page 7

Model 

5900 

D/P 

Module 

     

EX-1710-1

D/P Range Adjustment DIP Switch Settings

The D/P transmitter span can be adjusted from 70% 
to 140% of the nominal range indicated by the model 
number. (Refer to Model No. Designation on page 3.) This 
is how the transmitter’s pressure range can be changed 
for a specific application. When the D/P transmitter is 
used with a KING-GAGE

®

 digital tank level indicator, 

the “Application Datapack” (iButton memory module) is 
generally programmed with the nominal range setting. The 
indicator programming will correlate the output signal to 
tank capacity regardless of whether the maximum tank level 
generates less than 20 mA output from the transmitter.

WHEN NOT TO CHANGE SPAN

—If a KING-GAGE indicator 

is part of the system, you should not have to change the 
range (span) of the transmitter.

Coarse Range Setting

An initial coarse range setting is provided by the DIP switches. 
Use the previously outlined Zero/Span Calibration to achieve 
the final trim setting for precise 4–20 mA output over the 
intended pressure range.

The DIP switches on the transmitter circuit board affect 
the span (range) of the transmitter. These provide coarse 
adjustment in addition to the fine span adjustment of the 
potentiometer. Please refer to the individual DIP switch 
positions listed for adjusting the existing setting of the 
transmitter.

The four (4) switches provide 16 increments of coarse 
adjustment. Prior to changing any switch setting, check 
the current output of the transmitter at the desired upper 
pressure value. Also note the existing switch setting.

1. 

Apply the desired maximum pressure to the sensing 
diaphragm of the D/P transmitter (requires a pressure 
test shell available from King Engineering).

2. 

Record the existing setting positions of the DIP 
switches.

3. 

Adjust the potentiometer to maximum output by 
turning clockwise until it “clicks”.

4. 

To increase the milliamp output, use a higher switch 
setting arrangement; to reduce the milliamp output, 
use a lower switch setting arrangement. (The goal is 
to achieve a output signal value just slightly above 
20 milliamps and then use the potentiometer to 
trim the setting.)

5. 

Follow the Zero/Span Calibration procedure to check 
both the zero and span output.

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

DIP Switch

Increase

Maximum mA

Output

Minimum mA

Output

Decrease

Increase

Decrease

Increase

Decrease

Содержание KING-GAGE 5900

Страница 1: ...e to Range Calculation Calibration Procedures Zero Span Adjustments for Differential Pressure Transmitters Model 5900 D P Module 4 mA to 20 mA Pressure Transmitter Multiple Tank Level Display KING GAGE A NOSHOK Company I 1010 West Bagley Road Berea Ohio 44017 I Ph 855 367 2494 I www king gage com ...

Страница 2: ...ties of fitnessforaparticularpurposeormerchantability aregiven bythisagreement Theexclusiveremedyfornonconformity of these goods shall be repair and or replacement of the nonconforming goods or parts Sellerwillnotbeliableforconsequentialdamagesresulting from breach of this agreement The term consequential damages shall include but shall not be limited to damage toallmachines equipmentandgoodsother...

Страница 3: ...pan Adjustment 6 Low Pressure Input for differential pressure 8 Calibration Test Setup Typical 9 Pressure Range Calculation 10 Troubleshooting 11 5900 1 2 Fittings 1 none 1 8 NPT connection 4 Swagelok 1 4 tube 1 8 NPT compatible with copper or poly tubing Range 0 0 5 psid 0 0 3 bar 1 0 10 psid 0 0 69 bar 2 0 15 psid 0 1 03 bar 3 0 30 psid 0 2 06 bar 4 0 50 psid 0 3 44 bar Model No Designations ...

Страница 4: ...r Supply Voltage 14 40 Vdc unregulated Power Supply Stability Effect on FSO less than 0 005 of span change in output per volt change at input terminals Burst Pressure 200 psi Span Adjustment Range Transmitter adjustment turndown is 3 1 for the 0 15 0 30 0 50 psid nominal ranges Nominal Minimum Range of Adjustment 0 5 psid 0 3 psid 0 83 in thru 0 138 in water 0 2 1 m thru 0 3 5 m water 0 10 psid 0 ...

Страница 5: ...Pressure Transm itter T E S T Plug in Power Signal Connector Ð 2 1 RL K IN G G A G E ZERO SPAN D P M O DULE 4 2 0 m A Pressure Transm itter T E S T Plug in Power Signal Connector Ð 2 1 Power Requirement The D P transmitter requires a source of DC power 14 40 Vdc for operation Minimum excitation voltage must be no less than 14 Vdc Any receiver installed on the signal loop meters data loggers contro...

Страница 6: ...t to the maximum depth hydrostatic pressure Measure the output using the meter terminal posts on the transmitter board 2 Adjust span potentiometer as necessary to increase output clockwise ordecreaseoutput counterclock wise until the signal displays as 20 00 or 20 01 mA on the test meter 3 Next step is to re check the zero output and slightly adjust if necessary In Process Zero Span Adjustment It ...

Страница 7: ...lease refer to the individual DIP switch positions listed for adjusting the existing setting of the transmitter The four 4 switches provide 16 increments of coarse adjustment Prior to changing any switch setting check the current output of the transmitter at the desired upper pressure value Also note the existing switch setting 1 Apply the desired maximum pressure to the sensing diaphragmoftheD Pt...

Страница 8: ...tter sensing element and the high pressure to the other side the internal tank pressure above the liquid low pressure is balanced across the sensing element This is also referred to as being equalized which is why we designate the low pressure connection as E CAUTION While the internal pressure above the liquid is not a factor in determining range span there may be instances where the sum of the l...

Страница 9: ...ipment MILLIAMMETER 3 1 2 digit minimum 0 05 accuracy 20 ohms max internal resistance DC POWER SUPPLY PRESSURE INDICATOR PSI or IN OF WATER 0 05 accuracy corresponding to transmitter range 5 psid nominal 0025 psi or 0693 of water 10 psid nominal 005 psi or 1385 of water 15 psid nominal 0075 psi or 2078 of water 30 psid nominal 015 psi or 4156 of water 50 psid nominal 025 psi or 6927 of water NOTE ...

Страница 10: ...rve represents the distance from the lowest point on the bottom of the tank to the installed sensor Full is the level of contents at which the tank is filled to desired level which is less than the actual full capacity of the tank The liquid contents in the tank has a specific gravity of 1 032 C 1 032 Specific Gravity B 300 Upper Level A 28 Reserve 300 28 1 032 27 6807 10 14 psid 300 28 1 032 281 ...

Страница 11: ...20 0 mA Check zero output of transmitter adjust zero to 4 00 mA if necessary Check span setting adjust to 20 00 mA at nominal range or calculated full pressure Maximum output less than 20 00 mA Check that applied pressure is within span limits for transmitter range Transmitter has 40 span adjustment Check span setting adjust to 20 00 mA at nominal range or calculated full pressure Higherresistivel...

Страница 12: ......

Отзывы: