background image

17

9.

 Water Piping

This appliance suitable for potable water and space heating applications. Do not use this appliance if any part has
been underwater.  Immediately call a qualified service technician to inspect the appliance and replace any part of the
control system and gas control which has been under water.

If the water heater is installed in a closed water supply system, such as one having a backflow preventer in the cold
water supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local plumb-
ing inspector on how to control this situation.

A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying with
either The Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, or
The ANSI/ASME Boiler and Pressure Vessel Code, Section IV ( Heating Boilers ). This pressure relief valve must
be capable of an hourly Btu rated temperature steam discharge of 180,000 Btuh. Multiple valves may be used. The
pressure relief capacity must not exceed 150 psi. No valve shall be placed between the relief valve and the water
heater. The relief valve must be installed such that the discharge will be conducted to a suitable place for disposal
when relief occurs. No reducing coupling or other restriction may be installed in the discharge line. The discharge line
must be installed to allow complete drainage of both the valve and the line. If this unit is installed with a separate
storage vessel, the separate vessel must have its own temperature and pressure relief valve. This valve must also
comply with The Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI
Z21.22. (in the U.S. only). A temperature relief valve is not required, but if one is used, do not install the valve with the
probe directly in the flow of water. This may cause unwarranted discharge of the valve.

Piping and components connected to the water heater shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.
A water heater used to supply potable water may not be connected to any heating system or components previously
used with a nonpotable water heating appliance.
When water is required in one part of the system at a higher temperature than in the rest of the system, means such
as a mixing valve shall be installed to temper the water to reduce the scald hazard.

• Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.
• Take appropriate heat insulation measures (e.g., wrapping with heat insulation materials, using electric heaters)

according to the climate of the region to prevent the pipe from freezing.

• Use a union coupling or flexible pipe for connecting the pipes to reduce the force applied to the piping.
• Do not use piping with a diameter smaller than the coupling.
• When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measure.
• Avoid using joints as much as possible to keep the piping simple.
• Avoid piping in which an air holdup can occur.
• If installing the unit on a roof:
• About lower-level hot water supply

If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied to
the unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water pressure
is maintained at this level.
Check the pressure before putting the unit into operation.
Failure to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, and may
cause the unit to shut down frequently.

Supply water piping

• Do not use PVC, iron, or any piping which has been

treated with chromates, boiler seal or other chemicals.

• Mount a check valve and a shut off valve (near the inlet).
• In order for the client to use the water heater

comfortably, 98.1 to 491 kPa (14 to 70 psi) of
pressure is needed from the water supply.
Be sure to check the water pressure. If the water
pressure is low, the water heater cannot perform
to its full capability, and may become a source of
trouble for the client.

Drain piping

• Expansion water may drop from the pressure

prevention device and wet the floor. If neces-
sary, provide drain piping or use a drain hose to
remove the water.

Hot water piping

• Do not use lead, PVC, iron or any piping which

has been treated with chromates, boiler seal or
other chemicals.

• The longer the piping, the greater the heat loss.

Try to make the piping as short as possible.

• Use mixing valves with low water resistance. Use

shower heads with low pressure loss.

• If necessary, use a pump or other means to en-

sure that the supply water pressure to the inlet of
the heater does not fall below 29 psi when the
maximum amount of water is being demanded.
Also install a pressure meter on the inlet. If this is
not done, local boiling will occur inside the water
heater causing abnormal sounds and decreasing
the durability of the heat exchanger.

Installation and service must be performed by a qualified plumber.  In the
Commonwealth of Massachusetts, this product must be installed by a licensed
plumber or gas fitter in accordance with the Massachusetts Plumbing and Fuel
Gas Code 248 CMR Sections 2.00 and 5.00. Observe all applicable codes.

 SAR8584C̲015̲025̲E̲J.p65

06.11.2, 11:06 PM

Page 17

Adobe PageMaker 6.5J/PPC

Содержание N-0631S

Страница 1: ...d the warranty to the customer along with the Owner s Guide WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or...

Страница 2: ...Cord 10ft 1 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation Outdoor Vent Cap Q ty Shape Part Part Shape Q ty 1 1 Remote Contr...

Страница 3: ...s hard acidic or otherwise impure treat the water with approved methods in order to ensure full warranty coverage WARNING CAUTION Check the Gas Check that the rating plate indicates the correct type o...

Страница 4: ...places where dust or debris will accumulate Dust may block the air supply opening causing the performance of the device fan to drop and incomplete combustion to occur as a result Avoid installation i...

Страница 5: ...t vent as specified For outdoor installation use the outdoor vent cap If it is necessary to vent above the roof line in an outdoor instal lation also use the base of the vent cap for rain protection A...

Страница 6: ...6 Outdoor If possible leave 8 or more on either side of the unit to facilitate inspection If possible leave 24 or more in front of the unit to facilitate maintenance and service if necessary Securing...

Страница 7: ...4 Maintain the following clearance from both combustible and non combustible materials indicates the distance when installing a heat insulat ing board incombustible material other than metal with thic...

Страница 8: ...k or paved driveway located on public property Under veranda porch deck or balcony 7 M indicates clearances required in Canada Maintain clearances in accordance with local installation codes and the r...

Страница 9: ...any building 3 above any forced air inlet within 10 Vent Clearances When Heater is In stalled Outdoors With a Vent Cap All clearance requirements are in accordance with ANSI Z21 10 3 and the National...

Страница 10: ...tration For Installations in Canada clearances are as follows To windows doors gravity air inlets 36 To forced air inlets 6 3 1 1 1 Outdoor Clearances to Opening into Any Building 1 below 1 horizontal...

Страница 11: ...e transfer of vibration Do not drop or apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensur...

Страница 12: ...system Vent Piping Use only UL listed category III vent materials Follow the vent pipe manufacturer s installation instructions Make the vertical section of the exhaust vent as short as possible Main...

Страница 13: ...anufacturer s instructions Slope the horizontal vent 1 4 for every 12 to wards the drain tee Do not vent straight upwards Always have a horizontal section of venting Install a condensation drain in th...

Страница 14: ...t is installed in a mechanical closet provide a 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per...

Страница 15: ...gas line consult local codes or the National Fuel Gas Code ANSI Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Gas Water Heater 180 000 Btuh Clothes Dryer 35 000 Btuh Barbe...

Страница 16: ...ubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 10 20 30 40 50 60 70 80 90 100 150 200 206 383 614 1261 2934 147 269 418 888 2...

Страница 17: ...dirt before connecting it Take appropriate heat insulation measures e g wrapping with heat insulation materials using electric heaters according to the climate of the region to prevent the pipe from f...

Страница 18: ...hall be provided to temper the water for the other uses to help prevent scalding For Space Heating Purposes Check Valve Aquastat Aquastat Pump Expansion Tank Install According to Local Codes Optional...

Страница 19: ...r supply when not in use When the power is off the freeze prevention in the water heater will not activate resulting in possible freezing damage Do not let the power cord contact the gas piping Tie th...

Страница 20: ...utton on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display When setting the maximum temperature to 125 160 F 1 Turn the water heater off...

Страница 21: ...Part RC CORD26 or use 18AWG wire Install according to the National Electrical Code and all applicable local codes Connecting Remote Controller Cord to Unit Keep the remote controller cord away from th...

Страница 22: ...needs to be cleaned it must be performed by a qualified service technician Do not obstruct the flow of combustion and ventilation air The pressure relief valve must be operated once a year to ensure...

Страница 23: ...ns stop and follow the instructions on page 3 of Owner s Guide 6 Turn the gas control manual valve counterclockwise to the on position 7 Turn on electric power to the unit 8 The unit will now operate...

Страница 24: ...LD WATER INLET 3 4 GAS INLET 3 4 HOT WATER OUTLET 3 4 UPPER WALL MOUNT BRACKETS LOWER WALL MOUNT BRACKETS BOTTOM OF CASE BOTTOM OF CASE WIRING THROUGHWAYS 7 1 4 3 1 6 GAS INLET 3 4 1 8 1 8 10 5 6 2 HO...

Страница 25: ...otes on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locat...

Страница 26: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Страница 27: ...he wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wa...

Отзывы: