ES3 "Intelligent" Pressure and Level Transmitter   

 

 

 

 

EX-1861

 

 

OUTPUT SELECTION  4-20 mA or 20-4 mA

  Factory setting = 4 - 20 mA

1. Navigate to program point 

P105

, and push the menu button to enter the menu.

2. Two choices appear on the screen: 

4-20

 and 

20-4

3. Make an output choice and push the menu button to confirm.
4. The transmitter will return to the home screen.

  DAMPING 

ADJUSTMENT

 

 

The transmitter has an adjustable damping between 0.00 to 25.00 seconds. 

  Factory setting = 0.00 seconds

1. Navigate to program point 

P106

, and push the menu button to enter the menu.

2. Two choices appear on the screen: 

Set

 and 

Reset

 Choosing 

Set

 allows a value to be set between 0.00 and 25.00 seconds.

  • 

Select 

Set

, and push the menu button to confirm.

 

 

• Adjust the damping with the push buttons and push the menu button to confirm.

 

 

• The transmitter will return to the home screen.

 Choosing 

Reset

 will put the transmitter back to factory setting (0.00 seconds)

  • 

Select 

Reset

, and push the menu button to confirm to reset back to factory setting.

 

 

• The transmitter will return to the home screen.

 

  TEMPERATURE 

UNITS

 

 

In this menu the preferred temperature unit can be selected.

  Factory setting = Fahrenheit

1. Navigate to program point 

P107

, and push the menu button to enter the menu.

2. Two choices appear on the screen: 

Fahrenheit

 and 

Celsius

.

3. Make a choice and push the menu button to confirm.
4. The transmitter will return to the home screen.

  DEVICE 

SETUP

  In this menu, several operational settings can be made for the transmitter and the display.

1. Navigate to program point 

P108

, and push the menu button to enter the menu.

2. Five choices appear on the screen:
 

LocProtect

 : The transmitter can be protected against local adjustments 

 

ComProtect

 : The transmitter can be protected against adjustments with HART.

 

HART

®

 : Option for HART

®

 5 and HART

®

 7 communication.

 

DispMode

 : Option for turning the display 

on

 or 

off

.

  

Disp.Upd.

: Adjust the refresh rate of the measuring value on the display between 0.0 to 

5.0 seconds. For example when this value is set to 2.0 seconds, the measuring value on the 
display will be refreshed every 2 seconds.

 

 

• Select Set, and push the menu button to confirm.

 

 

• Adjust the setting with the push buttons and confirm with the menu button.

Содержание King-Gage 5800 Series

Страница 1: ... recommendations and warnings in this manual before the instrument is installed For personal safety optimal use and maintenance of the KING GAGE 5800 Series ES3 Transmitter these instructions should be studied carefully KING GAGE A NOSHOK Company I 1010 West Bagley Road Berea Ohio 44017 I Ph 855 367 2494 I www king gage com ...

Страница 2: ...or merchantability are given by this agreement The exclusive remedy for nonconformity of these goods shall be repair and or replacement of the nonconforming goods or parts Seller will not be liable for consequential damages resulting from breach of this agreement The term consequential damages shall include but shall not be limited to damage toallmachines equipmentandgoodsotherthanthegoods sold he...

Страница 3: ...3 5 Wiring 4 4 Remaining 5 4 1 CE EMC Rules 5 4 2 Display and push buttons 5 4 3 Display read out 5 5 Summary Programming Points 6 5 1 Explanation Programming Points 6 P101 Zero Adjustment Zero 6 P102 Span Adjustment Span 6 P103 Cancel Mounting Position Effect 7 P104 Display Setting Of Units 7 P105 Output Selection 4 20 Ma Or 20 4 Ma 8 P106 Damping Adjustment 8 P107 Temperature Units 8 P108 Device...

Страница 4: ... laser welded and helium leak tested A very small amount of oil fills the chamber surrounding the sensor and transfers pressure from the flush mounted dia phragm to the sensor Pressure on the sensor element creates a very small deflection of the silicon substrate and bridge network The resulting strain in the silicon resistors causes a change in the bridge resistance that is proportional to the pr...

Страница 5: ...st be connected to the terminal board The wiring terminals can be operated without a screwdriver The opening levers of the terminal can be lifted and pressed down by hand Lift the opening levers of the termi nals and insert the corresponding wires Press down the levers by hand The terminal spring will close and the wire is clamped 3 5 WIRING The transmitter must always be connected to ground The t...

Страница 6: ...ast display for optimal readout The menu is controlled by 3 push buttons Navigate with the up and down buttons through menus and measuring values Enter a menu and confirm selections with the menu button Push the up button to browse through various menus and adjusting values Push the down button to browse through various menus and adjusting values Push the menu button to enter menus or confirm a se...

Страница 7: ...nt P104 2 Navigate to program point P101 and push the menu button to enter the menu 3 The actual measured value appears on the display 4 Increase this value with the arrow button to 1 45 psi push the button till save appear on the display 5 The transmitter will return to the home screen The measurement value at atmospheric pressure is now 1 45 psi With a applied pressure of 1 45 psi the transmitte...

Страница 8: ...e 0 003 psi instead of 0 000 psi 1 Navigate to program point P103 and push the menu button to enter the menu 2 Two choices appear on the screen Set and Reset Choosing Set will adjust the zero to 0 000 psi in the mounting position when applicable Select Set and push the menu button to confirm The corrected is value is shown on the display Push the menu button to save Choosing Reset will put the tra...

Страница 9: ...y setting The transmitter will return to the home screen TEMPERATURE UNITS In this menu the preferred temperature unit can be selected Factory setting Fahrenheit 1 Navigate to program point P107 and push the menu button to enter the menu 2 Two choices appear on the screen Fahrenheit and Celsius 3 Make a choice and push the menu button to confirm 4 The transmitter will return to the home screen DEV...

Страница 10: ... Five choices appear on the screen Mode Cntrl Cmd number Message Period and Trigger 3 Select Mode Cntrl and push to confirm 4 Two choices appear on the screen On and Off Choose On to turn on burst mode Choose Off to turn off burst mode 5 Select Message to select the burst message 0 1 2 or 3 and push the menu button to confirm 6 Select Cmd number and push the menu button to confirm Five choices app...

Страница 11: ...sing The Burst message is triggered when the measured value rises above the triggered value Falling The Burst message is triggered when the measured value falls below the triggered value On Change The Burst message is triggered when any value in the measuring changing Choose the desired burst mode and set the preferred parameters INFORMATION This menu summarizes information about the configuration...

Страница 12: ...Page 12 ES3 Intelligent Pressure and Level Transmitter EX 1861 ...

Отзывы: