Nortek R8GE Series Скачать руководство пользователя страница 18

18

2. Remove the regulator cap. Turn the high fire adjusting screw 

clockwise to increase the pressure or counterclockwise to 

reduce the pressure.

3. Replace the regulator cap after adjustments are complete.

OPERATING SEQUENCE

The operating sequences for the heating, cooling, and fan 

modes are described below. Refer to the field and 

Figure 11 

(page 25)

 and 

Figure 12 (page 26)

.

Heating Mode

1. On a call for heat, the thermostat closes and applies 24 

VAC to terminal 

W

 on the control board.

2. The control board checks for continuity on the 24 VAC limit 

control circuit, over-temperature limit switch, flame rollout 

switches, and blocked vent switch in series. If an open limit 

is detected, the control board will energize the inducer 

blower. All other system functions will be inoperable until 

the limit circuit closes. While the limit is open, the red LED 

will pulse at a rate of 1 blink per unit time.

3. The furnace control checks for continuity (24 VAC) across 

the pressure switch. If the pressure switch is closed, the 

heat mode sequence will not continue. If it remains closed 

for 10 seconds, the red LED will flash 3 times repetitively 

until the fault condition clears.

4. The inducer energizes (if pressure switch is open).

5. The pressure switch will close. If the pressure switch does 

not close after 10 seconds, the fault LED will flash 2 times 

and the inducer will continue to run until the switch is closed.

6. The inducer will pre-purge for 30 seconds and then the 

igniter will start its warm-up as follows:

 

Initial Power up:

 After 30 seconds of igniter warm-up, the 

gas valves (24 VAC) will open. The igniter circuit will stay 

energized for 3 seconds after the gas valve opens.

 

After Initial Power up

: The control has a programmed adaptive 

ignition feature which varies the warm-up period as follows: 

If ignition is successful the warm-up is reduced by 3 seconds 

on each subsequent call for heat until ignition failure occurs. 

Upon ignition failure, the warm-up is increased by 3 seconds 

on the next try. If successful, the timing remains fixed at 

this level. In general, whenever ignition failure occurs the 

warm-up interval is increased by 3 seconds on the next try. 

And if successful, it remains there. Minimum and maximum 

warm-up time limits are set at 6 and 54 seconds.

7. The furnace control must prove flame via the flame sensor 

5 seconds after the gas valves open. If flame is sensed, 

burners are on and the igniter cools off. If no flame is sensed, 

the gas valve closes immediately and the inducer continues 

to run. A second trial for ignition (step 6) begins. If no flame 

is sensed on the fifth try for ignition, the furnace control is 

locked and the red LED will blink 4 times repetitively. The 

thermostat must be opened for at least ten seconds to reset 

the furnace control after a lock out. Otherwise, the furnace 

will attempt another ignition sequence in 1 hour.

8. After the gas valve opens (30 seconds), the blower will ramp 

to the selected airflow and continues to run.

9. When the thermostat has been satisfied, the 

W

 terminal on 

the integrated control is de-energized.

10. The gas valve circuit is de-energized and the gas vallve 

closes.

11. The inducer motor will continue to run for the post purge 

period of 25 seconds.

12. The main blower will continue to run for the BLOWER OFF 

delay of 135 seconds.

13. After the BLOWER OFF timer has been satisfied, the 

integrated control de-energizes the main circulating blower 

circuit.

Cooling Mode

1. On a call for cooling, the thermostat closes and applies 24 

VAC to the green and yellow leads in the low voltage area.

2. The green lead applies 24VAC to the 

G

 terminal of the 

integrated control, energizing the main circulating blower 

circuit at the cooling speed.

3. The yellow lead applies 24VAC to the contactor.

4. When the thermostat is satisfied, the contactor and integrated 

control de-energize.

5. The circulating blower motor de-energizes after a 85-90 

second delay.

Fan Mode

1. On a call for fan operation, the thermostat applies 24 VAC to 

the green lead connected to the 

G

 terminal of the integrated 

control.

2. The circulating blower is energized immediately at the 

heating speed if 2-SPD is selected or fan only speed if 

3-SPD is selected on the control. 

NOTE:

 If a call for heat 

occurs, the circulating blower de-energizes prior to normal 

heating cycle.

EQUIPMENT MAINTENANCE

 WARNING:

ELECTRICAL SHOCK, FIRE OR

EXPLOSION HAZARD

Failure to follow safety warnings exactly could 

result in serious injury, death or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.
•  Before servicing, disconnect all electrical power 

to furnace.

•  When servicing controls, label all wires prior to 

disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

 AVERTISSEMENT:

RISQUE D’ÉLECTROCUTION, D’INCENDIE

OU D’EXPLOSION

Si les consignes de sécurité ne sont pas suivies à la 

lettre, cela peut entraîner la mort, de graves blessures, un 

fonctionnement dangereux ou des dommages matériels.
Un entretien inadéquat peut entraîner la mort, de 

graves blessures, un fonctionnement dangereux ou 

des dommages matériels.
•  Avant de faire l’entretien de l’appareil de chauffage, 

le débrancher de l’alimentation électrique.

• Avant l’entretien des commandes, étiqueter tous 

les fils avant de les déconnecter. Rebrancher 

correctement les fils.

•  Vérifier que l’appareil fonctionne correctement après 

l’entretien.

Содержание R8GE Series

Страница 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflamma...

Страница 2: ...P Propane Gas Conversion 15 START UP ADJUSTMENTS 16 Pre Start Check List 16 Start Up Procedure 16 Air Circulation 16 System Cooling 16 System Heating 16 Verifying Adjusting Temperature Rise 16 Verifyi...

Страница 3: ...brancher S assurer de les raccorder correctement S assurer que l appareil fonctionne ad quatement apr s l entretien WARNING TheseunitsarefullychargedwithR 410Arefrigerant andreadyforinstallation When...

Страница 4: ...d the air vent intake terminal See page 8 Combustionproductsmustbedischargedoutdoors Connect this unit to an approved vent system only as specified on page 8 Never test for gas leaks with an open flam...

Страница 5: ...nt Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructions D gaugement conforme aux codes d installation locaux aux...

Страница 6: ...s suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapessuivantesdoivent tresuivi...

Страница 7: ...als Carbon tetrachloride Halogen type refrigerants Cleaning solvents Cements glues paint removers varnishes etc Hydrochloric acid Masonry acid washing materials Plumbing Stack Venting Requirements Thi...

Страница 8: ...ing operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under norma...

Страница 9: ...tbelocatedaccordingtolocalbuilding codes or ordinances and these requirements The roof must be capable of handling the weight of the unit For unit weights see Table 9 page 21 Reinforce the roof if nec...

Страница 10: ...ove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Remo...

Страница 11: ...iring methods must be acceptable to authority having jurisdiction Useonlycopperwireforthelinevoltagepowersupplytothis unit See Table 4 page 12 Use proper code agency listed conduit and a conduit conne...

Страница 12: ...225 110 Table 5 Thermostat Wire Gauge Table 3 Electrical Data MODEL NUMBER HEATING INPUT BTUH NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAX...

Страница 13: ...lating blower motor has started Set the heat anticipator according to the thermostat manufacturer s instructions for heat anticipator settings Blower Speed The blower speed is preset at the factory fo...

Страница 14: ...tbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases GAS SUPPLY PIPING WARNING FIRE OR...

Страница 15: ...e carbon monoxide poisoning personal injury or death Conversion of this equipment to LP Propane gas must be made by qualified service personnel using approved factory parts Conversion to LP can be acc...

Страница 16: ...andverifythecompressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for any unusual noises If unusua...

Страница 17: ...operates for more thanfourminuteswithnoreturnair setthethermostatbelow room temperature shut off power to the unit and replace the over temperature limit control Verifying Burner Operation WARNING Un...

Страница 18: ...ignition the furnace control is locked and the red LED will blink 4 times repetitively The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out Otherwise t...

Страница 19: ...e unit 4 Turn the gas control knob to the OFF position See Figure 10 page 24 for gas valve shut off instructions 5 Disconnect the wires from the gas valve ignitor and flame sensor CAUTION Use care whe...

Страница 20: ...ustion blower will continue to operate if the flame roll out control opens Flame Sensor Proves that flame has carried over from the ignitor to the right most burner If no flame is sensed the unit will...

Страница 21: ...al Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 R8GE Dimensions Table 9 Center of Gravity Unit Shipping Weights Model Numb...

Страница 22: ...62 1113 66 T3 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T4 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T5 2015 37 1970 37 1915 39 1870 39 1805 41 1740 42 168...

Страница 23: ...E REVOLUTION SECONDS CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 1...

Страница 24: ...utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Nejamaisutiliserd outils S iln estpaspo...

Страница 25: ...SE FLAME OR GAS RELAY SHORTED PRESURE SWITCH STUCK OPEN WITH INDUCER ON PRESURE SWITCH STUCK CLOSED WITH INDUCER OFF WIRING DIAGRAM FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 10076210 05 15 FLAME ST...

Страница 26: ...NGE BLUE RED GREEN YELLOW RED RED ORANGE WHITE WHITE BLUE YELLOW BLACK GREY GREEN BLACK BLACK GREEN WHITE YELLOW RED WHITE BLACK YELLOW 460 Volt Three Phase 60Hz 3 If any of the original wire as suppl...

Страница 27: ...EFRIGERANT WHEN BELOW CURVE R8GE X36C X48C X60C Charging Chart Cooling Figure 13 Charging Chart for 3 Ton Units 3 5 TON MODELS 4 TON MODEL 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 5...

Страница 28: ...Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity...

Отзывы: