6. Servicing. 

These appliances should be serviced annually by a competent person to ensure safe and 
efficient  operation.  In  exceptionally  dusty  or  polluted  conditions  more  frequent             

servicing may be required. The manufacturer offers a maintenance service. Details  available 
on request. 

Isolate electricity supplies before commencing any work.

 

Cross point 
screwdriver 

6.1 Tools required. 

The  following  tools  and  equipment  are        
recommended to complete the tasks laid out in 
this  manual.  

 

 
Suitable alternative tools may be used.

 

 

Small flat head 
screwdriver 

Allen key set 

Adjustable 
 spanner 

10mm spanner 

13mm spanner 

Soft 
brush 

 
 
 

 

 

 

 
 

6.2 Air outlet louvres. 

The air outlet louvres should be cleaned with a 
soft brush. Check that the louvres are set to the 
required angle. (See Figs. A/B on page 5 for 
setting procedure). 
 

6.3 Air distribution fans. 

The air distribution fans can be accessed by 
opening the fan access lid as described in    
section 7.1 Fig.2. 
 
Clean off any dust or deposits with a soft brush 
paying particular attention to the impeller. Check 
that the impeller spins freely, and that there is 
no play in the fan bearings. 
The fan(s) can be removed, if necessary, as   
described in section 7.1. 
 

6.4 Elements 

Remove element housing as described in 

 

 

 

 

section 7 (parts replacement). Clean off any 
dust or deposits with a soft brush. 
 
Visually inspect element coils for signs of 

 

 

 

 

 

discolouration, burning, sagging etc. 

 

6.5 Electrical. 

Isolate 

electricity 

supplies 

before      

commencing any work. 

 

Check condition and tightness of all terminations 
in control panel. 
 
Remove the fan/elements terminal box cover 
located on top of the air curtain (Fig.1), and   
repeat above procedure for the fan/elements 
terminations. 
 
Check that the plug/socket connection to each 
fan (inside the unit) is tight and that the cable is 
in good condition. Switch control panel on and 
check air curtain operation in each selector 
switch position (heat on/off, low//high speed). 

Fig.1 

Содержание AB 175E

Страница 1: ...Replacement 7 Spare Parts 8 Fault Finding 9 User Instructions 10 WARNINGS 1 This appliance must only be installed by a competent person in accordance with the requirements of the Codes of Practice or...

Страница 2: ...g an air curtain is to prevent the influx of cold outside air through a door opening into a heated area Typical applications include large despatch bay doors in factories and warehouses and internal d...

Страница 3: ...Doc No 702105 Page 3 of 16 2 Dimensions Diagram 1 Dimensions FRONT VIEW PLAN VIEW R H VIEW...

Страница 4: ...ans 3 4 Maximum air volume 9600m3 hr 12800m3 hr Voltage 230V 1PH 50Hz Power rating per fan 1140 W Current per fan 5 2A FLC Start current per fan 12A Power Elements 18kW 24kW Total power consumption 21...

Страница 5: ...e air curtains should be bolted together using 3 off M10 set pins nuts and washers fitted through the holes provided in the mounting brackets then suitable support channels not supplied must be fixed...

Страница 6: ...R CURTAIN Diagram 4 Support channel multiple air curtains Typical support channels Air curtain 1 Air curtain 2 PLAN VIEW TWIN AIR CURTAINS Factory fitted brackets Support points 4 Installation Details...

Страница 7: ...ector switch a high low fan speed selector switch and a heat on off selector switch Panel operation is described in section 10 of this manual user instructions A customer specific control panel wiring...

Страница 8: ...ution fans can be accessed by opening the fan access lid as described in section 7 1 Fig 2 Clean off any dust or deposits with a soft brush paying particular attention to the impeller Check that the i...

Страница 9: ...the retaining screws securing the hinged lid on the underside of the air curtain next to the louvres Fig 3 7 Parts Replacement Fig 5 Fan closure plate Fan outlet Fig 3 Fig 4 Fig 6 Fan closure plate F...

Страница 10: ...equiring removal and disconnect it from its cable mount ed plug socket See Fig 7 The four bolts securing the fan can now be removed as shown in Fig 8 and the fan removed from the air curtain downwards...

Страница 11: ...ightly and lifted from the 3 retaining tab slots D See diagram 8 7 2 5 The wiring to the element assembly can now be accessed at the rear of panel E and disconnected after first noting the cable posit...

Страница 12: ...date the warranty of the appliance AB 225E 24kW elements full set 100528 AB 175E 18kW elements full set 100527 Thermal cutout 1 per module 900001 8 Spare Parts Item Description Part No 3 speed air dis...

Страница 13: ...ntactor and associated wiring All air distribution fans off YES If the fan s still fail to operate normally please contact the Nortek service department YES Check 1 Power supply YES NO Air distributio...

Страница 14: ...vice department YES Check 1 Power supply YES NO Elements NO Low heat Check 1 Check current load on all elements Should be balanced If not could be element s open circuit If it is determined that the o...

Страница 15: ...Doc No 702105 Page 15 of 16 Notes...

Страница 16: ...h to the desired position 10 3 2 Switch on electrical supply to the control panel The panel live lamp will illuminate and the unit will now only operate when the BMS relay or remote switch is closed 1...

Отзывы: