Nortek R8GE Series Скачать руководство пользователя страница 6

6

COMBUSTION AIR & VENTING REQUIREMENTS

 WARNING:

 AVERTISSEMENT:

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for 

each appliance connected to the venting system 

being placed into operation could result in carbon 

monoxide poisoning or death.
The following steps shall be followed with each 

individual appliance connected to the venting 

system being placed in operation, while all other 

appliances connected to the venting system are 

not in operation:
1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and 

horizontal pitch, as required in the National Fuel 

Gas Code, ANSI Z223.1/NFPA 54 or the CSA 

B149.1, Natural Gas and Propane Installation 

Codes and these instructions. Determine that 

there is no blockage or restriction, leakage, 

corrosion and other deficiencies which could 

cause an unsafe condition.

3. As far as practical, close all building doors and 

windows and all doors between the space in 

which the appliance(s) connected to the venting 

system are located and other spaces of the 

building.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not 

connected to the venting system. Turn on 

any exhaust fans, such as range hoods and 

bathroom exhausts, so they are operating at 

maximum speed. Do not operate a summer 

exhaust fan.

6. Follow the lighting instructions. Place the 

appliance being inspected into operation. 

Adjust the thermostat so appliance is operating 

continuously.

7. Test for spillage from draft hood equipped 

appliances at the draft hood relief opening after 

5 minutes of main burner operation. Use the 

flame of a match or candle.

8. If improper venting is observed during any of 

the above tests, the venting system must be 

corrected in accordance with the National Fuel 

Gas Code, ANSI Z223.1/NFPA 54 and/or CSA 

B149.1, Natural Gas and Propane Installation 

Codes.

9. After it has been determined that each appliance 

connected to the venting system properly vents 

when tested as outlined above, return doors, 

windows, exhaust fans, fireplace dampers and 

any other gas-fired burning appliance to their 

previous conditions of use.

RISQUE D’INTOXICATION AU MONOXYDE DE 

CARBONE

Si les étapes décrites ci-dessous ne sont pas suivies 

pour chacun des appareils raccordés au système de 

ventilation au moment de sa mise en marche, cela peut 

entraîner une intoxication au monoxyde de carbone 

ou la mort.
Les étapes suivantes doivent être suivies pour chacun 

des appareils raccordés au système de ventilation 

au moment de sa mise en marche, alors que tous les 

autres appareils raccordés au système de ventilation 

ne sont pas en marche :
1. Sceller toutes les ouvertures inutilisées du système 

de ventilation.

2. Inspecter le système de ventilation afin de vérifier 

si la taille et l’inclinaison par rapport à l’horizontale 

sont conformes aux exigences du National Fuel 

Gas Code, ANSI Z223.1/NFPA 54 ou du Code 

d’installation du gaz naturel et du propane, CSA 

B149.1 et à ces instructions. Vérifier qu’il n’y a pas 

d’obstruction ou de restriction, de fuite, de corrosion 

et d’autres problèmes qui pourraient entraîner une 

situation dangereuse.

3. Si possible, fermer toutes les portes et fenêtres 

du bâtiment ainsi que toutes les portes séparant 

l’endroit où se trouvent les appareils raccordés 

au système de ventilation et les autres zones du 

bâtiment.

4. Fermer le registre des foyers.

5. Mettre les sécheuses en marche ainsi que tous 

les autres appareils qui ne sont pas raccordés au 

système de ventilation. Mettre en marche tous les 

ventilateurs de tirage, comme celui des hottes de 

cuisine et des salles de bains, et les régler à la 

puissance maximale. Ne pas mettre en marche les 

ventilateurs d’été.

6. Suivre les instructions d’allumage. Mettre en marche 

l’appareil soumis à l’inspection. Régler le thermostat 

de manière à ce que l’appareil fonctionne en continu.

7. Vérifier la présence de fuite au niveau de l’ouverture 

du coupe-tirage des appareils qui en sont dotés 

après 5 minutes de fonctionnement du brûleur 

principal. Utiliser la flamme d’une allumette ou 

d’une bougie.

8. Si un problème de ventilation est observé pendant 

l’un des essais décrits ci-dessus, des correctifs 

doivent être apportés au système de ventilation 

conformément au National Fuel Gas Code, ANSI 

Z223.1/NFPA 54 et (ou) au Code d’installation du 

gaz naturel et du propane, CSA B149.1.

9. Une fois qu’il a été déterminé que chaque appareil 

raccordé au système de ventilation fonctionne 

correctement au moyen des essais décrits ci-

dessus, les portes, les fenêtres, les ventilateurs, 

les registres de foyer et tous les autres appareils 

de combustion alimentés au gaz doivent être remis 

dans leur état initial.

Содержание R8GE Series

Страница 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflamma...

Страница 2: ...P Propane Gas Conversion 15 START UP ADJUSTMENTS 16 Pre Start Check List 16 Start Up Procedure 16 Air Circulation 16 System Cooling 16 System Heating 16 Verifying Adjusting Temperature Rise 16 Verifyi...

Страница 3: ...brancher S assurer de les raccorder correctement S assurer que l appareil fonctionne ad quatement apr s l entretien WARNING TheseunitsarefullychargedwithR 410Arefrigerant andreadyforinstallation When...

Страница 4: ...d the air vent intake terminal See page 8 Combustionproductsmustbedischargedoutdoors Connect this unit to an approved vent system only as specified on page 8 Never test for gas leaks with an open flam...

Страница 5: ...nt Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructions D gaugement conforme aux codes d installation locaux aux...

Страница 6: ...s suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapessuivantesdoivent tresuivi...

Страница 7: ...als Carbon tetrachloride Halogen type refrigerants Cleaning solvents Cements glues paint removers varnishes etc Hydrochloric acid Masonry acid washing materials Plumbing Stack Venting Requirements Thi...

Страница 8: ...ing operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under norma...

Страница 9: ...tbelocatedaccordingtolocalbuilding codes or ordinances and these requirements The roof must be capable of handling the weight of the unit For unit weights see Table 9 page 21 Reinforce the roof if nec...

Страница 10: ...ove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Remo...

Страница 11: ...iring methods must be acceptable to authority having jurisdiction Useonlycopperwireforthelinevoltagepowersupplytothis unit See Table 4 page 12 Use proper code agency listed conduit and a conduit conne...

Страница 12: ...225 110 Table 5 Thermostat Wire Gauge Table 3 Electrical Data MODEL NUMBER HEATING INPUT BTUH NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAX...

Страница 13: ...lating blower motor has started Set the heat anticipator according to the thermostat manufacturer s instructions for heat anticipator settings Blower Speed The blower speed is preset at the factory fo...

Страница 14: ...tbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases GAS SUPPLY PIPING WARNING FIRE OR...

Страница 15: ...e carbon monoxide poisoning personal injury or death Conversion of this equipment to LP Propane gas must be made by qualified service personnel using approved factory parts Conversion to LP can be acc...

Страница 16: ...andverifythecompressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for any unusual noises If unusua...

Страница 17: ...operates for more thanfourminuteswithnoreturnair setthethermostatbelow room temperature shut off power to the unit and replace the over temperature limit control Verifying Burner Operation WARNING Un...

Страница 18: ...ignition the furnace control is locked and the red LED will blink 4 times repetitively The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out Otherwise t...

Страница 19: ...e unit 4 Turn the gas control knob to the OFF position See Figure 10 page 24 for gas valve shut off instructions 5 Disconnect the wires from the gas valve ignitor and flame sensor CAUTION Use care whe...

Страница 20: ...ustion blower will continue to operate if the flame roll out control opens Flame Sensor Proves that flame has carried over from the ignitor to the right most burner If no flame is sensed the unit will...

Страница 21: ...al Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 R8GE Dimensions Table 9 Center of Gravity Unit Shipping Weights Model Numb...

Страница 22: ...62 1113 66 T3 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T4 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T5 2015 37 1970 37 1915 39 1870 39 1805 41 1740 42 168...

Страница 23: ...E REVOLUTION SECONDS CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 1...

Страница 24: ...utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Nejamaisutiliserd outils S iln estpaspo...

Страница 25: ...SE FLAME OR GAS RELAY SHORTED PRESURE SWITCH STUCK OPEN WITH INDUCER ON PRESURE SWITCH STUCK CLOSED WITH INDUCER OFF WIRING DIAGRAM FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 10076210 05 15 FLAME ST...

Страница 26: ...NGE BLUE RED GREEN YELLOW RED RED ORANGE WHITE WHITE BLUE YELLOW BLACK GREY GREEN BLACK BLACK GREEN WHITE YELLOW RED WHITE BLACK YELLOW 460 Volt Three Phase 60Hz 3 If any of the original wire as suppl...

Страница 27: ...EFRIGERANT WHEN BELOW CURVE R8GE X36C X48C X60C Charging Chart Cooling Figure 13 Charging Chart for 3 Ton Units 3 5 TON MODELS 4 TON MODEL 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 5...

Страница 28: ...Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity...