REQUIREMENTS & CODES

• This furnace must be installed in accordance with 

these instructions, all applicable local building codes 

and the current revision of the National Fuel Gas Code 

(NFPA54/ANSI Z223.1) or the Natural Gas and Propane 

Installation Code, CAN/CSA B149.1.

• Use only with type of gas approved for this furnace. 

Refer to the furnace rating plate.

• Install this furnace in accordance to the minimum 

clearances to combustible materials listed in 

Table 1, 

(page 6)

.

•  Provide adequate combustion and ventilation air to the 

furnace space as specified on 

page 7

Do not block 

or obstruct air openings on the furnace, air openings 

to the area where the furnace is installed, or the space 

around the furnace.

• Combustion products must be discharged outdoors. 

Connect this furnace to an approved vent system, as 

specified on 

page 10

.

• Never test for gas leaks with an open flame. Use 

a commercially available soap solution to check all 

connections. See 

page 17

.

• This furnace is designed to operate with a maximum 

external pressure rise of 0.3 inches of water column. 

NOTE 1:

 The static pressure measurement should not 

include the coil (if applicable). Consult the rating plate 

for the proper circulating air flow and temperature rise.

 

NOTE 2:

 It is important that the duct system be designed 

to handle the desired flow rate and external pressure 

rise. An improperly designed duct system can result in 

nuisance shutdowns, and comfort or noise issues.

•  When supply ducts carry air circulated by the furnace 

to areas outside the space containing the furnace, the 

return air shall also be handled through the front door 

of the furnace. Make sure there is sufficient return air 

through the door. See return air connections 

page 7

.

• Additional information listed below is for reference 

purposes only and does not necessarily have jurisdiction 

over local or state codes. Always consult with local 

authorities before installing any gas appliance.

Combustion & Ventilation Air

•  US: National Fuel Gas Code (NFGC), Air for Combustion and 

Ventilation

• CANADA: Natural Gas and Propane Installation Codes 

(NSCNGPIC), Venting Systems and Air Supply for Appliances

Duct Systems

•  US and CANADA: Air Conditioning Contractors Association 

(ACCA) Manual D, Sheet Metal and Air Conditioning 

Contractors National Association (SMACNA), or American 

Society of Heating, Refrigeration, and Air Conditioning 

Engineers (ASHRAE) Fundamentals Handbook

Electrical Connections

•  US: National Electrical Code (NEC) ANSI/NFPA 70

•  CANADA: Canadian Electrical Code CSA C22.1

Gas Piping & Gas Pipe Pressure Testing

•  US: NFGC and National Plumbing Codes

•  CANADA: NSCNGPIC

General Installation

•  US: Current edition of the NFGC and the NFPA 90B. For 

copies, contact the National Fire Protection Association Inc., 

Batterymarch Park, Quincy, MA 02269; or American Gas 

Association, 400 N. Capitol, N.W., Washington DC 20001 or 

www.NFPA.org

•  CANADA: NSCNGPIC. For a copy, contact Standard Sales, 

CSA International, 178 Rexdale Boulevard, Etobicoke 

(Toronto), Ontario, M9W 1R3 Canada

Safety

•  US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the Installation 

Standards, Warm Air Heating and Air Conditioning Systems 

ANSI/NFPA 90B.

•  Federal Manufactured Home Constructions & Safety Standard 

(H.U.D. Title 24, Part 3280.707[a][2])

• The Standard for Manufactured Home Installations 

(Manufactured Home Sites, Communities, and Set-Ups) ANSI 

A225.1 and/or CAN/CSA-2240 MH Series).

•  American National Standard (ANSI-119.2/NFPA-501C) for 

all recreational vehicle installations.

•  CANADA: CAN/CSA-B149.1 and .2–M00 National Standard 

of Canada. (NSCNGPIC)

• The Commonwealth of Massachusetts requires 

compliance with regulation 248 CMR 4.00 and 5.00 for 

installation of through – the – wall vented gas appliances 

as follows:

1. For direct-vent appliances, mechanical-vent heating 

appliances or domestic hot water equipment, where the 

bottom of the vent terminal and the air intake is installed 

below four feet above grade the following requirements 

must be satisfied:

a.) A carbon monoxide (CO) detector and alarm shall be 

placed on each floor level where there are bedrooms. 

The detector shall comply with NFPA 720 (2005 

Edition) and be mounted in the living area outside 

the bedroom(s).

b.) A (CO) detector shall be located in the room that 

houses the appliance or equipment and shall:

• Be powered by the same electrical circuit as the 

appliance or equipment. Only one service switch shall 

power the appliance and the (CO) detector;

•  Have battery back-up power;

• Meet ANSI/UL 2034 Standards and comply with 

NFPA 720 (2005 Edition); and Approved and listed 

by a Nationally Recognized Testing Laboratory as 

recognized under 527 CMR.

c.)  A Product-approved vent terminal must be used, and 

if applicable, a product-approved air intake must be 

used. Installation shall be in strict compliance with the 

manufacturer’s instructions. A copy of the installation 

instructions shall remain with the appliance or 

equipment at the completion of the installation.

d.) A metal or plastic identification plate shall be mounted 

at the exterior of the building, 4 feet directly above 

the location of vent terminal. The plate shall be of 

sufficient size, easily read from a distance of eight 

feet away, and read “Gas Vent Directly Below”.

Содержание MG1 Series

Страница 1: ...ier call the fire department QUE FAIRE S IL Y A UNE ODEUR DE GAZ N essayez d allumer aucun appareil Ne touchez aucun interrupteur lectrique n utilisez aucun t l phone dans le b timent vacuez l immeubl...

Страница 2: ...nversion to Propane LP Gas 19 Atmospheric Direct Ignition Furnaces 19 Measuring the Supply Gas Pressure 19 Measuring the Manifold Pressure 19 STARTUP ADJUSTMENTS 20 Operating Instructions Direct Ignit...

Страница 3: ...pendant l installation l entretien et le fonctionnement de cette fournaise Le non respect des recommandations de s curit peut causer des dommages l quipement ou des blessures graves voire mortelles A...

Страница 4: ...ANSI NFPA 70 CANADA Canadian Electrical Code CSA C22 1 Gas Piping Gas Pipe Pressure Testing US NFGC and National Plumbing Codes CANADA NSCNGPIC General Installation US Current edition of the NFGC and...

Страница 5: ...sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide min 250 sq in 1613 cm open free area in front or side...

Страница 6: ...e a louvered door with a minimum of 250 in2 free area with the openings in the closet door in line with the louvered openings in the furnace door A fully louvered closet door may be used See Circulati...

Страница 7: ...ode ANSI C1 NFPA 70 Gaspipingisnotruninorthroughthereturnductsystem CAUTION HAZARDOFASPHYXIATION Negativepressure inside the closet with closet door closed and the furnace blower operating on high spe...

Страница 8: ...1 7 8 2 7 8 C L Figure 7 Cut Out Dimensions for Round Duct Connectors Bend tabs up 90 Mounting Plate Duct Connector Connector Tabs Supply Air Duct Hole for Gas Line Wood Floor Figure 8 Standard Duct...

Страница 9: ...to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 8 For round ducts see Figure 7 page 8 1 Measure 10 from the rear wall or alcove and mark the centerline...

Страница 10: ...ector and the mounting plate to the wood floor with appropriate size screws 5 Connect the round supply duct to the underside of the duct connector and secure them with field supplied sheet metal screw...

Страница 11: ...ING F S AW1523 0 2 4 A S 15 23 F S AW2135 0 2 4 A S 21 35 F S AW2747 0 2 4 A S 27 47 F S AW3563 0 2 4 A S 35 63 F S AW5195 0 2 4 A S 51 95 NOTE Not all models are available Check with your local distr...

Страница 12: ...ough the opening cut on the roof 3 Connect inner flue pipe to vent collar of the furnace See Figure 22 4 Connectcombustionairpipetofurnacecollarwithsheet metal screw See Figure 22 NOTES Itisrecommende...

Страница 13: ...stallations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes It is recommended that 115VAC line voltage be supplied to the f...

Страница 14: ...unless the polarity and ground are properly connected as shown in Figure 25 and Figure 26 page 14 ForinstallationofA sizeCabinetfurnaces allowsufficient slack in the wiring if an optional cooling coi...

Страница 15: ...Specifications Thermostat Wire Gauge FURNACE MODEL NUMBER FURNACE INPUT BTUH CABINET WIDTH IN NOMINAL ELECTRICAL SUPPLY MINIMUM OPERATING VOLTAGE MAXIMUM OPERATING VOLTAGE MAXIMUM FURNACE AMPERES MAXI...

Страница 16: ...follow all safety warnings could result in serious injury death or property damage This furnace may be installed with left right or bottom gas entry Whenconnectingthegassupply provideclearance between...

Страница 17: ...60HZ 30 vac Normal Anticipator Setting 0 4 Manifold Pressure for Natural Gas 3 5 w c Manifold Pressure for LP Gas 10 w c AVERTISSEMENT RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissement...

Страница 18: ...e explosion carbon monoxide poisoning personal injury or death High altitude conversion with this furnace depends on the installation altitude and the heating value of the gas The installation of this...

Страница 19: ...Pressure To obtain an accurate pressure reading turn off all gas appliances i e Dryers water heaters stoves etc at their ON OFF control or individual gas valves 1 Remove the inlet pressure plug from t...

Страница 20: ...ace in service it must be checkedtoensureitisequippedforthetypeofgas being used The burner flame must be observed andadjustedifnecessary Failuretoobservethis cautionmayresultinunsafeoperation explosio...

Страница 21: ...supplier See page 19 Verifying Adjusting Temperature Rise Confirm the temperature rise through the furnace is within the limits specified on the furnace rating plate Any temperature rise outside the...

Страница 22: ...to the furnace before shutting off the electrical supply 7 When call for heat is satisfied the thermostat contacts open thegasvalveshutsoffgasflowandthecombustion blower remains on for a 30 45 second...

Страница 23: ...gnitortipforflamerectification Misalignedignitordoesnotallowflametocontactignitor tip for flame rectification Burner Short Cycling Thermostat Calls for Heat Limit Switches Closed Check for polarity Ch...

Страница 24: ...h Inspect the combustion chamber blower compartment flue collar and Roof Jack Check the gas valve if applicable and fuel line connections for leaks Make any adjustments necessary for good operation WA...

Страница 25: ...439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 16...

Страница 26: ...27 24 Service Orifice Size Table 13 High Altitude Deration Chart for Natural Gas Low Heating Value Table 11 Natural Gas Heating Values LOCAL HEATING VALUES FOR NATURAL GAS ALTITUDE ABOVE SEA LEVEL BTU...

Страница 27: ...115V N C L R GROUND SCREW GROUND SCREW GAS VALVE NEUTRAL L1 WIRE NUTS SUPPLIED BY INSTALLER 1 2 3 4 5 N L C G ECM BLOWER MOTOR G W Y R C CONTROL LIGHTS 1 2 1 2 BLACK BLACK 1 2 3 4 5 6 1 2 3 4 5 6 MOTO...

Страница 28: ...Gas valve De energized when it should be Energized Rapid Flash Reverse Polarity Continuous On Normal Operation Flash codes stored in memory auto erased after 14 days Flash codes NOT stored in memory...

Страница 29: ...79 53 2 Med Low 996 57 960 59 924 62 885 64 848 67 1 Low MG1E 090F1AAM1 MODEL NAME HEATING INPUT MOTOR SPEED EXTERNAL STATIC PRESSURE IN W C 0 1 0 2 0 3 0 4 0 5 CFM RISE CFM RISE CFM RISE CFM RISE CFM...

Страница 30: ...6 0 7 0 8 CFM CFM CFM CFM CFM CFM CFM CFM MG1E 077F1AAM1 77 000 BTU Hr 5 High 1 573 1 541 1 511 1 479 1 452 1 419 1 388 1 358 4 Alternate 1 333 1 300 1 268 1 236 1 201 1 162 1 129 1 093 3 Med High 1 2...

Страница 31: ...31...

Страница 32: ...Literature Package been left with the unit YES NO ATTENTION INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict...

Отзывы: