28
Table 12. Air Flow Settings for Heating
AIRFLOW INFORMATION
Table 11. Air Flow Settings for Cooling
NOTE:
0 = OFF; 1 = ON
*Factory settings are in bold.
3 TON UNITS
4 - 5 TON UNITS
SWITCH NUMBER
RECOMMENDED
A/C AIRFLOW
RATE (CFM)
SWITCH NUMBER
RECOMMENDED
A/C AIRFLOW
RATE (CFM)
1
2
3
4
1
2
3
4
0
0
0
1
720
0
0
0
1
4
T
O
N
1440
0
0
0
0
800
1
0
0
1
1575
1
0
0
1
855
0
0
0
0
1600
0
0
1
0
880
0
1
0
1
1620
1
0
0
0
950
1
0
0
0
5
T
O
N
1750
0
1
0
1
990
1
1
0
1
1755
1
0
1
0
3
T
O
N
1045
0
0
1
0
1760
0
1
0
0
1100
0
1
0
0
1800
1
1
0
1
1170
1
0
1
0
1925
0
1
1
0
1210
1
1
0
0
1950
1
1
0
0
1300
0
1
1
0
1980
1
1
1
0
1430
1
1
1
0
2145
2 TON UNITS
SWITCH NUMBER
RECOMMENDED
A/C AIRFLOW
RATE (CFM)
1
2
3
4
0
0
0
1
630
0
0
0
0
2
T
O
N
700
0
0
1
0
770
1
0
0
1
783
1
0
0
0
870
0
1
0
1
918
1
0
1
0
957
0
1
0
0
1020
1
1
0
1
1053
0
1
1
0
1122
1
1
0
0
1170
1
1
1
0
1287
Switches
2 Ton
3 Ton
4 & 5 Ton
Low Fire Input
High Fire Input
Low Fire Input
High Fire Input
Low Fire Input
High Fire Input
5
6
7
46,800
72,000
65,000
100,000
78,000
120,000
0
0
#
550
63
732
73
700
59
1170
63
750
77
1255
71
1
0
#
650
53
865
62
800
60
1240
60
900
64
1395
64
0
1
#
750
46
998
53
1000
48
1640
45
1050
55
1720
52
1
1
#
900
39
1062
50
1200
40
2005
37
1200
48
2005
44
NOTES:
0 = OFF
1 = ON
# Switch is not used - Can be 0 or 1
1. Recommended temperature rises are highlighted in
bold
. Use of any other setting may result in nuisance trips.
2. Temperature rises in the table are approximate. Actual temperature rises may vary.
Table 10. Nominal Airflow Rates & Temperature Rises (
°
F)
Model Number
DF6SF-
Heating Input
(Btuh)
Heating Output
(Btuh)
Heat Switch
Setting
CFM
Heating Rise
Range (° F)
Cooling Output
(Btuh)
Blower
Size
Motor
(HP)
X24K072C
72,000
57,600
1,1
0,1
1,062
998
35-65
24,000
10 X 10
1/2
46,800
37,440
1,1
0,1
900
750
X36K100C
100,000
80,000
0,1
1,1
1,640
2,005
40-70
35,000
10 X 10
1/2
65,000
52,000
0,1
1,1
1,000
1,200
X48K120C
120,000
96,000
1,1
0,1
2,005
1,720
40-70
46,000
11 X 10
1
78,000
62,400
1,1
0,1
1,200
1,050
X60K120C
120,000
96,000
1,1
0,1
2,005
1,720
40-70
55,500
11 X 10
1
78,000
62,400
1,1
0,1
1,200
1,050
NOTE:
CFM and Rise are independent of ESP in a variable speed blower.