Page 32 of 34 Equipment replacement
553-2601-500A
Standard 2.0
December 1994
Procedure 16
QRF12 Rectifier replacement
1
Set AC BRKR breaker on the front of the rectifier to OFF.
2
Disconnect rectifier commercial power line cord from its receptacle.
3
If equipped, remove the bottom EMI shield.
4
Tag and disconnect the commercial power line cord, sense leads,
DCON lead and battery leads from the rear of the rectifier (
).
5
Remove the mounting screws at the front of the rectifier and remove
the rectifier from cabinet.
6
Position the new rectifier in the cabinet and secure with mounting
screws.
7
Set the ac breaker on the new rectifier to OFF.
8
Reconnect all previously disconnected wiring (
9
Ensure that the 110V/220V switch on the front of the new rectifier is set
to the correct voltage.
10
Connect the rectifier commercial power line cord to its receptacle.
11
Set the rectifier AC BRKR breaker on the front rectifier to ON.
CAUTION
Service in the cabinet is interrupted when replacing the rectifier unless
battery backup is provided.