background image

11

Fixed torque ecM Motor

1. Shut off all electrical power to the unit and remove the 

blower panel. Locate the orange and red wires terminated to 

the blower motor. 

note:

 The orange wire controls cooling 

operation while the red wire controls heating operation.

2. Verify the required speed from the airflow data found in 

Table 4

. Place appropriate wire on the correct motor speed 

tap for the required airflow point.

Start uP & SySteM cHeck

Pre-Start check list

  Verify the unit is level and allows condensate to drain.

  Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/control 

panels are in place.

  Verify that the duct work is sealed to prevent air leakage. 

  Verify that the line voltage power leads are securely 

connected and the unit is properly grounded.

   Verify that the low voltage wires are securely connected 

to the correct leads on the low voltage terminal strip.

  Verify that the outdoor fan turns freely.

  Verify that the power supply branch circuit overcurrent 

protection is sized properly.

  Verify that the thermostat is wired correctly. The thermostat 

system mode should be set to OFF and the thermostat 

fan mode should be set to AUTO.

Start-up Procedure

Close all electrical disconnects to energize the system.

Air Circulation

Leave the thermostat system mode on OFF, and set the fan 

mode to ON. Blower should run continuously. Check the air 

delivery at the supply registers and adjust register openings 

for balanced air distribution. Examine ductwork for leaks or 

obstruction if insufficient air is detected. Set the thermostat 

fan mode to AUTO. The blower should stop running.

 Warning:

if the unit is equipped with a crankcase heater, 

allow 24 hours prior to continuing the start up 

procedures to allow for heating of the refrigerant 

compressor crankcase. Failure to comply may 

result in damage and could cause premature 

failure of the system. this warning should be 

followed at initial start up and any time the power 

has been removed for 12 hours or longer.

System Cooling

1.  Set the thermostat’s system mode to COOL and the fan 

mode to AUTO. Gradually lower the thermostats setpoint 

below room temperature and verify the outdoor unit and 

indoor blower energize.

2.  Feel the air being circulated by the indoor blower and verify 

that it is cooler than ambient temperature. Listen for any 

unusual noises. If unusual sounds occur, determine the 

source of the noise and correct as necessary.

3.  Allow the cooling system to operate for several minutes 

and then set the temperature selector above room 

temperature. Verify the fan and compressor cycle off 

with the thermostat. 

note:

 The blower should also stop 

unless fan mode is set to ON.

System Heating

If the unit has been equipped with optional electric heater 

kits, set the thermostat's system mode to HEAT and the fan 

mode to AUTO. Verify the compressor and outdoor fan are 

not energized but that the blower and heaters are. Feel the 

air being circulated by the indoor blower and verify that it is 

warmer than ambient temperature. Listen for any unusual 

noises. If unusual sounds occur, determine the source of 

the noise and correct as necessary.

air conditioner Maintenance

 Warning:

to prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

the unit may have more than one electrical 

supply.

Proper maintenance is important to achieve optimum 

performance from the Air Conditioner. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these 

skills, contact your dealer for maintenance. Consult your 

local dealer about the availability of maintenance contracts. 

Routine maintenance should include the following:

•  Inspect  the  condensate  drain  and  outdoor  coil  at  the 

beginning of each cooling season. Remove any debris. 

Clean the outdoor coil and louvers as necessary using a 

mild detergent and water. Rinse thoroughly with water.

•  Inspect  the  electrical  connections  for  tightness  at  the 

beginning of each heating and cooling season. Service 

as necessary.

•  Inspect and clean or replace air filters at the beginning 

of each heating and cooling season, or more frequently 

if required.

 caution:

the unit should never be operated without a 

filter in the return air system. replace disposable 

filters with the same type and size.

•  The motors for the circulating air blower and the outdoor 

fan are pre-lubricated at the factory. No further oiling is 

required for the life of this product.

kW/H

btu/H

5

17,060

8

27,297

9

30,709

10

34,121

15

51,182

20

68,242

table 5. kW & btu/h ratings

Содержание P8SD-X36C

Страница 1: ...sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local...

Страница 2: ... 7 Horizontal to Downflow Conversion 7 Removal of Internal Filter Rack 7 Installing Filters in the Filter Rack 7 Removing Filters from Filter Rack 7 Condensate Drain 7 ELECTRICAL WIRING 8 Pre Electrical Checklist 8 Line Voltage 8 Grounding 8 Unbalanced 3 Phase Supply Voltage 8 Optional Outdoor Thermostat 9 Optional Electric Heater Kits 9 Airflow 10 Blower Speed 10 Fixed Torque ECM Motor 11 START U...

Страница 3: ...all instructions before servicing this equipment Pay attention to all safety warnings and any other special notes highlighted in the manual Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored WARNING indicatesapotentiallyhazardoussituationthatifnotavoided couldresultinpersonalinjuryordeath CAUTIONindicatesa potentially ...

Страница 4: ...e materials including gasoline and any other flammable vapors and liquids in the vicinity of the unit WARNING The safety information listed below must be followed during the installation service and operation of this unit Unqualified individuals shouldnotattempttointerprettheseinstructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equ...

