![Noritz NH150-DV Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/noritz/nh150-dv/nh150-dv_installation-and-instruction-manual_1705062024.webp)
24
B
Priority 1
(Indirect Tank)
Priority 1 (Indirect Tank)
Priority 2
(Heating)
Burner
Power
Power supply for circulator
AC120Volts Max. 2.2Amp.
Circulation terminal
For External Lamp
No Power supply (Only Contact)
Hot Neutral Hot Neutral
Priority 1
(Indirect Tank)
Priority 2
(Heating)
Priority 2 (Heating)
Burner
Power
Power supply for circulator
AC120Volts Max. 2.2Amp.
For External Lamp
No Power supply (Only Contact)
Hot Neutral Hot Neutral
A
C
D
120VAC
Thermostat
Aquastat
Priority 1
(Indirect Tank)
Priority 2
(Heating)
T - T Connection
(DC15V 0.1Amp.)
Hot
GND
Power Input
AC120Volts
Power connection to the boiler.
Connection to
the terminal.
Connection to
the terminal.
Connection to
the terminal.
Connection to
the terminal.
When burning,
the lamp turns
to "ON".
When the power on/off button
is "ON", lamp turns to "ON".
Input up to
120VAC 1Amp.
Input up to
120VAC 1Amp.
Ground
Input
120VAC output
Connect the signal line from
the indirect tank (Aquastat)
Connect the signal line from
the room thermostat
Connection to
the terminal.
120VAC output
Neutral
External Lamp
Signal line connection
Priority 1
(Indirect Tank)
Priority 2
(Heating)
Burner
Power
Power supply for circulator
AC120Volts Max. 2.2Amp.
For External Lamp
No Power supply (Only Contact)
Hot Neutral Hot Neutral
W
d
i
i
l
f
i
h b il
l
h
i
l
f h
i
l
b l
CAUTION
Pump Cautions
- Use the circulating pumps listed below or their equivalents. Add a pump if these are too small. The pump terminal
in the unit is rated for 2.2 Amps.
(See p. 25 for instructions for pumps that require greater than 2.2 Amps).
Taco Model 0013:F3 (1/6 HP) Grundfos Model 26-99F (1/6 HP) Size the circulating pump based on the pressure
loss of the boiler and the piping.
- Install the circulating pump near the return to the boiler.