background image

3

GENERAL INFORMATION

C84DA series coils are designed for upflow or  downflow 

applications and are equipped with down turned refrigerant 

connections and are ready for brazing.
•  Check the coils orifice size and confirm that it’s suitable 

for application with the intended outdoor unit. Depending 

on application, additional installer supplied orifice or 

TXV may be required.

• Optional cooling/heating equipment must be 

properly sized and installed in accordance with the 

furnace manufacturer’s specifications and approved 

recommendations.

•  Heating only furnace air circulators may have to be 

replaced with multi-speed Heating/Cooling blowers to 

upgrade the air delivery (CFM) when an add-on coil is 

installed. Refer to Table 1 (page 6) for coil specifications, 

recommended CFM, and allowances for pressure drop 

across the coil and filters.

•  Verify that the air delivery of the furnace/air handler is 

adequate to handle the static pressure drop of the coil, 

filter, and duct work.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 

contact of the refrigerant lines with metal surfaces.

• Refrigerant lines should be wrapped with pressure 

sensitive neoprene or other suitable material where 

they pass against sharply edged sheet metal.

•  The coil enclosure (if provided) and suction line must 

be insulated as needed to prevent condensate from 

forming and causing property damage.

• Do not remove seals from the coil until the tubing 

connections are ready to be made.

• Close-off plates are available in some air filter kits. 

Refer to the Replacement Parts List for available part 

numbers. Install the necessary close-off plates around 

the refrigerant lines and drain line where required.  

Reinstall all inner and outer panels of the furnace/air 

handler that were previously removed when installing 

the indoor coil.

COIL INSTALLATION

 WARNING:

ELECTRICAL SHOCK, FIRE OR EXPLOSION 
HAZARD

Failure to follow safety warnings exactly could 

result in serious injury or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.
•  Before servicing, disconnect all electrical power 

to the furnace and outdoor condensing unit.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

 CAUTION:

The coil must be level to ensure proper 
condensate drainage. An unlevel installation 
may result in structural damage, premature 
equipment failure, or possible personal injury.

Upflow Installations

1. Disconnect all electrical power to the furnace.
2. Install the coil case on the furnace air discharge opening 

and level it as needed to ensure proper condensate 

drainage. If needed, make a plate to adapt the coil to 

the air discharge opening. See Figure 2 (page 6) for 

coil dimensions.

3. Make and install the plenum over the coil. Insulate as 

required.

4. Seal the enclosure as required to minimize air leakage.
5. Connect the refrigerant lines as outlined in the 

Refrigerant Line Connection section.

Downflow Installations

These coils may be installed in downflow applications. It 

is required that the furnace and coil cabinets are securely 

mounted together before setting in place. Fossil fuel 

applications require the coil to be placed in the supply 

air stream only.

Refrigerant Line Connections

System Depressurization

1. Remove the cap (Figure 1) from the end of the liquid line.
2. Verify pressurization by depressing the Schrader valve 

on the end of the liquid line. Listen for any escaping gas. 

If there is no pressure, test the coil for leakage.

•  If leakage is found, clearly mark the location of the leak 

and return the coil to the distributor for processing.

•  If no leaks are found, the coil may be installed.
3. Depress the valve to relieve all pressure from the coil.

Suction 

Line

Liquid 

Line

Cap

Schrader 

Valve

Figure 1. Suction & Liquid Line Locations

Содержание C84DA Series

Страница 1: ...ciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper in...

Страница 2: ...of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment If you do not posses mechanical skills or tools call your local dealer forassistance...

Страница 3: ...l COIL INSTALLATION WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Improper servicing could result in dan...

Страница 4: ...ate Drain CAUTION The coil must be level to ensure proper condensate drainage Improper condensate disposal may result in structural damage premature equipment failure or possible personal injury Metho...

Страница 5: ...equipmentfailure thefollowingmaintenancetasksshould be performed periodically on this equipment 1 Theairfilterinstalledwiththesystemshouldbechecked and cleaned or replaced twice per year 2 Check the c...

Страница 6: ...18 18 18 25 25 29 D Depth in 19 1 2 19 1 2 19 1 2 19 1 2 19 1 2 19 1 2 19 1 2 Connection Liquid Line in 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Connection Suction Line in 3 4 3 4 3 4 7 8 7 8 7 8 7 8 NOTES 1 Indiv...

Страница 7: ...7...

Страница 8: ...VE THESE INSTRUCTIONS WITH THE EQUIPMENT OWNER 1040996A Replaces 1040996 0 Specifications illustrationssubjecttochangewithoutnoticeorincurringobligations 04 22 O Fallon MO Nortek Global HVAC LLC 2022...

Отзывы: