background image

4

shock. Do not work on electrical equipment unless you are 

adequately trained, qualified, and are properly licensed.

•  This equipment may contain liquid and gaseous refrigerant 

under high pressure. Installation or servicing should only be 

performed by qualified trained personnel thoroughly familiar 

with this type equipment.

•  This equipment is 

not

 to be used for temporary heating 

of buildings or structures under construction.

•  Use  caution  when  handling  this  appliance  or  removing 

components. Personal injury can occur from sharp metal 

edges present in all sheet metal constructed equipment.

•  Follow  all  precautions  in  the  literature,  on  tags,  and  on 

labels provided with the equipment. Read and thoroughly 

understand the instructions provided with the equipment 

prior to performing the installation and operational checkout 

of the equipment.

•  Suggestions  and  procedures  in  this  manual  are  general 

guidelines only, and must be disregarded if they in any 

way contradict the electrical component’s equipment 

manufacturer’s guidelines. It is the dealer’s/service 

technician’s sole responsibility to insure all electrical tests 

and service are performed in strict accord with all applicable 

codes and with the respective electrical component’s 

manufacture’s guidelines and directions.

rEQuIrEMEnts & coDEs

•  The  installer  must  comply  with  all  local  codes  and 

regulations which govern the installation of this 

type of equipment. local codes and regulations take 

precedence over any recommendations contained in 

these instructions. consult local building codes and the 

national Electrical code (nEc) for special installation 

requirements.

•  The  use  of  Grout  111  is  only  authorized  with  the 

installation of the lineset associated with the nortek 

Global HVAC Geothermal System.  Use of Grout 111 

for any other applications is prohibited.

•  Obtain all required permits (Federal, State, and/or Local) 

prior to commencing work. This may include mechanical, 

electrical, drilling/excavation, erosion control, and grouting 

permits. Additionally, some subdivision developments and/

or some homeowner associations have certain landscaping, 

etc., requirements where approvals must be obtained prior 

to excavation and/or equipment positioning. 

• 

locate all underground utilities and objects prior to any 

drilling and/or excavation

. Many areas have a “One Call” 

number that may assist in (but should not necessarily be 

relied upon) locating underground utilities. Failure to comply 

with local laws may subject the homeowner or excavator to 

expensive fines, legal fees or prosecution. Failure to check 

for, and to avoid, underground utilities may also result in 

physical injury or death.

•  All electrical wiring must be completed in accordance with 

local, state and national codes and regulations and with the 

National Electric Code (ANSI/NFPA 70) or in Canada the 

Canadian Electric Code Part 1 CSA C.22.1.

•  Design the duct work according to methods described by 

the Air Conditioning Contractors of America (ACCA). This 

unit should be sized to provide the design load requirement. 

Load estimates can be made using approved methods 

available from Air Conditioning Contractors of America 

(Manual J); American Society of Heating, Refrigerating, and 

Air Conditioning Engineers; or other approved engineering 

methods.

•  This unit is designed for indoor and outdoor installations and 

should be located with consideration given to the accessibility 

of fuel, electric power, service access, noise, shade, and 

drainage for the units condensate drainage. Install this unit 

only in a location and position as specified on 

page 5

.

•  It is the installing/servicing dealer’s/authorized contractor’s 

sole responsibility to obtain and possess, or to insure the 

appropriate possession of, all necessary licenses prior to 

installing or servicing.

•  Check for full and complete compliance with all applicable 

local mechanical, drilling, excavation, grouting, erosion 

control, and building codes, and check for full and complete 

compliance with all applicable national codes/regulations 

(such as OSHA and the National Electrical Codes, the 

“NEC”, for example).

GEnEral InForMatIon

Geothermal heating/cooling systems operate via sub-surface 

conductive heat transfer, using the naturally renewable 

temperature of the earth’s crust as a heat source in the winter, 

and as a heat sink in the summer.

 

Within any climate zone, the 

weather, and underground conditions vary from place to place. 

To determine your climate zone, see 

Figure 9 (page 19)

.

This geothermal heat pump system contains an earth loop that 

includes a vapor line, an insulated liquid line, and a bottom 

segment called a torpedo. See 

Figure 8 (page 18)

.

This unit has been tested for capacity and efficiency and 

will provide many years of safe and dependable comfort, 

providing it is properly installed and maintained. With regular 

maintenance, this unit will operate satisfactorily year after 

year. Abuse, improper use, and/or improper maintenance can 

shorten the life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment 

failure, it is recommended that periodic maintenance be 

performed on this unit. The ability to properly perform 

maintenance on this equipment requires certain tools and 

mechanical skills. See 

page 12

 for additional maintenance 

information.

Before You Install this unit

 The cooling and heating load of the area to be conditioned 

must be calculated and a system of the proper capacity 

selected.

 Check the electrical supply and verify the power supply is 

adequate for unit operation.

 The indoor section (air handler, furnace, etc) should be 

installed before routing the refrigerant tubing. Refer to the 

installation instructions supplied with the air handler or 

furnace.

 All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Claims for damage 

(apparent or concealed) should be filed immediately with 

the carrier.

 Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 
instructions before installing the unit.

system sizing

Make sure the system has been properly sized prior to 

installation. The system must be sized using ACCA Manual 

J, or similar, load sizing criteria.

Содержание Y1SA

Страница 1: ...ty warnings and any other special notes highlighted in the manual Improper installation of this unit or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require licensed installation service personnel for this type of equip...

Страница 2: ...R 410A Charging Procedure 10 Initial Charge 10 Starting In Heating Mode Charging To Sight Glass 10 System Check 11 Air Circulation Indoor Blower 11 System Heating 11 OperatinG Sequence 11 Cooling 11 Heating 11 Unit MAINTENANCE 12 Filter Drier 12 Replacing the Oil Separator Filter 12 Adding Compressor Oil 12 Troubleshooting 13 Two Digit Display 13 Loss Of Capacity 14 Restricted Refrigerant System 1...

Страница 3: ...akeitnecessaryfor evacuationandcharging itshouldonlybeattempted by qualified trained personnel thoroughly familiar with this equipment Some local codes require licensed installation service personnel to service this type of equipment Under no circumstances should the equipment owner attempt to install and or service this equipment Failure to comply with this warning could result in equipment damag...

Страница 4: ...d requirement Load estimates can be made using approved methods available from Air Conditioning Contractors of America ManualJ AmericanSocietyofHeating Refrigerating and Air Conditioning Engineers or other approved engineering methods Thisunitisdesignedforindoorandoutdoorinstallationsand shouldbelocatedwithconsiderationgiventotheaccessibility of fuel electric power service access noise shade and d...

Страница 5: ...sor section is equipped with components and control logics described in the following sections Heating To Cooling Transition The compressor section includes a hot gas injection valve to ensure smooth transition from heating to cooling mode operations See Figure 6 page 16 After heating mode operation the earth loop temperature maybebelowthenormalundergroundtemperature around 58 F As the refrigerant...

Страница 6: ...ler Insulating Interior Line Sets Insulate all interior refrigerant lines and their connections The compressor section contains the expansion valve and the liquid line is more likely to sweat as it condenses moisture from the interior air Use at least a 3 4 inch wall closed cell insulation that is non corrosive to copper to insulate all refrigerant lines Use Armaflex Neoprene or Rubatex having at ...

Страница 7: ...rature rather than operating on a preferred temperature maintain mode If the system has electric strip heat back up within the air handler the system can operate together with the electric supplement heat as the strip heating coils are installed downstream of the refrigerant heat exchanger The electric strip heat is supplemental to the heat provided by the geothermal system The thermostat used wit...

Страница 8: ...efrigerantlineconnectionsarecompleted itisrequired that you leak check and evacuate the indoor section and all line connections using proper methods before finalizing the full system refrigerant charge For final charges based on matched systems and specified line lengths see Table 4 page 9 Pressure test the entire system at 400 psig with dry nitrogen prior to pulling a vacuum and charging Prior to...

Страница 9: ...n by using the following formula TROV ft 3 Total refrigerant charge lb x 40 The examples below were calculated assuming 25 single line length between well and compressor sections L1 and 6 single line length between compressor section and air handler L2 For the 2 ton example the well length is 200 ft and for the 5 ton example the well length is 400 ft as shown in Table 4 Theinstalledsystemiswithane...

Страница 10: ...g the compressor to draw high watts Too little refrigerant will freeze the indoor coil in cooling mode operation The recommended charging method is to charge refrigerant to the middle of the sight glass of the accumulator during heating operation In cooling mode with correct R 410A charge the refrigerant returning from the well is in a saturated condition The conventional method of charging by sub...

Страница 11: ...rt e If the system has run in the previous 5 minutes a 5 minute anti short cycle timer must expire before the system will restart 3 If the above conditions are met the compressor will start and the reversing valve shift into position if not already in the cooling position a At any time during compressor operation the system will stop if The discharge pressure exceeds 635 psig The suction pressure ...

Страница 12: ...lter which is installed at the factory The second filter is to be used as a replacement within 24 to 48 hours of operation These coalescent filters will pick up all dirt and particulates down to 0 3 microns Typical filter driers only catch 50 microns or larger Frequently check the pressure drop across the separator on new installations See Figure 2 and Table 5 page 10 Changethefilterafteraninitial...

Страница 13: ...e numbers represent the firmware version When the unit is ready to run it will display which indicates that the unit is in standby mode The display will alternate between the current status and any current or recent events See Table 7 page 14 for status and event codes The display alternates between showing the current status code and the 5 most recent event codes as shown in Table 3 If an event c...

Страница 14: ... compressor will eventually overheat and shut off by its own internal overload since the motor s windings are not being cooled by refrigerant vapor Sand Or Dirt In The Sub Surface Tubing Prior to Initial Charging The following steps should be performed if debris removal is required after the field lines have been connected to the liquid line assembly 1 Recoverallrefrigerantfromfromthelinesettotheb...

Страница 15: ...d Air In The Winter Or Cooled Air In The Summer Check system operational pressures for a potential refrigerant leak operational pressures will be too low NOTE If pressures are too high in the summer or too low in the winter the geothermal heat pump exchange field may have been overstressed This can be accomplished by either turning the system off use your supplemental back up heating during the wi...

Страница 16: ...l Separator Bracket Check Valve Hot Gas Bypass Valve Coil Large Valve Small Valve EXV Valve Coil Solenoid Valve Coil Figure 6 Components H W L 8 72 11 25 13 86 16 38 19 90 22 40 1 54 5 42 5 26 Liquid Line to Air Handler Vapor Line to Air Handler Vapor Line to Earth Loop Liquid Line to Earth Loop Line Voltage Connections Low Voltage Connections Figure 5 Dimensions ...

Страница 17: ...nnect to 24 vac 60va class 2 circuit See air handler installation instructions for control circuit and optional relay transformer kits 711415B Replaces 711415A 04 20 W2 W1 O C Y2 R Y1 RELAY THESE WIRES RELAY AND WELL SEAL VALVE ON 4 5 TON 14 17 5 kW UNITS ONLY CCH SUCTION TEMP TO 1PH POWER SUPPLY GND CONTACTOR T2 L2 T1 REVERSING VALVE 1 2 3 4 5 6 7 HOT GAS INJECTOR EXV MOTOR SUCTION PRESSURE SENSO...

Страница 18: ...MMN36K B B6EMMN60K C B6EMMN60K C Physical Data Length L 25 1 25 1 25 1 25 1 Width W 25 2 25 2 25 2 25 2 Height H 30 5 30 5 30 5 30 5 Weight 165 170 215 220 Refrigerant Vapor Line O D Both to air handler and earth loop 3 4 3 4 7 8 7 8 Liquid Line O D Both to air handler and earth loop 1 2 1 2 1 2 1 2 Unit is shipped from factory with nitrogen holding charge Table 9 Electrical Physical Data Insulate...

Страница 19: ... Star Wade Hampton Nome Yukon Koyukuk North Slope NOTE Zone 1 includes Hawaii Guam Puerto Rico and the Virgin Islands Figure 9 Climate Map IECC Zones Earth Loop Size ft ton 1 2 3A 3B 100 3C 4A 4B 80 4C 5 6 7 8 65 There are exceptions to the earth loop sizes shown in this table Within a climate zone the weather and underground conditions vary from place to place The earth loop length may need to be...

Страница 20: ...e size Number of borehole s or Earth Loop s _____________________ Depth of each borehole or Earth Loop____________________ Ft Line set size Vapor line O D Inches _______ Liquid line O D inches ________ Line set distances to each well______________________ distance between the compressor and the air handler Distance feet ___________________________________ Tubing size Vapor line O D Inches _______ ...

Отзывы: