background image

19

Conversion to Propane (LP) Gas

 WARNING:

This furnace was shipped from the factory 

equipped to operate on natural gas. Conversion 

to LP/propane gas must be performed by qualified 

service personnel using factory supplied 

conversion parts. Failure to use the proper 

conversion kit can cause fire, explosion, property 

damage, carbon monoxide poisoning, personal 

injury, or death.

 WARNING:

Shut off the gas supply at the manual gas shutoff 

valve, before disconnecting the electrical power. 

A fire or explosion may result causing property 

damage, personal injury or loss of life. Failure to 

follow the safety warnings exactly could result in 

serious injury, death or property damage.

 WARNING:

To avoid electric shock, personal injury, or death, 

turn off the electric power at the disconnect or the 

main service panel before making any electrical 

connections.

This furnace can be converted from factory-equipped 

natural gas to liquid propane gas. Conversion of this valve 

requires replacement of the burner orifice and flipping the 

regulator cap to the side marked LP. The orifice required 

for conversion is supplied with the furnace. See 

Figure 27

.

For altitudes between 0 and 1,999 feet, use the factory 

supplied LP orifice as shown in 

Table 6, (page 17)

.

Altitudes between 2,000 and 10,000 feet require the orifice 

to be changed. 

Table 14, (page 29)

 lists the correct orifice 

size and manifold pressure at different altitudes.

Atmospheric & Direct Ignition Furnaces

1. Follow the instructions in “How to Shut Off Gas - Direct 

Ignition” on 

page 21

.

2. Disconnect the gas pipe union and the electrical wires 

connected to the gas valve.

3. Remove the gas valve assembly:

4. Remove screw(s) from gas valve bracket. Gas valve and 

spud may be removed. Orifice is located at the end of 

the spud.

5. Replace the main orifice with the L.P. gas orifice supplied 

in the envelope located by the gas valve. Verify the 

orifice size matches the nameplate or 

Table 6, (page 

17)

.

6. Unscrew the pressure regulator cap and check for the 

letters NAT or LP. See 

Figure 27 (page 17)

.

7. Invert the cap and tighten until snug.

8. Reassemble the burner assembly into the furnace.

9. Reconnect the gas piping and electrical wires to the 

gas valve.

10. Open the manual shut-off valve and follow the Operating 

Instructions on 

page 20.

Measuring the Supply Gas Pressure

To obtain an accurate pressure reading, turn off all 

gas appliances (i.e. Dryers, water heaters, stoves, 

etc.) at their ON/OFF control or individual gas valves.

1. Remove the inlet pressure plug from the INLET side 

of the gas valve with a 3/16 Allen wrench. See 

Figure 

27

.

2. Install a 1/8 NPT fitting, which is compatible with a 

manometer or similar pressure gauge.

3. Connect the manometer or pressure gauge to the inlet 

pressure tap.

4. Turn on all electrical power to the furnace.

5. Turn the main gas supply valve (on the outside of the 

unit) to the ON position.

6. Start the furnace by adjusting the thermostat to it’s 

highest setting. Allow the furnace to run for 10 minutes.

7. Check the incoming gas line pressure. Propane gas 

furnaces must be between 11.0”-14.0” W.C. Natural 

gas installations must be between 4.5”-10.0” W.C. If 

the pressure is not between these specified ranges, 

contact your local gas supplier for adjustment.

8. Adjust the thermostat to it’s lowest setting and allow 

the unit to cycle off.

9. Turn the main gas supply valve (on the outside of the 

unit) to the OFF position.

10. Turn off all electrical power to the furnace.

11. Disconnect the manometer or pressure gauge.

12. Remove the NPT fitting and reinstall the inlet pressure 

plug.

 

NOTE: 

To prevent cross threading, hand tighten 

the plug first, then tighten with 3/16 Allen wrench.

Measuring the Manifold Pressure

The manifold pressure must be measured by installing a 

pressure gauge (Manometer, Magnehelic Meter, etc.) to 

the outlet end of the gas valve.
1. Remove the manifold pressure plug from the outlet side 

of the gas valve with a 3/16 Allen wrench.See 

Figure 

27 (page 17)

.

2. Install a 1/8 NPT fitting, which is compatible with a 

Manometer or similar pressure gauge.

3. Connect the manometer or pressure gauge to the pipe 

thread fitting.

4. Start the furnace by adjusting the thermostat 5 degrees 

above room temperature. Allow the furnace to operate 

for 3 minutes.

5. Measure the manifold pressure on the manometer or 

pressure gauge. Compare the measured value to the 

value in 

Table 12, (page 26)

Table 13, (page 26)

or 

Table 14, (page 29)

.

6. Replace the cap so that the letters facing up represent 

the type of gas being used for the furnace. See 

Figure 

27 (page 17)

.

7. Adjust the thermostat to its lowest setting.

8. Turn off the main gas supply to the unit at the manual 

shut-off valve, which is located outside of the unit.

9. Turn off all of the electrical power to the furnace.

Содержание MG1 Series

Страница 1: ...ier call the fire department QUE FAIRE S IL Y A UNE ODEUR DE GAZ N essayez d allumer aucun appareil Ne touchez aucun interrupteur lectrique n utilisez aucun t l phone dans le b timent vacuez l immeubl...

Страница 2: ...nversion to Propane LP Gas 19 Atmospheric Direct Ignition Furnaces 19 Measuring the Supply Gas Pressure 19 Measuring the Manifold Pressure 19 STARTUP ADJUSTMENTS 20 Operating Instructions Direct Ignit...

Страница 3: ...pendant l installation l entretien et le fonctionnement de cette fournaise Le non respect des recommandations de s curit peut causer des dommages l quipement ou des blessures graves voire mortelles A...

Страница 4: ...ANSI NFPA 70 CANADA Canadian Electrical Code CSA C22 1 Gas Piping Gas Pipe Pressure Testing US NFGC and National Plumbing Codes CANADA NSCNGPIC General Installation US Current edition of the NFGC and...

Страница 5: ...sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide min 250 sq in 1613 cm open free area in front or side...

Страница 6: ...e a louvered door with a minimum of 250 in2 free area with the openings in the closet door in line with the louvered openings in the furnace door A fully louvered closet door may be used See Circulati...

Страница 7: ...ode ANSI C1 NFPA 70 Gaspipingisnotruninorthroughthereturnductsystem CAUTION HAZARDOFASPHYXIATION Negativepressure inside the closet with closet door closed and the furnace blower operating on high spe...

Страница 8: ...1 7 8 2 7 8 C L Figure 7 Cut Out Dimensions for Round Duct Connectors Bend tabs up 90 Mounting Plate Duct Connector Connector Tabs Supply Air Duct Hole for Gas Line Wood Floor Figure 8 Standard Duct...

Страница 9: ...to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 8 For round ducts see Figure 7 page 8 1 Measure 10 from the rear wall or alcove and mark the centerline...

Страница 10: ...ector and the mounting plate to the wood floor with appropriate size screws 5 Connect the round supply duct to the underside of the duct connector and secure them with field supplied sheet metal screw...

Страница 11: ...ING F S AW1523 0 2 4 A S 15 23 F S AW2135 0 2 4 A S 21 35 F S AW2747 0 2 4 A S 27 47 F S AW3563 0 2 4 A S 35 63 F S AW5195 0 2 4 A S 51 95 NOTE Not all models are available Check with your local distr...

Страница 12: ...ough the opening cut on the roof 3 Connect inner flue pipe to vent collar of the furnace See Figure 22 4 Connectcombustionairpipetofurnacecollarwithsheet metal screw See Figure 22 NOTES Itisrecommende...

Страница 13: ...stallations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes It is recommended that 115VAC line voltage be supplied to the f...

Страница 14: ...unless the polarity and ground are properly connected as shown in Figure 25 and Figure 26 page 14 ForinstallationofA sizeCabinetfurnaces allowsufficient slack in the wiring if an optional cooling coi...

Страница 15: ...Specifications Thermostat Wire Gauge FURNACE MODEL NUMBER FURNACE INPUT BTUH CABINET WIDTH IN NOMINAL ELECTRICAL SUPPLY MINIMUM OPERATING VOLTAGE MAXIMUM OPERATING VOLTAGE MAXIMUM FURNACE AMPERES MAXI...

Страница 16: ...follow all safety warnings could result in serious injury death or property damage This furnace may be installed with left right or bottom gas entry Whenconnectingthegassupply provideclearance between...

Страница 17: ...60HZ 30 vac Normal Anticipator Setting 0 4 Manifold Pressure for Natural Gas 3 5 w c Manifold Pressure for LP Gas 10 w c AVERTISSEMENT RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissement...

Страница 18: ...e explosion carbon monoxide poisoning personal injury or death High altitude conversion with this furnace depends on the installation altitude and the heating value of the gas The installation of this...

Страница 19: ...Pressure To obtain an accurate pressure reading turn off all gas appliances i e Dryers water heaters stoves etc at their ON OFF control or individual gas valves 1 Remove the inlet pressure plug from t...

Страница 20: ...ace in service it must be checkedtoensureitisequippedforthetypeofgas being used The burner flame must be observed andadjustedifnecessary Failuretoobservethis cautionmayresultinunsafeoperation explosio...

Страница 21: ...supplier See page 19 Verifying Adjusting Temperature Rise Confirm the temperature rise through the furnace is within the limits specified on the furnace rating plate Any temperature rise outside the...

Страница 22: ...to the furnace before shutting off the electrical supply 7 When call for heat is satisfied the thermostat contacts open thegasvalveshutsoffgasflowandthecombustion blower remains on for a 30 45 second...

Страница 23: ...gnitortipforflamerectification Misalignedignitordoesnotallowflametocontactignitor tip for flame rectification Burner Short Cycling Thermostat Calls for Heat Limit Switches Closed Check for polarity Ch...

Страница 24: ...h Inspect the combustion chamber blower compartment flue collar and Roof Jack Check the gas valve if applicable and fuel line connections for leaks Make any adjustments necessary for good operation WA...

Страница 25: ...439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 16...

Страница 26: ...27 24 Service Orifice Size Table 13 High Altitude Deration Chart for Natural Gas Low Heating Value Table 11 Natural Gas Heating Values LOCAL HEATING VALUES FOR NATURAL GAS ALTITUDE ABOVE SEA LEVEL BTU...

Страница 27: ...115V N C L R GROUND SCREW GROUND SCREW GAS VALVE NEUTRAL L1 WIRE NUTS SUPPLIED BY INSTALLER 1 2 3 4 5 N L C G ECM BLOWER MOTOR G W Y R C CONTROL LIGHTS 1 2 1 2 BLACK BLACK 1 2 3 4 5 6 1 2 3 4 5 6 MOTO...

Страница 28: ...Gas valve De energized when it should be Energized Rapid Flash Reverse Polarity Continuous On Normal Operation Flash codes stored in memory auto erased after 14 days Flash codes NOT stored in memory...

Страница 29: ...79 53 2 Med Low 996 57 960 59 924 62 885 64 848 67 1 Low MG1E 090F1AAM1 MODEL NAME HEATING INPUT MOTOR SPEED EXTERNAL STATIC PRESSURE IN W C 0 1 0 2 0 3 0 4 0 5 CFM RISE CFM RISE CFM RISE CFM RISE CFM...

Страница 30: ...6 0 7 0 8 CFM CFM CFM CFM CFM CFM CFM CFM MG1E 077F1AAM1 77 000 BTU Hr 5 High 1 573 1 541 1 511 1 479 1 452 1 419 1 388 1 358 4 Alternate 1 333 1 300 1 268 1 236 1 201 1 162 1 129 1 093 3 Med High 1 2...

Страница 31: ...31...

Страница 32: ...Literature Package been left with the unit YES NO ATTENTION INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict...

Отзывы: