Nortek R8GE Series Скачать руководство пользователя страница 8

8

CIRCULATING AIR SUPPLY

 WARNING:

Products of combustion must not be allowed to 

enter the return air ductwork or the circulating air 

supply. Failure to prevent products of combustion 

from being circulated into the living space can create 

potentially hazardous conditions including carbon 

monoxide poisoning that could result in personal 

injury or death.
All return ductwork must be adequately sealed, all 

joints must be taped, and the ductwork must be 

secured to the unit with sheet metal screws. When 

return air is provided through the bottom of the unit, 

the joint between the unit and the return air plenum 

must be air tight.
The roof curb or cement pad that the unit is mounted 

must provide sound physical support of the unit 

with no gaps, cracks, or sagging bewteen the unit 

and pad.
Return air and circulating air ductwork must not 

be connected to any other heat producing device 

such as a fireplace insert, stove, etc. Doing so may 

result in fire, explosion, carbon monoxide poisoning, 

personal injury, or property damage.

Air Ducts

This unit is designed only for use with a supply and return 

duct. Air ducts should be installed in accordance with 

the standards of the National Fire Protection Association 

“Standard for Installation of Air Conditioning Systems” (NFPA 

90A), “Standard for Installation of Residence Type Warm Air 

Heating and Air Conditioning Systems” (NFPA 90B), and all 

applicable local codes. NFPA publications are available by 

writing to: National Fire Protection Association, Batterymarch 

Park, Quincy, ME 02269 or visit www.NFPA.org on the web.
•  Design the duct work according to Manual D by the Air 

Conditioning Contractors of America (ACCA).

• The ducts must be properly sized and not exceed 0.2” 

W.C. pressure drop at 400 scfm per nominal ton of cooling 

capacity.

•  Duct work should be attached directly to the unit flanges for 

horizontal applications.

•  If roof curb is installed, the ducts must be attached to the 

curb hangers, not the unit.

•  It is recommended that the outlet duct be provided with a 

removable access panel. The opening should be accessible 

when the unit is installed in service and shall be sizes so that 

smoke or reflected light may be observed inside the casing 

to indicate the presence of leaks in the heat exchanger. The 

cover for the opening shall be attached in a way that will 

prevent leaks.

•  If outside air is utilized as return air to the unit for ventilation 

or to improve indoor air quality, the system must be designed 

so that the return air to the unit is not less than 50° F (10° 

C) during heating operation.

•  If a combination of indoor and outdoor air is used, the ducts 

and damper system must be designed so that the return air 

supply to the furnace is equal to the return air supply under 

normal, indoor return air applications.

Air Filter Requirements

 WARNING:

Never operate the unit without a filter in place. 

Dust and lint could accumulate on internal parts, 

resulting in loss of efficiency, equipment damage 

and possible fire.

• A suitable air filter must be installed upstream of the 

evaporator coil of the return air system. Refer to 

Table 1

 

and 

Table 2 (page 10)

 for recommended filter sizes.

•  All return air must pass through the filters before entering 

the evaporator coil.

 

It is important that all filters be kept clean 

and replaced frequently to ensure proper operation of unit. 

Dirty or clogged filters will reduce the efficiency of the unit 

and result in unit shutdowns.

•  Air filter pressure drop must not exceed 0.08 inches WC.

•  Downflow Installations require an internal filter accessory 

kit to be installed.

•  Horizontal Installations require the air filter system be installed 

in the return air ductwork.

NOTE TO INSTALLER:

 After installing or replacing the 

filtration system for this unit, add the following statement 

on or adjacent to the filter service panel: 

“Replace filter(s) 

installed in your system only with the same dimensional 

size filters that are being replaced.”

Unconditioned Spaces

All duct work passing through unconditioned space must 

be properly insulated to minimize duct losses and prevent 

condensation. Use insulation with an outer vapor barrier. Refer 

to local codes for insulation material requirements.
Acoustical Duct Work

Certain installations may require the use of acoustical lining 

inside the supply duct work.

•  Acoustical insulation must be in accordance with the current 

revision of the Sheet Metal and Air Conditioning Contractors 

National Association (SMACNA) application standard for 

duct liners.

•  Duct lining must be UL classified batts or blankets with a 

fire hazard classification of FHC-25/50 or less.

•  Fiber duct work may be used in place of internal duct liners if 

the fiber duct work is in accordance with the current revision 

of the SMACNA construction standard on fibrous glass 

ducts. Fibrous duct work and internal acoustical lining must 

be NFPA Class 1 air ducts when tested per UL Standard 

181 for Class 1 ducts.

Table 1. Air Filter Requirements

NOMINAL

COOLING

(TONS)

APPROXIMATE

AIR FLOW 

RANGE (CFM)

APPROXIMATE

FILTER AREA (SQ. 

IN.)*

RECOMMENDED

FILTER SIZE

(IN. X IN.)

3.0

1,100 - 1,300

625

25 x 25

4.0

1,400 - 1,800

850

18 x 24 (2 required)

5.0

1,800 - 2,200

1,000

20 x 25 (2 required)

* Based on velocity of 300 ft/min for disposable filters and 500 ft/min for 

high velocity (cleanable) Filters.

Содержание R8GE Series

Страница 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflamma...

Страница 2: ...P Propane Gas Conversion 15 START UP ADJUSTMENTS 16 Pre Start Check List 16 Start Up Procedure 16 Air Circulation 16 System Cooling 16 System Heating 16 Verifying Adjusting Temperature Rise 16 Verifyi...

Страница 3: ...brancher S assurer de les raccorder correctement S assurer que l appareil fonctionne ad quatement apr s l entretien WARNING TheseunitsarefullychargedwithR 410Arefrigerant andreadyforinstallation When...

Страница 4: ...d the air vent intake terminal See page 8 Combustionproductsmustbedischargedoutdoors Connect this unit to an approved vent system only as specified on page 8 Never test for gas leaks with an open flam...

Страница 5: ...nt Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructions D gaugement conforme aux codes d installation locaux aux...

Страница 6: ...s suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapessuivantesdoivent tresuivi...

Страница 7: ...als Carbon tetrachloride Halogen type refrigerants Cleaning solvents Cements glues paint removers varnishes etc Hydrochloric acid Masonry acid washing materials Plumbing Stack Venting Requirements Thi...

Страница 8: ...ing operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under norma...

Страница 9: ...tbelocatedaccordingtolocalbuilding codes or ordinances and these requirements The roof must be capable of handling the weight of the unit For unit weights see Table 9 page 21 Reinforce the roof if nec...

Страница 10: ...ove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Remo...

Страница 11: ...iring methods must be acceptable to authority having jurisdiction Useonlycopperwireforthelinevoltagepowersupplytothis unit See Table 4 page 12 Use proper code agency listed conduit and a conduit conne...

Страница 12: ...225 110 Table 5 Thermostat Wire Gauge Table 3 Electrical Data MODEL NUMBER HEATING INPUT BTUH NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAX...

Страница 13: ...lating blower motor has started Set the heat anticipator according to the thermostat manufacturer s instructions for heat anticipator settings Blower Speed The blower speed is preset at the factory fo...

Страница 14: ...tbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases GAS SUPPLY PIPING WARNING FIRE OR...

Страница 15: ...e carbon monoxide poisoning personal injury or death Conversion of this equipment to LP Propane gas must be made by qualified service personnel using approved factory parts Conversion to LP can be acc...

Страница 16: ...andverifythecompressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for any unusual noises If unusua...

Страница 17: ...operates for more thanfourminuteswithnoreturnair setthethermostatbelow room temperature shut off power to the unit and replace the over temperature limit control Verifying Burner Operation WARNING Un...

Страница 18: ...ignition the furnace control is locked and the red LED will blink 4 times repetitively The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out Otherwise t...

Страница 19: ...e unit 4 Turn the gas control knob to the OFF position See Figure 10 page 24 for gas valve shut off instructions 5 Disconnect the wires from the gas valve ignitor and flame sensor CAUTION Use care whe...

Страница 20: ...ustion blower will continue to operate if the flame roll out control opens Flame Sensor Proves that flame has carried over from the ignitor to the right most burner If no flame is sensed the unit will...

Страница 21: ...al Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 R8GE Dimensions Table 9 Center of Gravity Unit Shipping Weights Model Numb...

Страница 22: ...62 1113 66 T3 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T4 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T5 2015 37 1970 37 1915 39 1870 39 1805 41 1740 42 168...

Страница 23: ...E REVOLUTION SECONDS CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 1...

Страница 24: ...utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Nejamaisutiliserd outils S iln estpaspo...

Страница 25: ...SE FLAME OR GAS RELAY SHORTED PRESURE SWITCH STUCK OPEN WITH INDUCER ON PRESURE SWITCH STUCK CLOSED WITH INDUCER OFF WIRING DIAGRAM FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 10076210 05 15 FLAME ST...

Страница 26: ...NGE BLUE RED GREEN YELLOW RED RED ORANGE WHITE WHITE BLUE YELLOW BLACK GREY GREEN BLACK BLACK GREEN WHITE YELLOW RED WHITE BLACK YELLOW 460 Volt Three Phase 60Hz 3 If any of the original wire as suppl...

Страница 27: ...EFRIGERANT WHEN BELOW CURVE R8GE X36C X48C X60C Charging Chart Cooling Figure 13 Charging Chart for 3 Ton Units 3 5 TON MODELS 4 TON MODEL 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 5...

Страница 28: ...Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity...

Отзывы: