background image

6

air Filter requirements

 Warning:

never operate the unit without a filter in place. 

dust and lint could accumulate on internal parts, 

resulting in loss of efficiency, equipment damage 

and possible fire. replace disposable filters with 

the same type and size.

•  Air  filter(s)  are  not  supplied  and  must  be  installed  in 

the unit or in the return air system by the installer. Only 

three phase units are equipped with an internal filter rack 

assembly.

•  If using an Economizer or Fresh Air Equipment, the factory 

installed filter rack must be removed prior to installation. 
See 

page 7

 for removal instructions.

•  All  return  air  must  pass  through  the  filters  before 

entering the unit.

 

Recommended filter sizes are listed in  

Table 1

note:

 It is important that all filters be kept clean 

and replaced frequently to ensure proper operation of 

unit. Dirty or clogged filters will reduce the efficiency of 

the unit and result in unit shutdowns.

•  Air filter pressure drop must not exceed 0.08 inches WC.

 

When replacing the air filters, a suitable air filter must be 

installed upstream of the evaporator coil of the return air 

system.

•  Downflow Installations require an internal filter accessory 

kit to be installed.

•  Horizontal  Installations  require  the  air  filter  system  be 

installed in the return air ductwork.

air conditioner inStallation

Packaging removal

Remove the shipping carton and User’s Manual from the 

equipment. Take care not to damage the tubing connections 
when removing the carton. For rooftop installations, remove 
and discard the two supports attached beneath the unit.

rigging & Hoisting

 Warning:

to avoid the risk of property damage, personal 

injury, or death, it is the rigger’s responsibility 

to ensure that whatever means are used to hoist 

the unit are safe and adequate:

•  The lifting equipment must be adequate for the 

load. refer to 

table 6 (page 13)

 for unit weights.

•  The unit must be lifted from the holes in the 

base rails using cables or chains.

•  Spreader bars are required to protect the unit 

and ensure even loading.

•  Keep the unit in an upright position at all times. 

the rigging must be located outside the units 

center of gravity. refer to 

Figure 8 (page 13)

 

for locating the center of gravity.

•  All  panels  must  be  securely  in  place  during 

rigging and hoisting.

Minimum clearance requirements

P8SD units are certified as cooling equipment for outdoor 
installation only. 

Figure 2 (page 5)

 displays the minimum 

clearances to obstructions for both Downflow and Horizontal 

discharge.

Units may be installed on wood flooring or on Class A, B, 

or C roof covering material when used with bottom supply 

and return air ducts. If using bottom discharge with return air 

ducts, a roof curb must be installed prior to unit installation. 

See Rigging and Hoisting section for setting of the unit 
(

page 6

).

ground level

Ground level installations must be located according to local 

building codes or ordinances and these requirements:

•  Clearances must be in accordance with those shown in 

Figure 2

.

•  A suitable mounting pad must be provided and separate 

from the building foundation. The pad must be level to 

ensure proper condensate disposal and strong enough 

to support the unit’s weight. The slab height must be a 

minimum  of  2”  (5cm)  above  grade  and  with  adequate 

drainage. See 

Figure 3 (page 7)

.

•  Allow sufficient clearances for access to the internal filter 

rack.

table 1. internal Filter Size requirements.

unit Size

internal Filter Size

P8SE-X36

P8SE-X48

(2) 14” x 25”

or

(2) 14” x 25”

P8SE-X60

(2) 18” x 25”

or

(2) 18” x 25”

Содержание P8SD-X36C

Страница 1: ...sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local...

Страница 2: ... 7 Horizontal to Downflow Conversion 7 Removal of Internal Filter Rack 7 Installing Filters in the Filter Rack 7 Removing Filters from Filter Rack 7 Condensate Drain 7 ELECTRICAL WIRING 8 Pre Electrical Checklist 8 Line Voltage 8 Grounding 8 Unbalanced 3 Phase Supply Voltage 8 Optional Outdoor Thermostat 9 Optional Electric Heater Kits 9 Airflow 10 Blower Speed 10 Fixed Torque ECM Motor 11 START U...

Страница 3: ...all instructions before servicing this equipment Pay attention to all safety warnings and any other special notes highlighted in the manual Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored WARNING indicatesapotentiallyhazardoussituationthatifnotavoided couldresultinpersonalinjuryordeath CAUTIONindicatesa potentially ...

Страница 4: ...e materials including gasoline and any other flammable vapors and liquids in the vicinity of the unit WARNING The safety information listed below must be followed during the installation service and operation of this unit Unqualified individuals shouldnotattempttointerprettheseinstructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equ...

Страница 5: ...sted for capacity and efficiency in accordance with AHRI Standards This unit will provide many years of safe and dependable comfort providing it is properly installed and maintained With regular maintenance this unit will operate reliably year after year Abuse improper use and or improper maintenance can shorten the life of the appliance and create unsafe hazards Pre Installation Check Before you ...

Страница 6: ...t is the rigger s responsibility to ensure that whatever means are used to hoist the unit are safe and adequate The lifting equipment must be adequate for the load Refer to Table 6 page 13 for unit weights The unit must be lifted from the holes in the base rails using cables or chains Spreader bars are required to protect the unit and ensure even loading Keep the unit in an upright position at all...

Страница 7: ... NOTE The assembly can now be easily collapsed and removed from the unit See Figure 5 for filter rack securing screw locations Installing Filters in the Filter Rack 1 Remove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide the first filter between bot...

Страница 8: ...lance occurs when the voltages of all phases of a 3 phase power supply are no longer equal This unbalancereducesmotorefficiencyandperformance Some underlying causes of voltage unbalance may include Lack of symmetry in transmission lines large single phase loads andunbalancedoroverloadedtransformers Amotorshould never be operated when a phase imbalance in supply is greater than 2 Perform the follow...

Страница 9: ...alues given in step 1 the BC voltage 460V is the greatest difference in value from the average 460 454 6 454 451 3 454 453 1 4 Determine percent of voltage imbalance by using the results from steps 2 3 in the following equation 6 454 100 x 1 32 Example max voltage deviation from average voltage 100 x average voltage Voltage Imbalance The amount of phase imbalance 1 32 is satisfactory since the amo...

Страница 10: ... 19 1399 20 Tap 4 46 1968 14 1926 15 1873 15 1823 16 1774 16 1717 17 1665 17 1619 18 Tap 5 60 2242 13 2183 13 2143 13 2098 14 2044 14 1995 14 1953 15 1907 15 X60 Tap 1 21 1161 24 1116 25 1084 26 1031 28 954 30 895 32 834 34 779 37 Tap 2 31 1553 18 1521 19 1474 19 1437 20 1379 21 1335 21 1276 22 1183 24 Tap 3 40 1862 15 1818 16 1766 16 1731 16 1678 17 1635 17 1599 18 1539 18 Tap 4 46 2009 14 1973 1...

Страница 11: ...ze 2 Feeltheairbeingcirculatedbytheindoorblowerandverify that it is cooler than ambient temperature Listen for any unusual noises If unusual sounds occur determine the source of the noise and correct as necessary 3 Allow the cooling system to operate for several minutes and then set the temperature selector above room temperature Verify the fan and compressor cycle off with the thermostat NOTE The...

Страница 12: ...ipment and at listed airflows for the indoor coil Assemblies of indoor coils and outdoor units not listed are not recommended Charging the Unit in AC Mode Outdoor Temperatures Above 65F 1 With the system operating at steady state measure the liquid refrigerant pressure in psig at the service valve 2 Measure the liquid refrigerant temperature in Fahrenheit at the service valve 3 For the temperature...

Страница 13: ...ioner Dimensions FIGURES TABLES Table 6 Center of Gravity Unit Shipping Weights Model Number P8SE Unit Shipping Weight Center of Gravity Height C in inches A B with base rails without base rails X36 375 29 20 5 35 0 30 76 X48 398 29 20 5 35 0 30 76 X60 437 27 25 23 5 43 0 39 3 NOTE To determine unit weight subtract 21lbs from unit shipping weight Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 ...

Страница 14: ...ions de plus de 150 V la terre 5 For supply wire ampacities and overcurrent protection see unit rating plate 711011A Replaces 7110110 11 14 1 2 3 4 5 6 7 8 9 R C S 1 5 2 6 3 4 TO 208 230 VAC POWER SUPPLY 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 COMPRESSOR COMPRESSOR CONTACTOR CAPACITOR PLUG A OUTDOOR FAN MOTOR PRESSURE SWITCH TO DISCHARGE AIR SENSOR 3 AMP FUSE T2 T1 ...

Страница 15: ...GREEN RED RED RED BROWN ORANGE RED BLACK BLUE WHITE BLACK BLACK BLACK YELLOW BLACK BLUE BLACK WHITE RED YELLOW YELLOW BK BK BK WHITE WHITE WHITE WHITE WIRING DIAGRAM NOTES FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 460 Volt Convertable Packaged Air Conditioner Three Phase 60Hz 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 If any of the original wir...

Страница 16: ...SSORY HEAT PLUG C W1 R Y2 Y1 G TERMINAL STRIP Red Black Green FROMTRANSFORMER FROM CONTACTOR Optional Check T stat Instructions Figure 11 AC Thermostat Connections 208 230V 1 2 3 4 5 6 7 8 9 10 11 12 24V Common R Y2 C G W Gray Yellow Blue ECONOMIZER PLUG INDOOR THERMOSTAT SUB BASE 1 2 3 4 5 6 7 8 9 Orange ACCESSORY HEAT PLUG C W1 R Y2 Y1 G TERMINAL STRIP Red Black Green FROMTRANSFORMER FROM CONTAC...

Отзывы: