Nortech PD160 Enhanced Series Скачать руководство пользователя страница 10

 

304UM0001 Rev 00 

PD160 Enhanced Series User Manual 

Page: 10 of 39 

 

 

3.2.1  Idle Display 

 

The  idle  display  is  the  normal  display  shown  when  not  in  the  menu 
system.  It  displays  the  model  of  the  unit.  Any  button  pressed  will 
enter the menu system. The up (

) and down (

) arrows are used to 

navigate  the  system,  while  the  enter  button  is  used  to  select  items, 
e.g.  changing  settings,  going  deeper  into  the  menu,  or  going  back. 
Under  normal  operating  conditions,  if  a  button  is  inadvertently 
pressed, or during the use of the menu system, the menu will go back 
one display every 25 seconds. This is not the case in the diagnostics 
thus keeping certain desired information on display. 

 
The  menu  system  does  NOT  interfere  with  the  operation  of  the  unit;  it  merely  provides  the  ability  to 
change settings and to view diagnostics. The unit is fully operational while menu settings are changed 
and most settings have immediate effect. 
 

3.2.2  Frequency 

 

The frequency settings menu is the first menu and is used to shift the 
operating  frequency  of  the  detector.  This  is  primarily  used  to  handle 
situations  in  which  more  than  one  detector  is  used  at  the  same site. 
The  detectors  must  be  set-up  to  ensure  no  crosstalk  (interference) 
occurs between adjacent loops connected to different detectors. This 
is  achieved  by  ensuring  that  the  loops  of  the  two  detectors  are 
spaced  sufficiently  apart  (approximately  2  metres  between  adjacent 
edges)  and  also  ensuring  that  the  detectors  are  set  to  different 
frequencies.  
 

The loops connected to multichannel detectors are not susceptible to crosstalk due to the design of the 
loop interface. For more information about crosstalk refer to section 5.2.2. 
 
The  frequency  setting  allows  the  operating  frequency  of  the  loop  to  be  shifted  higher  or  lower 
depending  on  the  selection.  However,  the  operating  frequency  of  the  detector  channel  is  determined 
by a combination of: 

 

 

Inductance of the loop and feeder cable 
Detector frequency settings 

 

The operating frequency of the detector channel increases as the loop inductance decreases and vice 
versa. The inductance of the loop and feeder cable is determined by:  

 
Size of the loop 
Number of turns in the loop 
Length of feeder cable 

 

As a general rule, the detector connected to the inductive loop with the greatest inductance should be 
set to operate at the lowest frequency.  
 
If  the  frequency  reading  from  the  on-board  diagnostics  is  close  to  the  maximum  frequency,  the 
inductance of the loop is too low and more turns need to be added to the loop. However if the reading 
is  close  to  the  minimum  frequency,  the  inductance  of  the  loop  is  too  high  and  you  need  to  remove 
turns from the loop. 
 
If the detector is operating close to either limit, it is possible that either the frequency drift caused by 
environmental  changes  or  the  shift  in  frequency  caused  by  a  large  %

L/L  detect  will  cause  the 

frequency to go outside the limits and cause a retune. 

Содержание PD160 Enhanced Series

Страница 1: ...ww nortech co za PD160 Enhanced Series Inductive Loop Vehicle Detector USER MANUAL NORTECH INTERNATIONAL PTY LTD All rights reserved Copyright 2011 Document Number 304UM0001_00 Date of Issue October 2...

Страница 2: ...3 2 5 3 Output polarity 15 3 2 6 Diagnostics 15 3 2 7 Reset 17 3 2 7 1 Power fail 18 3 3 Front Panel Indicator 19 4 PRINCIPAL OF OPERATION 20 4 1 Detector Tuning 20 4 2 Detector Sensitivity 20 4 3 Ty...

Страница 3: ...r On Board Diagnostics 32 8 3 Functional Test 32 APPENDIX A FCC ADVISORY STATEMENT 33 APPENDIX B INSTALLATION OUTDOORS 34 Appendix B 1 IEC 60950 22 2005 Outdoor cabinet 34 Appendix B 2 IEC 60950 22 20...

Страница 4: ...ugh the barrier area during installation and testing that may result in unexpected operation of the barrier WARNING 6 USA FCC Advisory Statement Refer to Appendix A at the end of this document WARNING...

Страница 5: ...l as customisable outputs the product is easily configurable to suit most applications With the introduction of the easy to operate LCD menu system settings can be changed for frequency sensitivity pr...

Страница 6: ...ult set to 150ms Filter Delay Eight step selectable output filter Ranging from 100ms to 10seconds Default is OFF Presence Method Permanent or Limited to approximately 1 hour for a 1 L L Presence Time...

Страница 7: ...rated 1 A 230 VAC Optional Opto Isolated 50mA 30VDC For ambient temperatures above 60 C De rate the rel ay maximum current as per graph below 2 3 Environmental Data Storage Temperature 40 C to 80 C Op...

Страница 8: ...nd Mounting Position Shelf or DIN rail mounting Connections 11 pin Submagnal JEDEC No B11 88 Size of Housing 78mm High X 41mm Wide X 80mm Deep 2 5 Approvals CE Regulations EN 301 489 3 Equipment Type...

Страница 9: ...helf or DIN rail mounted with the controls and visual indicators at the front and wiring at the rear of the enclosure The power loop and relay outputs are all connected to the single 11 pin plug which...

Страница 10: ...ciently apart approximately 2 metres between adjacent edges and also ensuring that the detectors are set to different frequencies The loops connected to multichannel detectors are not susceptible to c...

Страница 11: ...detector only evaluates the user selected frequency Due to the increased processing required AFS takes longer to tune than when it is deactivated When AFS is activated under the normal or idle displa...

Страница 12: ...th fifteen available settings Defined as the percentage change in inductance the sensitivity selections range from 0 01 which is the highest sensitivity to 5 0 as the lowest sensitivity Setting 0 01 H...

Страница 13: ...to 60 minutes If limited presence is selected and a time out is defined the first time to expire will release the detect effectively tuning out the vehicle s presence In this way subsequent vehicles...

Страница 14: ...d or limited to a shorter period of time than the time the vehicle remains over the loop Longer pulses may be used where the output required is longer than the time the vehicle remains over the loop 3...

Страница 15: ...ion such as the min and max values and the number of vehicles counted are provided The following parameters may be verified using the diagnostics Loop status Display the actual loop operating frequenc...

Страница 16: ...put events depending on your output settings For example fault outputs would yield a different total output count from the number of vehicles detected Where the current value is shown as opposed to ma...

Страница 17: ...ts and the recovered from fault state This can also be achieved by power cycling the unit The detector automatically tunes to the inductive loop connected to it when the power is applied whether on in...

Страница 18: ...ondition The memory retention of the vehicle is designed to be infinite but is subject to the following limitations The level of the detect must be sufficiently greater at least 0 5 than the sensitivi...

Страница 19: ...ning condition the Channel LED displays the same in tuning as it does in fault Once the channel is tuned the Green Channel LED will go off As indicated above if the unit has recovered from a fault the...

Страница 20: ...ny of the following events occur When power is applied to the detector A channel reset is initiated via the menu system A detect of greater than 16 L L occurs A fault has occurred and is self healing...

Страница 21: ...e either a presence or pulse output Refer to section 3 2 5 for more information on how to set the outputs 4 3 1 Presence Output When a relay is configured as a presence output it will produce a contin...

Страница 22: ...is a fail secure output 4 4 Response Times The response time of the detector is the time taken from when a vehicle moves over the loop to when the detector gives an output The response times of the PD...

Страница 23: ...Circuit Breaker for AC models and a fuse for DC models v WARNING This product must be installed in an enclosure as the IP rating of the detector is IP 30 vi WARNING No user serviceable parts inside N...

Страница 24: ...ng the inductance and therefore the sensitivity of the loop detection system Hence where reinforcing exists 2 turns should be added to the normal loop as referred to in section 5 4 The ideal minimum s...

Страница 25: ...des at right angles to the direction of traffic movement These sides should ideally be 1 metre apart Loops operating from the same detector module can share a common slot along one of the longer sides...

Страница 26: ...o the loop slot Once the required number of turns of wire are wound into the slot around the loop circumference the wire is routed again via the feeder slot to the roadway edge A similar length is all...

Страница 27: ...304UM0001 Rev 00 PD160 Enhanced Series User Manual Page 27 of 39 4 mm 30 50 mm Figure 5 2 Slot Details...

Страница 28: ...ss than 60 V dc or less than 42 V ac If the relays are to switch higher voltages use CE LVD approved 11 pin sockets NOTE 2 All relay contact descriptions refer to the tuned and undetected state 6 1 PD...

Страница 29: ...ink 10 Relay 1N C White 11 Relay 2N C 6 3 PD164 Enhanced Series Detector English 11 pin connector wiring for PD164 DETECTOR Order number 304FT1004 301FT0041 Wiring Harness Wire COLOUR 11 PIN Connector...

Страница 30: ...s To arm card readers and ticket dispensers As a barrier gate door closing detector As a barrier gate door opening detector Free exit To generate pulses for vehicle counting Some of the features that...

Страница 31: ...the loop due to faulty loop or feeder connection Loop may be too small or too large Faulty detector unit Check on board diagnostics to confirm fault Check loop installation and connections Check on bo...

Страница 32: ...g a small metal object approximately the size of a matchbox close to the loop coil The following will happen on detection The OUTPUT LED will light up Output relays set to PRESENCE will operate Output...

Страница 33: ...this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by...

Страница 34: ...ution degree 2 Appendix B 2 IEC 60950 22 2005 Northern Europe To achieve outdoor operation down to 50 C as requ ired by IEC 60950 22 2005 for Northern Europe Finland Norway and Sweden a heater with a...

Страница 35: ..._________ FAX No ____________________________ Postal address ____________________________________ _____________________________________ _____________________________________ Product Model i e PD164 __...

Страница 36: ...POWER SUPPLY DETAILS Nominal Voltage _______ V Minimum Voltage _______ V Maximum Voltage ________ V AC or DC ______________ If AC then the Frequency _______ Hz LOOP DETAILS Size of loop ____ m by ____...

Страница 37: ...__________________ Thickness of insulation _____________ mm Type of feeder cable used screened armoured multicore etc _________________________________________________________________________________...

Страница 38: ...feeder cable __________ V AC voltage between one of the feeder cable wires and earth __________ V DC resistance of Feeder plus Loop _______ ohms Inductance of Feeder plus Loop ________ H Frequency of...

Страница 39: ...Indeterminate Inductance Change for each vehicle type Use the maximum sensitivity reading and reset the statistics between each reading Vehicle Type Inductance Change Bicycle L L Motorbike L L Car L L...

Отзывы: