FD67 Profibus-DP Manual
8
1
8.3.2.4 Bit assignments of parameter bytes
Bytes 0,4,8,12
Settings channels 0,1,2,3
7 6 5 4 3 2 1 0
Measuring range :
00 : inactive
01 : 0..10V
10 : +/- 10V
Diagnosis
14
0 : report
1 : do not report
Data format :
0 : Byte sequence High/Low (Motorola)
1 : Byte sequence Low/High (Intel)
Smoothing :
00 : none
01 : weak
10 : moderate
11 : strong
Reserved
Bytes (2,3),(6,7),(10,11),(14,15)
Channels (0,1,2,3) : Delta
Type of data
Unsigned16
Admissible values
0..32767
Unused channels should be disabled to optimise cycle time.
14
Diagnostic information of the corresponding channel.