 6R in a CAB 600AA Backbox 24 Connecting the APS 6R to an MPS 6 24 Appendix D System 500 25 Mounting an APS 6R in a CAB 500 Backbox 25 Connecting the APS 6R to an MPS 24BRB 25 Appendix E System 5000 AM2020 AFP 1010...

Страница 6: ...6 PN 50702 B2 4 14 03 www PDF Zoo com firealarmresources com ...

Страница 7: ...6R provides three 24 VDC filtered output circuits Figure 1 APS 6R Auxilliary Power Supply Control Panels Refer to Part Number NFS 3030 NFS 3030 Installation Manual 51330 NFS 640 NFS 640 Installation Manual 51332 System 500 System 500 Manual 15019 System 5000 System 5000 Manual 15583 AFP 200 AFP 200 Instruction Manual 15511 AFP 300 AFP 400 AFP 300 AFP 400 Installation Manual 50253 AFC 600 AFC 600 I...

Страница 8: ...In J4 Trouble Out J3 P style connectors for internal cabinet connections LED Status Indicators Green LED Indicates AC power on Yellow LED Indicates loss of AC or battery Fuse F2 for battery protection 10A 3AG slow blow Jumpers JP2 and JP3 for selecting 8 hour or 16 hour delay for AC loss reporting Default is immediate See Page 18 in Configuring the APS 6R APS 6Rsidebrd cdr JP1 Jumper JP1 for selec...

Страница 9: ...ted 10 15 6 A 24 VDC non power limited 10 15 Fuses F1 AC supervision F2 battery supervision 250 VAC 4A 3 AG slow blow 32 VAC 10 A 3 AG slow blow Trouble supervision bus J3 output J4 input Note J3 and J4 can be interchanged Form A contact open collector Form A contact open collector Loss of AC Indication Immediate indication default 8 or 16 hour delay Mechanical Specifications Size of APS 6R Inches...

Страница 10: ...ssembling and mounting the APS 6R It consists of the following items Quantity Description Part No 1 AC Power connector cover 02183 2 6 32 1 25 in 10 mm long 25 in 2mm hex standoff 42026 2 6 32 self tapping screw 38118 1 Trouble supervision cable 71033 www PDF Zoo com firealarmresources com ...

Страница 11: ...n topics covered in detail Additional information regarding installation may be found in the appendices Topic Refer to Mounting to a CAB 3 CAB 4 Series Cabinet Page 12 in Mounting in CAB 3 CAB 4 Series Cabinets Field Wiring Page 13 in Field Wiring an APS 6R Wiring Multiple APS 6Rs Page 15 in Connecting Multiple APS 6R Power Supplies Connecting to an ICM ICE Page 16 in Connecting the APS 6R to an I...

Страница 12: ...S 4L Chassis Step Action 1 Remove plastic cover from APS 6R 2 If 240 VAC is to be used cut JP1 jumper at this time See instructions and high voltage warning on Page 18 in Configuring the APS 6R 3 Place the APS 6R onto the mounting studs of the chassis Figure 4 on page 12 4 Insert a standoff through each of the printed circuit board mounting holes threading each standoff to the mounting studs on th...

Страница 13: ... for the XPIQ Audio Transponder only Note When using the J9 connector do not use the J2 connector This will satisfy the 0 25 6 35mm requirement for separation between power limited and nonpower limited circuits Primary and Secondary Power Connections See appendix for your specific system information CAUTION When finished wiring AC connections install the press fit terminal block cover over TB1 AC ...

Страница 14: ...y If 2 or more units are connected secondary units connect to earth ground on the previous APS 6R in the chain APS 6Rsidebrd cdr BATT BATT HOT NEUTRAL EARTH J9 Output Circuit 3 Non Power limited 6 A 24 VDC 10 15 J1 Output Circuit 1 J2 Output Circuit 2 Refer to the caution above this illustration about secondary power and supervision Output Circuit 2 J2 and TB2 Power limited 3 A 24 VDC 10 15 Output...

Страница 15: ...ing See appendix on your system for specific Trouble Input connection Note J3 and J4 can be interchanged Figure 6 Trouble Bus Connections for Multiple APS 6R Configurations J2 J9 J3 J1 TB2 JP3 JP2 J2 J9 J3 J1 TB2 JP3 JP2 J2 J9 J3 J1 TB2 JP3 JP2 To trouble input on main power supply or control panel First APS 6R Last APS 6R APS 6Rmultiple3 cdr Connect power as shown in Figure 5 www PDF Zoo com fire...

Страница 16: ...S 6R to an ICM ICE Module All four 4 NACs on the ICM are powered from the APS 6R output circuit 2 J2 and the four 4 NACs on the ICE are powered from circuit 1 J1 The NACs share the total 3A available from each circuit Typical connections for wiring Figure 7 Typical APS 6R Wiring to an ICM ICE Module J 6 5 J J 6 5 J J2 J9 J3 J1 TB2 JP3 JP2 ICM ICE Auxiliary Power Harness PN 71091 Black Blue Blue Bl...

Страница 17: ...to relevant control module installation documents for specific wiring instructions J2 J9 J3 J1 TB2 JP3 JP2 8 910 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 TENS ONES LOOP LOOP ADDRESS ADDRESS 8 9 7 6 5 9 8 7 6 5 0 1 2 3 4 4 3 2 1 0 TENS ONES 8 9 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 SLC loop To next device on SLC loop APS 6Rfcm cdr NAC www PDF Zoo com firealarmresources com...

Страница 18: ...ay for reporting loss of AC cut jumper JP2 and JP3 240 VAC operation See WARNING below Cut jumper JP1 before applying power The figure below illustrates the location of the jumpers Figure 9 Configuring the APS 6R JP1 J2 J9 J3 J1 TB2 JP3 JP2 JP3 JP2 JP1 APS 6Rconfig cdr WARNING HIGH VOLTAGE Cut JP1 before applying power for 240 VAC operation www PDF Zoo com firealarmresources com ...

Страница 19: ...s follows 1 Turn off and remove all power sources 2 Remove plastic cover 3 Remove the two retaining screws securing control board 4 Unplug the control PC board from the connectors 5 Replace fuses as required 6 Reinstall board in reverse order install plastic cover and connect all power The figure below illustrates the location of the fuses Figure 10 Servicing the APS 6R J2 J9 J3 J1 TB2 JP3 JP2 F2 ...

Страница 20: ...tions Figure 11 Mounting the APS 6R to an AFP 200 Backbox Step Action 1 Remove plastic cover from APS 6R 2 If 240 VAC is to be used cut JP1 jumper at this time See instructions and high voltage warning on Page 18 in Configuring the APS 6R 3 Locate the mounting holes in the AFP 200 backbox Insert a self tapping screw through each of the APS 6R mounting slots 4 Position the APS 6R in line with the h...

Страница 21: ...B1 on the APS 6R to terminal block TB7 NEUT and HOT on the AFP 200 Connect secondary power from TB3 on the APS 6R to terminal block J3 and on the AFP 200 Connect trouble input from J3 on the APS 6R to terminal block J11 on the AFP 200 Figure 12 Wiring to AFP 200 Power Supply J2 J9 J3 J1 TB2 JP3 JP2 APS 6R to AFP 200ps cdr To battery backup www PDF Zoo com firealarmresources com ...

Страница 22: ... is to be used cut JP1 jumper at this time See instructions and high voltage warning in Page 18 in Configuring the APS 6R 3 Place the APS 6R onto the mounting studs in the backbox 4 Insert a standoff through each of the printed circuit board mounting holes threading each standoff to the mounting studs 5 Tighten the standoffs until the APS 6R is securely fastened to the backbox 6 Reinstall the plas...

Страница 23: ...ry power from TB1 on the APS 6R to MPS 400 terminal block TB1 NEU and HOT Connect secondary power from TB3 on the APS 6R to MPS 400 terminal block TB1 and Connect trouble input from J3 on the APS 6R to MPS 400 terminal block J4 Figure 14 Wiring to MPS 400 J2 J9 J3 J1 TB2 JP3 JP2 J4 APS 6R to MPS 400 cdr To battery backup www PDF Zoo com firealarmresources com ...

Страница 24: ...Figure 15 Wiring to MPS 6 J2 J9 J3 J1 TB2 JP3 JP2 TB2 TB7 TB9 B B A A B B A A B B A A B B A A NO NC C NO NC C NO NC C NO NC C ALARM TB3 TROUBLE TB5 ACCESSORIES J1 J6 J2 AFP 600 CONNECTOR BATT BATT AC ON LED J7 TB11 J8 EARTH FAULT LED 24V POWER LIMITED RESET NON RESET NAC1 LED NAC2 LED MH4 MH6 MH3 MH1 JP4 JP2 NAC3 LED NAC4 LED CB1 JP5 JP6 J4 J5 J3 JP3 IF BOX IS CHECKED THIS POWER SUPPLY HAS BEEN CO...

Страница 25: ...PS 24BRB terminal block TB1 Pin 3 NEUT and Pin 4 HOT Connect secondary power from TB3 on the APS 6R to MPS 24BRB terminal block TB3 Pin 1 and Pin 2 Connect trouble input from J3 on the APS 6R to MPS 24BRB terminal block P4 Figure 16 Wiring to MPS 24BRB J2 J9 J3 J1 TB2 JP3 JP2 JP3 P3 P4 TB3 P1 TB2 TB1 CB1 P2 R55 1 2 3 4 6 7 8 7 5 3 2 1 EARTH ACNEUT COMMON COMMON BATT 24 VRESET ACHOT MPS 24BPCC REV ...

Страница 26: ...APS 6R to MPS 24A terminal block TB1 Pin 5 NEUT and Pin 7 HOT Connect secondary power from TB3 on the APS 6R to MPS 24A terminal block TB2 Pin 1 and Pin 2 Connect trouble input from J3 on the APS 6R to MPS 24A terminal block P5 Figure 17 Wiring to MPS 24A Connecting the APS 6R to an MPS 24BRB The connections are the same as for the System 500 Refer to Page 25 in System 500 for wiring instructions ...

Страница 27: ...640 Make the following connections as shown in the figure below Connect primary power from TB1 on the APS 6R to TB2 HOT NEUTRAL and EARTH on the NFS 640 Connect secondary power from TB3 on the APS 6R to TB1 on the NFS 640 BATT and BATT Connect trouble input from J3 on the APS 6R to J11 on the NFS 640 Figure 18 Wiring to the NFS 640 J2 J9 J3 J1 TB2 TB3 TB1 JP3 JP2 To battery backup APS 6R to NFS 64...

Страница 28: ...wn in the figure below Connect primary power from TB1 on the APS 6R to TB3 HOT NEUT and EARTH on the AMPS 24 Connect secondary power from TB3 BATT and BATT on the APS 6R to TB5 BAT IN and TB4 BAT OUT respectively on the AMPS 24 Connect trouble input from J3 on the APS 6R to the J5 Trouble bus connection on the CPU 3030 Figure 19 Wiring to AMPS 24 and CPU 3030 J2 J9 J3 J1 TB2 TB3 TB1 JP3 JP2 To bat...

Страница 29: ... to AMPS 24 28 to CPU 3030 28 to MPS 24A 26 to MPS 24BRB 25 26 to MPS 400 23 to MPS 6 24 to NFS 640 27 Control module typical connections 17 CPU 3030 28 D Document sources list of 7 E Earth Ground 14 Electrical Specifications 9 F Features of the APS 6R 8 Field wiring 13 Fuses 8 19 H High Voltage Warning 11 18 I ICM ICE 13 16 Installation topics 11 J JP1 jumper 8 18 JP2 jumper 8 18 JP3 jumper 8 18 ...

Страница 30: ...cations 9 Standoff 12 22 Status Indicators 8 System 500 7 9 25 System 5000 7 9 26 T Terminal block cover 13 Trouble Bus connectors 14 15 Trouble input 21 23 24 26 27 28 W Warning High Voltage 11 12 18 20 22 Wiring 13 X XP Series Transponder 7 XP5 Series Transponder 7 XP6 C 13 XPIQ 7 13 www PDF Zoo com firealarmresources com ...

Страница 31: ...ille Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that NOTIFIER is not an insurer and assumes no risk for l...

Страница 32: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www notifier com NOTIFIER is a company www PDF Zoo com firealarmresources com ...

Отзывы: