304UM0001 Rev 00
PD160 Enhanced Series User Manual
Page: 31 of 39
8.
CUSTOMER FAULT ANALYSIS
8.1 Fault Finding
FAULT
CAUSED BY
REMEDY
Red LED does not glow on
power up.
If the indicator is off then there
is a fault on the power
connection to the unit.
Check power feed to the unit.
After the initial tune period the
CH1 Green Channel LED
remains flashing at 2Hz.
Unit cannot tune to the loop
due to faulty loop or feeder
connection.
Loop may be too small or too
large.
Faulty detector unit.
Check on-board diagnostics to
confirm fault. Check loop
installation and connections.
Check on-board diagnostics to
confirm fault. Recut as per
installation instructions.
Replace unit.
After tuning, the loop output
LED flashes intermittently and
the relay chatters.
The loop is getting spurious
detects due to:
a) Crosstalk with adjacent
detector.
b) Faulty loop or feeder
connection.
a) Change frequency
setting.
b) Check that the feeders are
correctly connected and
adequately twisted.