FUEL SUPPLY & PIPING

 WARNING:

FIRE OR EXPLOSION HAZARD

•  Failure to follow safety warnings exactly could 

result in serious injury, death or property 

damage.

• Installation and service must be performed 

by a qualified installer, service agency or the 

gas supplier.

• Do not store or use gasoline or other 

flammable vapors and liquids in the vicinity 

of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch; do not 

use any phone in your building.

• Leave the building immediately.

• Immediately call your gas supplier from a 

neighbor’s phone. Follow the gas supplier’s 

instructions.

• If you cannot reach your gas supplier, call 

the fire department.

 AVERTISSEMENT :

RISQUE D’INCENDIE OU D’EXPLOSION

•  Le non-respect des avertissements de sécurité pourrait 

entraîner des blessures graves ou des dommages 

matériels importants.

• L’installation et l’entretien doivent être effectués par 

un installateur qualifié, un organisme de service ou le 

fournisseur de gaz.

• N’entreposez pas ni n’utilisez de l’essence ni d’autres 

vapeurs ou liquides inflammables dans le voisinage de 

cet appareil, ni de tout autre appareil.

QUE FAIRE S’IL Y A UNE ODEUR DE GAZ

•  N’essayez d’allumer aucun appareil.

• Ne touchez à aucun interrupteur électrique; n’utilisez 

aucun téléphone dans le bâtiment.

•  Évacuez l’immeuble immédiatement.

•  Appelez immédiatement votre fournisseur de gaz à l’aide 

du téléphone d’un voisin. Respectez les instructions du 

fournisseur de gaz.

•  Si personne ne répond, appelez le service des incendies.

 WARNING:

All piping must conform with local building codes, 

or in the absence of local codes, with the most 

recent edition of the National Fuel Gas Code ANSI 

Z223.1 or (CAN/CSA B149.1). Failure to follow all 

safety warnings could result in serious injury, 

death or property damage.

This furnace may be installed with left, right, or bottom gas 

entry. When connecting the gas supply, provide clearance 

between the gas supply line and the entry hole in the 

furnace casing to avoid unwanted noise and/or damage 

to the furnace. Typical gas service hookup for this furnace 

is shown in 

Figure 27

.

Table 10, (page 25)

 lists gas flow capacities for standard 

pipe sizes as a function of length in typical applications 

based on nominal pressure drop in the line.

IMPORTANT NOTES:

•  Some local regulations require the installation of a 

manual main shut-off valve and ground joint union 

external to the furnace. See 

Figure 27

The shut-

off valve should be readily accessible for service 

and/or emergency use. Consult the local utility or 

gas supplier for additional requirements regarding 

placement of the manual main gas shut-off.

•  Per ANSI 21.47, A 1/8-inch NPT plugged tapping, 

accessible for test gauge connection, must be 

installed immediately upstream of the gas supply 

connection to the furnace external to the cabinet. 

If local codes allow the use of a flexible gas appliance 

connector, always use a new listed connector. Do 

not use a connector that has previously serviced 

another gas appliance.

•  Gas piping must never run in or through air ducts, 

chimneys, gas vents, or elevator shafts.

•  Compounds used on threaded joints of gas piping 

must be resistant to the actions of -liquefied 

petroleum gases.

Floor

Control

Panel

On-Off-Fan

Switch

Alt. Fuel

Line Entry

Floor Cavity

Some codes may require installation of a manual main shut-off

valve and ground joint union external to the furnace. The shut-off

valve should be readily accessible for service and/or emergency

use. Consult the local utility or gas supplier for additional

requirements regarding placement of the manual main gas shut-off.

To Gas Supply

Figure 27. Typical Gas Piping

Содержание MG1 Series

Страница 1: ...ier call the fire department QUE FAIRE S IL Y A UNE ODEUR DE GAZ N essayez d allumer aucun appareil Ne touchez aucun interrupteur lectrique n utilisez aucun t l phone dans le b timent vacuez l immeubl...

Страница 2: ...nversion to Propane LP Gas 19 Atmospheric Direct Ignition Furnaces 19 Measuring the Supply Gas Pressure 19 Measuring the Manifold Pressure 19 STARTUP ADJUSTMENTS 20 Operating Instructions Direct Ignit...

Страница 3: ...pendant l installation l entretien et le fonctionnement de cette fournaise Le non respect des recommandations de s curit peut causer des dommages l quipement ou des blessures graves voire mortelles A...

Страница 4: ...ANSI NFPA 70 CANADA Canadian Electrical Code CSA C22 1 Gas Piping Gas Pipe Pressure Testing US NFGC and National Plumbing Codes CANADA NSCNGPIC General Installation US Current edition of the NFGC and...

Страница 5: ...sq in 1516 cm open free area in front or side wall 2 or In closet door located at top center or bottom CLOSET DOOR 6 152 mm Top Clearance Provide min 250 sq in 1613 cm open free area in front or side...

Страница 6: ...e a louvered door with a minimum of 250 in2 free area with the openings in the closet door in line with the louvered openings in the furnace door A fully louvered closet door may be used See Circulati...

Страница 7: ...ode ANSI C1 NFPA 70 Gaspipingisnotruninorthroughthereturnductsystem CAUTION HAZARDOFASPHYXIATION Negativepressure inside the closet with closet door closed and the furnace blower operating on high spe...

Страница 8: ...1 7 8 2 7 8 C L Figure 7 Cut Out Dimensions for Round Duct Connectors Bend tabs up 90 Mounting Plate Duct Connector Connector Tabs Supply Air Duct Hole for Gas Line Wood Floor Figure 8 Standard Duct...

Страница 9: ...to avoid misalignment of the furnace and vent piping To locate standard ducts see Figure 6 page 8 For round ducts see Figure 7 page 8 1 Measure 10 from the rear wall or alcove and mark the centerline...

Страница 10: ...ector and the mounting plate to the wood floor with appropriate size screws 5 Connect the round supply duct to the underside of the duct connector and secure them with field supplied sheet metal screw...

Страница 11: ...ING F S AW1523 0 2 4 A S 15 23 F S AW2135 0 2 4 A S 21 35 F S AW2747 0 2 4 A S 27 47 F S AW3563 0 2 4 A S 35 63 F S AW5195 0 2 4 A S 51 95 NOTE Not all models are available Check with your local distr...

Страница 12: ...ough the opening cut on the roof 3 Connect inner flue pipe to vent collar of the furnace See Figure 22 4 Connectcombustionairpipetofurnacecollarwithsheet metal screw See Figure 22 NOTES Itisrecommende...

Страница 13: ...stallations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes It is recommended that 115VAC line voltage be supplied to the f...

Страница 14: ...unless the polarity and ground are properly connected as shown in Figure 25 and Figure 26 page 14 ForinstallationofA sizeCabinetfurnaces allowsufficient slack in the wiring if an optional cooling coi...

Страница 15: ...Specifications Thermostat Wire Gauge FURNACE MODEL NUMBER FURNACE INPUT BTUH CABINET WIDTH IN NOMINAL ELECTRICAL SUPPLY MINIMUM OPERATING VOLTAGE MAXIMUM OPERATING VOLTAGE MAXIMUM FURNACE AMPERES MAXI...

Страница 16: ...follow all safety warnings could result in serious injury death or property damage This furnace may be installed with left right or bottom gas entry Whenconnectingthegassupply provideclearance between...

Страница 17: ...60HZ 30 vac Normal Anticipator Setting 0 4 Manifold Pressure for Natural Gas 3 5 w c Manifold Pressure for LP Gas 10 w c AVERTISSEMENT RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissement...

Страница 18: ...e explosion carbon monoxide poisoning personal injury or death High altitude conversion with this furnace depends on the installation altitude and the heating value of the gas The installation of this...

Страница 19: ...Pressure To obtain an accurate pressure reading turn off all gas appliances i e Dryers water heaters stoves etc at their ON OFF control or individual gas valves 1 Remove the inlet pressure plug from t...

Страница 20: ...ace in service it must be checkedtoensureitisequippedforthetypeofgas being used The burner flame must be observed andadjustedifnecessary Failuretoobservethis cautionmayresultinunsafeoperation explosio...

Страница 21: ...supplier See page 19 Verifying Adjusting Temperature Rise Confirm the temperature rise through the furnace is within the limits specified on the furnace rating plate Any temperature rise outside the...

Страница 22: ...to the furnace before shutting off the electrical supply 7 When call for heat is satisfied the thermostat contacts open thegasvalveshutsoffgasflowandthecombustion blower remains on for a 30 45 second...

Страница 23: ...gnitortipforflamerectification Misalignedignitordoesnotallowflametocontactignitor tip for flame rectification Burner Short Cycling Thermostat Calls for Heat Limit Switches Closed Check for polarity Ch...

Страница 24: ...h Inspect the combustion chamber blower compartment flue collar and Roof Jack Check the gas valve if applicable and fuel line connections for leaks Make any adjustments necessary for good operation WA...

Страница 25: ...439 84 43 214 429 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 16...

Страница 26: ...27 24 Service Orifice Size Table 13 High Altitude Deration Chart for Natural Gas Low Heating Value Table 11 Natural Gas Heating Values LOCAL HEATING VALUES FOR NATURAL GAS ALTITUDE ABOVE SEA LEVEL BTU...

Страница 27: ...115V N C L R GROUND SCREW GROUND SCREW GAS VALVE NEUTRAL L1 WIRE NUTS SUPPLIED BY INSTALLER 1 2 3 4 5 N L C G ECM BLOWER MOTOR G W Y R C CONTROL LIGHTS 1 2 1 2 BLACK BLACK 1 2 3 4 5 6 1 2 3 4 5 6 MOTO...

Страница 28: ...Gas valve De energized when it should be Energized Rapid Flash Reverse Polarity Continuous On Normal Operation Flash codes stored in memory auto erased after 14 days Flash codes NOT stored in memory...

Страница 29: ...79 53 2 Med Low 996 57 960 59 924 62 885 64 848 67 1 Low MG1E 090F1AAM1 MODEL NAME HEATING INPUT MOTOR SPEED EXTERNAL STATIC PRESSURE IN W C 0 1 0 2 0 3 0 4 0 5 CFM RISE CFM RISE CFM RISE CFM RISE CFM...

Страница 30: ...6 0 7 0 8 CFM CFM CFM CFM CFM CFM CFM CFM MG1E 077F1AAM1 77 000 BTU Hr 5 High 1 573 1 541 1 511 1 479 1 452 1 419 1 388 1 358 4 Alternate 1 333 1 300 1 268 1 236 1 201 1 162 1 129 1 093 3 Med High 1 2...

Страница 31: ...31...

Страница 32: ...Literature Package been left with the unit YES NO ATTENTION INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict...

Отзывы: