AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
39
Control Module
Read Status
3.7 Control Module
When a module address is entered into the Point Select Screen and the ACCEPT soft key is pressed, the following screen will display if
the module is a control module.
Figure 3.8 Control Module Screen - Read Status
Display
Lines 1 through 10 - Refer to the descriptions in Section 3.2, “Smoke Detector”, on page 35 with the exception of line 6, which is
described below.
Line 6 - This line displays statistics that display for control module output points; in the above example they are:
AUTOMATIC OFF
The first field displays the point control. There are four designations that could appear in this field
The second field displays the point status. There are three designations that could appear in this field.
The device is a control module (an output device) so by referring to the descriptions below, it can be determined that the point is in a nor-
mal state.
Outputs: (Control Modules)
If the point is not in fault or disabled and the status is Automatic, the display will read:
AUTOMATIC
OFF
AUTOMATIC
ON
AUTOMATIC
OFF-HOOK
If the point has been forced into a manual control state, the display will read as follows. <Fault Status> will appear when there is a point
fault.
MANUAL
OFF
<Fault Status>*
MANUAL
ON
<Fault Status>*
MANUAL
OFF-HOOK
<Fault Status>*
If the point is disabled, the display will read as follows. <Fault Status> will appear when there is a point fault.
DISABLED
OFF
<Fault Status>*
DISABLED
ON
<Fault Status>*
DISABLED
OFF-HOOK
<Fault Status>*
If the point is in fault, the display will read:
FAULT
OFF
<Fault Status>*
Point Control
Designation
Description
AUTOMATIC
The point is being controlled automatically by the panel.
MANUAL
The point has been forced into manual control state by an outside source.
DISABLED
A status change other than a change to MANUAL control has caused the
point to go off automatic control.
FAULT
Table 3.4
Point Status
Designation
Description
OFF
The point is currently not activated.
ON
The point is currently activated.
OFF-HOOK
The telephone point is currently off-hook.
Table 3.5
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 2 , 2 0 1 9
R E A D A D D R E S S : N 1 2 4 L 0 3 M 0 5 2
A U T O M A T I C
O F F
E L E V A T O R L O B B Y
E A S T W I N G
F I F T H F L O O R
Z 0 0 5
C O N T R O L
Z 0 0 5 ,
Z 0 2 7 ,
Z 0 6 6 ,
,
,
,
,
,
,
,
W A L K T E S T : Y E S
S W I T C H I N H I B I T : Y E S
S I L E N C E A B L E : Y E S - R E S O U N D F I R E
1 0 : 2 2 : 3 4 A
T U E J A N 2 2 , 2 0 1 9
B A C K