Страница 5: ...sted for capacity and efficiency in accordance with AHRI Standards This unit will provide many years of safe and dependable comfort providing it is properly installed and maintained With regular maintenance this unit will operate reliably year after year Abuse improper use and or improper maintenance can shorten the life of the appliance and create unsafe hazards Pre Installation Check Before you ...

Страница 6: ...t is the rigger s responsibility to ensure that whatever means are used to hoist the unit are safe and adequate The lifting equipment must be adequate for the load Refer to Table 6 page 13 for unit weights The unit must be lifted from the holes in the base rails using cables or chains Spreader bars are required to protect the unit and ensure even loading Keep the unit in an upright position at all...

Страница 7: ... NOTE The assembly can now be easily collapsed and removed from the unit See Figure 5 for filter rack securing screw locations Installing Filters in the Filter Rack 1 Remove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide the first filter between bot...

Страница 8: ...lance occurs when the voltages of all phases of a 3 phase power supply are no longer equal This unbalancereducesmotorefficiencyandperformance Some underlying causes of voltage unbalance may include Lack of symmetry in transmission lines large single phase loads andunbalancedoroverloadedtransformers Amotorshould never be operated when a phase imbalance in supply is greater than 2 Perform the follow...

Страница 9: ...alues given in step 1 the BC voltage 460V is the greatest difference in value from the average 460 454 6 454 451 3 454 453 1 4 Determine percent of voltage imbalance by using the results from steps 2 3 in the following equation 6 454 100 x 1 32 Example max voltage deviation from average voltage 100 x average voltage Voltage Imbalance The amount of phase imbalance 1 32 is satisfactory since the amo...

Страница 10: ... 19 1399 20 Tap 4 46 1968 14 1926 15 1873 15 1823 16 1774 16 1717 17 1665 17 1619 18 Tap 5 60 2242 13 2183 13 2143 13 2098 14 2044 14 1995 14 1953 15 1907 15 X60 Tap 1 21 1161 24 1116 25 1084 26 1031 28 954 30 895 32 834 34 779 37 Tap 2 31 1553 18 1521 19 1474 19 1437 20 1379 21 1335 21 1276 22 1183 24 Tap 3 40 1862 15 1818 16 1766 16 1731 16 1678 17 1635 17 1599 18 1539 18 Tap 4 46 2009 14 1973 1...

Страница 11: ...ze 2 Feeltheairbeingcirculatedbytheindoorblowerandverify that it is cooler than ambient temperature Listen for any unusual noises If unusual sounds occur determine the source of the noise and correct as necessary 3 Allow the cooling system to operate for several minutes and then set the temperature selector above room temperature Verify the fan and compressor cycle off with the thermostat NOTE The...

Страница 12: ...ipment and at listed airflows for the indoor coil Assemblies of indoor coils and outdoor units not listed are not recommended Charging the Unit in AC Mode Outdoor Temperatures Above 65F 1 With the system operating at steady state measure the liquid refrigerant pressure in psig at the service valve 2 Measure the liquid refrigerant temperature in Fahrenheit at the service valve 3 For the temperature...

Страница 13: ...ioner Dimensions FIGURES TABLES Table 6 Center of Gravity Unit Shipping Weights Model Number P8SE Unit Shipping Weight Center of Gravity Height C in inches A B with base rails without base rails X36 375 29 20 5 35 0 30 76 X48 398 29 20 5 35 0 30 76 X60 437 27 25 23 5 43 0 39 3 NOTE To determine unit weight subtract 21lbs from unit shipping weight Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 ...

Страница 14: ...ions de plus de 150 V la terre 5 For supply wire ampacities and overcurrent protection see unit rating plate 711011A Replaces 7110110 11 14 1 2 3 4 5 6 7 8 9 R C S 1 5 2 6 3 4 TO 208 230 VAC POWER SUPPLY 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 COMPRESSOR COMPRESSOR CONTACTOR CAPACITOR PLUG A OUTDOOR FAN MOTOR PRESSURE SWITCH TO DISCHARGE AIR SENSOR 3 AMP FUSE T2 T1 ...

Страница 15: ...GREEN RED RED RED BROWN ORANGE RED BLACK BLUE WHITE BLACK BLACK BLACK YELLOW BLACK BLUE BLACK WHITE RED YELLOW YELLOW BK BK BK WHITE WHITE WHITE WHITE WIRING DIAGRAM NOTES FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 460 Volt Convertable Packaged Air Conditioner Three Phase 60Hz 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 If any of the original wir...

Страница 16: ...SSORY HEAT PLUG C W1 R Y2 Y1 G TERMINAL STRIP Red Black Green FROMTRANSFORMER FROM CONTACTOR Optional Check T stat Instructions Figure 11 AC Thermostat Connections 208 230V 1 2 3 4 5 6 7 8 9 10 11 12 24V Common R Y2 C G W Gray Yellow Blue ECONOMIZER PLUG INDOOR THERMOSTAT SUB BASE 1 2 3 4 5 6 7 8 9 Orange ACCESSORY HEAT PLUG C W1 R Y2 Y1 G TERMINAL STRIP Red Black Green FROMTRANSFORMER FROM CONTAC...

Отзывы: