Load Short Circuit 

Load will be switched off when load short circuit (

4 times rated current) happens. Controller will automatically 

attempt to reconnect load for 5 times. If short circuit protection still exist after controller's 5 times attempts, user 
have to clear short circuit, then press the SET button or disconnect and restart the controller or wait for one night-
day cycle (night time>3 hours).  

 

Damaged Remote Temperature Sensor  

If the temperature sensor is short-circuited or damaged, the controller will be charging or discharging at the 
default temperature 25

º

C to prevent the battery damaged from overcharging or over discharged. 

 

Controller Overheating  

If the temperature of the controller heat sinks exceeds 85ºC, the controller will automatically start the overheating 
protection and recover below 75ºC.  

 

High Voltage Transients  

PV is protected against small high voltage surge. In lightning prone areas, additional external suppression is 
recommended. 

 
6.

 

Troubleshooting  

Faults 

Possible reasons 

Troubleshooting 

The LCD is off during 
daytime when

 

sunshine falls 

on PV modules properly

 

PV array disconnection

 

Confirm that PV wire connections are correct and tight

 

Wire connection is correct, 
LED not display 

1. Battery voltage is lower 
than 9V 
2. PV voltage is less than 
battery voltage 

1. Please check the voltage of battery. At least 9V voltage 
to activate the controller 
2. Check the PV input voltage which should be higher than 
battery's 

Interface blink 

Battery over voltage 

Check if the battery voltage is higher than OVD point 
(over voltage disconnect voltage), and disconnect the PV. 

Interface blink 

Battery over discharged 

When the battery voltage is restored to or above LVR point 
(low voltage reconnect voltage), the load will recover 

Interface blink 

Battery overheating 

The controller will automatically turn the system off. But 
while the temperature decline to be below 50 ºC, the 
controller will resume. 

Interface blink

 

Over load or Short circuit

 

Please reduce the number of electric equipment or check 
carefully loads connection. 

Содержание NSC1024A

Страница 1: ...play design dynamically displaying device s operating data and working condition Multiple load control modes Energy statistics function Battery temperature compensation function Extensive Electronic protection 2 Product Features 1 LCD 5 PV terminals 2 MENU Button 6 Battery Terminals 3 Mounting hole size Ø4 5 7 Load Terminals 4 RTS Port 8 SET Button Accessory Remote Temperature Sensor Acquisition o...

Страница 2: ...ontroller to recognize the system voltage 3 The battery fuse should be installed as close to battery as possible The suggested distance is within 150 mm 4 The controller is a positive ground controller Any positive connection of solar load or battery can be earth grounded as required NOTE Please connect the inverter or other load that it has the large start current to the battery rather than to th...

Страница 3: ...N Load OFF LOAD Load Voltage Current Load mode Browse interface NOTE 1 When no operation the interface will be automatic cycle but the follow two interfaces not be display 2 Accumulative power zero clearing Under PV power interface press SET button and hold on 5s then the value blink press SET button again to clear the value 3 Setting temperature unit Under battery temperature interface press SET ...

Страница 4: ...T button and hold on 5s till the number begin flashing then press MENU button to set the parameter press SET button to confirm 1 Timer 1 2 Timer 2 100 Light ON OFF 2 n Disabled 101 Load will be on for 1 hour since sunset 201 Load will be on for 1 hour before sunrise 102 Load will be on for 2 hours since sunset 202 Load will be on for 2 hour before sunrise 103 113 Load will be on for 3 13 hours sin...

Страница 5: ...tery Battery over voltage When the battery voltage reaches to the set point of Over Voltage Disconnect Voltage the controller will stop charging the battery to protect the battery from being over charged to break down Battery over Discharge When the battery voltage reaches to the set point of Low Voltage Disconnect Voltage the controller will stop discharging the battery to protect the battery fro...

Страница 6: ...onal external suppression is recommended 6 Troubleshooting Faults Possible reasons Troubleshooting The LCD is off during daytime when sunshine falls on PV modules properly PV array disconnection Confirm that PV wire connections are correct and tight Wire connection is correct LED not display 1 Battery voltage is lower than 9V 2 PV voltage is less than battery voltage 1 Please check the voltage of ...

Страница 7: ...ll dimension 132x84 6x39 7 mm Mounting dimension 120x56 mm Mounting hole size Ø4 5 mm Terminals 4 mm2 Net weight 0 18 kg If the controller is working under high temperature environment please derate capacity in service Battery voltage Parameters parameters is in 12v system at 25ºC please use double value in 24V Battery charging setting Sealed Gel Flooded Over Voltage Disconnect Voltage 16 0V 16 0V...

Страница 8: ...n unsuitable environment 2 PV or load current voltage or power exceeding the rated value of controller 3 User disassembly or attempted repair the controller without permission 4 The controller is damaged due to natural elements such as lighting 5 The controller is damaged during transportation and shipment Any changes without prior notice Version number V1 0 Northern Sunshine Co Ltd 82 33 Soi Ratt...

Отзывы: