I-UDSA-UK (02-19) PN 06 00116 UDSA R3, page 11

The electrical installation may only be carried out by an 

appropriately qualified person current to IEE Regulations. The 

supply line to the heater should include a main switch. The 

minimum 

clearance 

distance between the contacts must be 

more than 3 mm.

All electrical connections should be made in the heater control 

compartment. Screw type terminals are provided. Connections 

should be in accordance with the terminal markings and the 

wiring diagram affixed to the air heater.

Attention: Serious damage can occur to burner relay when 

faulty connection of thermostat, reset switch or burner 

failure lamp.

Switching of wires for reset switch and flame failure (e.g. 

in a remote control box) will destroy the burner relay.

The minimum external control required for the air heater is 

a room thermostat. 

It is essential that the main input line 

and neutral to terminals L and N remain live at all times 

even when the heater is switched off to ensure correct 

operation of the unit.

A burner reset switch with red indicator light is fitted on the 

heater. To add a remote reset button, make connections to the 

terminals in the electric box as indicated on the wiring diagram.

DANGER: THIS APPLIANCE MUST BE EARTHED.

THERMOSTAT LOCATION

Do not attempt to control more than one air heater from 

a single thermostat or control panel unless a properly 

wired relay is fitted. Follow the instructions supplied with 

such panels.

The location of the room thermostat or sensor is very important. 

It should not be positioned on a cold wall or cold surface. Avoid 

location in draughty areas or where it may be influenced by 

heat sources (e.g., the sun, process plant, etc.). The thermostat 

should be mounted on a vibration free surface and mounted 

about  1,5  metres  above  floor  level.  Follow  the  thermostat 

manufacturers instructions. The thermostat must be suitable 

for potential free contacts.

 

11 

ELECTRICAL CONNECTION

IMPORTANT: If the reset button requires activating for any 

reason, the cause must be determined. After determining 

and correcting the problem, restart the heater and monitor 

long enough to ensure proper operation (approximately 

5 minutes).

An orange indicator light is fitted on the heater to signify when 

the burner is on.

Ensure that all cables and installers wiring are fixed to the 

gas pipe and that they do not touch the combustion collector 

box.

Warnings: 

All components of a gas supply system must 

be leak tested prior to placing equipment in service. 

NEVER TEST FOR LEAKS WITH AN OPEN FLAME.

 

Failure to comply could result in personal injury, property 

damage or death.

This appliance is equipped for a maximum gas supply 

pressure of 50 mbar.

Pressure testing supply piping

Test pressures above 50 mbar :

 Disconnect the heater 

and manual valve from the gas supply line which is to be 

tested. Cap or plug the supply line.

Test pressures below 50 mbar : 

Before testing, close 

the manual valve on the heater.

Figure 8 : Gas connection 

Warning: Do not over tighten and do not rotate the gas 

valve inside the heater control compartment.

The unit is equipped with a nipple that extends outside the 

cabinet. The gas connection is 1/2-, 3/4-, or 1-inch, depending 

on the size of the unit.

Leak test all connections by brushing on a leak detecting 

solution.

Table 7 : Diameter gas connection

UDSA-4E

Natural Gas/Propane 

Connection 

(Inches)

011

030

1/2

035

100

3/4

120 and

 

145

1

Содержание Reznor UDSA-4E 011

Страница 1: ...he appliance or gas service meter after installation WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death All work must be carried out b...

Страница 2: ...e supervised to ensure that they do not play with the appliance These units must be installed in accordance with BS6230 or BS5440 as appropriate plus all local building codes Models UDSA 4E are design...

Страница 3: ...00 267 404 696 546 131 191 129 67 85 413 15 5 98 350 120 413 250 015 020 383 700 343 404 723 546 199 5 191 139 122 86 413 15 5 98 350 120 413 450 025 030 586 700 546 404 771 546 367 5 191 222 122 121...

Страница 4: ...stible supports Table 3 Gas Connection Diameters Diameters UDSA 4E 008 011 015 020 025 030 035 043 050 055 064 073 085 100 120 145 Flue air inlet diameter mm 80 100 130 Gas connection diameter inches...

Страница 5: ...e heater with A 160m Q 2 Table 4 Technical data UDSA 4E 011 015 020 025 030 035 043 050 055 064 073 085 100 120 145 Gas category II2H3 Combustion air and flue type B installation 1 B22 Combustion air...

Страница 6: ...t duct and a flue pipe or as a power vented heater type B the combustion air is taken from the space where heater is installed which requires only a flue pipe exhausting to outdoors All products of co...

Страница 7: ...must be at least 150 mm away from any combustible material B22 roof B22 wall Warning Single wall flue pipe exposed to cold air or run through unheated areas should be insulated to avoid condensation...

Страница 8: ...ombustion from the space in which it is installed Do not restrict the combustion air intake Always ensure that adequate combustion air is provided to suit the total installation of all combustion equi...

Страница 9: ...d toward the exposed walls In large areas units should be located to discharge air along exposed walls with extra units provided to discharge air in toward the centre of the area For optimum results h...

Страница 10: ...s Support gas piping with pipe hangers metal strapping or other suitable material Do not rely on the heater to support the gas pipe Figure 6a Suspending the heater with rods from the threaded nut reta...

Страница 11: ...in draughty areas or where it may be influenced by heat sources e g the sun process plant etc The thermostat should be mounted on a vibration free surface and mounted about 1 5 metres above floor lev...

Страница 12: ...Heater Specification UDSA V4 E Series Modulating Burner Control Brahma TC340A Legend Heater Terminals Controls Terminals Notes 1 Link wires MUST be fitted where shown solid 2 Terminals shown may not b...

Страница 13: ...cian to inspect the appliance and to replace any part of the control system and any gas control When overheating occurs or when gas supply is not turned off shut the manual gas tap before turning off...

Страница 14: ...soundness Reset temperature control room thermostat to comfort operating level Figure 10 Gas valve models 050 4E 145 4E Table 8 Burner jets and pressures Diameters Pressures UDSA 4E 011 015 020 025 03...

Страница 15: ...e gas valve being energized and the flame sensor checking for flame NOTE If no flame is sensed the burner relay will attempt ignition five times before going into lock out mode Post purge time The 5 m...

Страница 16: ...eful to reassemble cor rectly to ensure that no unsafe conditions are created When starting the heater always follow the lighting instructions on the heater Warning If you turn off the power supply al...

Страница 17: ...rminal blocks 3 Pressure switch S3 4 Electronic burner relay fuse 3 15AF This heater is equipped with a patented T CORE2 heat exchanger Remove any external dirt or dust accumulation Visually check the...

Страница 18: ...he union outside of the cabinet 4 Open the access door Figure 12a Figure 12b 15 BURNER MAINTENANCE 5 Disconnect the manifold and move it out of the way At the gas valve mark and disconnect the connect...

Страница 19: ...osite order Ignitor See Figure 11a and locate the ignitor Disconnect the wire remove the screw and the ignitor Clean the ignitor as sembly with an emery cloth Spark gap must be maintained to 3 mm see...

Страница 20: ...ition Do not open the control relay Each heating season check the lead wires for insulation deterioration and good connections Proper operation of the direct spark ignition system re quires a minimum...

Страница 21: ...el position on shaft Figure 18a Venter motor and wheel assembly models 011 020 Rotation clockwise from motor shaft end Figure 18b Venter motor and wheel assembly models 025 and 030 Rotation clockwise...

Страница 22: ...es that proper com bustion airflow is available The switch senses the differential pressure between the negative pressure in the flue gas collec tor box and the pressure in the control section On star...

Страница 23: ...ater If the heater fails to operate properly review the flow chart below and see the operating sequence in section 16 The general troubleshooting charts on the following pages will also help you to de...

Страница 24: ...I UDSA UK 02 19 PN 06 00116 UDSA R3 page 24 2 Air heater does not operate and lock out indicator light is on...

Страница 25: ...I UDSA UK 02 19 PN 06 00116 UDSA R3 page 25...

Страница 26: ...I UDSA UK 02 19 PN 06 00116 UDSA R3 page 26...

Страница 27: ...I UDSA UK 02 19 PN 06 00116 UDSA R3 page 27...

Страница 28: ...eplace worn or grounded spark cable Replace ceramic spark electrode if cracked or grounded Check burner relay ground wire Ensure that unit is properly field grounded earthed and properly phased L1 to...

Страница 29: ...lamp All 60 61997 Reset switch All 60 61998 Gas valve natural gas modureg 011 043 03 25140M 050 145 03 35145 Gas valve plug and wire 011 043 03 25141 V1 050 145 03 25136 V1 Two stage head 011 100 03...

Страница 30: ...tioned machinery directive Complies with the requirements of further directives namely EU 2016 426 GAR EMC 2014 30 EU LVD 2014 35 EU The following harmonized standards have been applied EN 1020 Non do...

Страница 31: ...Useful Efficiency Useful efficiency at rated heating capacity nom 84 2 83 8 83 4 83 6 84 0 83 7 84 6 84 4 84 3 84 2 82 8 84 3 84 2 82 0 82 8 Useful efficiency at minimum capacity pl 82 4 81 8 81 4 82...

Страница 32: ...gdom Tel 01384 489250 Fax 01384 489707 reznorsales nortek com www reznor eu Nortek Global HVAC is a registered trademark of the Nortek Global HVAC limited Because of the continuous product innovation...

Отзывы: