APPENDIX A - AFP-200
PN 50702:B2 4/14/03
21
Connecting the APS-6R to an AFP-200 Power Supply
Make the following connections as shown in the figure below.
• Connect primary power from
TB1
on the APS-6R to terminal
block
TB7
(
NEUT
and
HOT
) on the AFP-200.
• Connect secondary power from
TB3
on the APS-6R to terminal
block
J3
(+ and –) on the AFP-200.
• Connect trouble input from
J3
on the APS-6R to terminal block
J11
on the AFP-200.
Figure 12 Wiring to AFP-200 Power Supply
J2
J9
J3
J1
TB2
JP3
JP2
AP
S-
6R
to
AFP
-2
0
0p
s.cd
r
To battery backup
+
-
www.PDF-Zoo.com