I-UDSA-UK (02-19) PN 06 00116 UDSA R3, page 31
Information Requirements for Warm Air Heaters Commission Regulation (EU) 2016/2281
B1 warm air heater
NO
C2 warm air heater
NO
C4 warm air heater
NO
Type of fuel
GAS: G20/G25
UDSA-4E 011
015
020
025
030
035
043
050
055
064
073
085
100
120
145
Capacity
Rated heating
capacity
P
rated,h
kW 11.13 14.77 18.35 25.75 29.59 35.06 43.01 49.47 55.69 65.45 72.91 86.58 98.78 127.51 145.79
Minimum capacity P
min
kW 5.44 8.83 8.96 12.64 14.56 17.25 21.14 24.31 27.31 31.99 35.04 42.74 48.39 74.17 70.87
Electric Power Consumption*
At rated heating
capacity
el
max
kW
0.04
0.08
0.32
0.35
At minimal
capacity
el
min
kW
0.04
0.08
0.32
0.35
In standby mode
el
sb
kW
0.02
0.03
Useful Efficiency
Useful efficiency
at rated heating
capacity
*
η
nom
%
84.2 83.8 83.4 83.6 84.0 83.7 84.6 84.4 84.3 84.2 82.8 84.3 84.2
82.0
82.8
Useful efficiency
at minimum
capacity
*
η
pl
%
82.4 81.8 81.4 82.0 82.7 82.4 83.1 82.9 82.7 82.3 79.6 83.2 82.5
79.5
80.5
Other Items
Envelope loss
factor
F
env
%
0
Ignition burner
power
consumption
*
P
ign
kW
0.02
0.03
Emissions of
nitrogen oxides
(input energy
(GCV))
*
NO
x
mg/
kWh 89.1 98.0 97.5 93.3 94.3 98.6 97.2 94.5 90.1 92.9 91.6 97.1 99.8
99.0
99.2
Emission
efficiency
η
s,flow
%
93.9 92.9
93.9
94.4
94.6
94.8
94.6
94.0
94.7
ERP seasonal
space heating
energy efficiency
η
s,h
%
74.5 72.8 74.4 74.8 75.5 75.8 76.9 76.7 76.6 76.4 74.2 77.2 76.7
72.4
74.6
Thermal efficiency
at rated heating
capacity (NCV)
η
th
%
93.5 93.1 92.6 92.8 93.3 93.0 93.9 93.7 93.6 93.5 93.9 93.6 93.7
91.1
91.9
*
Not required for electric warm air heaters
Contact details: Nortek Global HVAC,
Содержание Reznor UDSA-4E 011
Страница 24: ...I UDSA UK 02 19 PN 06 00116 UDSA R3 page 24 2 Air heater does not operate and lock out indicator light is on...
Страница 25: ...I UDSA UK 02 19 PN 06 00116 UDSA R3 page 25...
Страница 26: ...I UDSA UK 02 19 PN 06 00116 UDSA R3 page 26...
Страница 27: ...I UDSA UK 02 19 PN 06 00116 UDSA R3 page 27...