FD67 Profibus-DP Manual
17
5.3.2 Structure of a configuration string
The configuration string is transmitted to the data field of the configuration message. The IDs are entered
in the order in which the modules are connected to the bus node.
Part No.
Description
Process data length Identification
Input
Output
FD67DIOM121216
16 x Output/input M12
2 bytes
2 bytes
C2
hex
01
hex
01
hex
DD
hex
18
hex
FD67DIM121216
*
16 x Input M12
2 bytes
-
42
hex
01
hex
DD
hex
1A
hex
FD67DOM121216
*
16 x Output M12
-
2 bytes
82
hex
01
hex
DD
hex
1C
hex
FD67DIOM120016
16 x Output/input M12
2 bytes
2 bytes
C2
hex
01
hex
01
hex
DD
hex
19
hex
FD67DIM120016* 16 x Input M12
2 bytes
-
42
hex
01
hex
DD
hex
1B
hex
FD67DOM120016* 16 x Output M12
-
2 bytes
82
hex
01
hex
DD
hex
1D
hex
FD67DIM120016
16 x Input M12
2 bytes
-
42
hex
01
hex
DD
hex
1B
hex
FD67DIOM120008
8 x Output/input M12
2 bytes
2 bytes
C2
hex
01
hex
01
hex
DD
hex
23
hex
FD67DIM120008
*
8 x Input M12
2 bytes
-
42
hex
01
hex
DD
hex
25
hex
FD67DOM120008
*
8 x Output M12
-
2 bytes
82
hex
01
hex
DD
hex
27
hex
FD67DIM120008
8 x Input M12
2 bytes
-
42
hex
01
hex
DD
hex
25
hex
FD67DIOM080008
8 x Output/input M8
1 byte
1 byte
C2
hex
00
hex
00
hex
DD
hex
2D
hex
FD67DIM080008
*
8 x Input M8
1 byte
-
42
hex
00
hex
DD
hex
2F
hex
FD67DOM080008
*
8 x Output M8
-
1 byte
82
hex
00
hex
DD
hex
31
hex
FD67DIM080008
8 x Input M8
1 byte
42
hex
00
hex
DD
hex
2F
hex
FD67AIVM120004
Analogue input (voltage) M12
4 words
-
42
hex
43
hex
DD
hex
7C
hex
FD67AOVM120004
Analogue output (voltage) M12 -
4 words
82
hex
43
hex
DD
hex
86
hex
FD67AOCM120004
Analogue output (current) M12 -
4 words
82
hex
43
hex
DD
hex
90
hex
FD67AICM120004
Analogue input (current) M12
4 words
-
42
hex
43
hex
DD
hex
9A
hex
FD67DODSC0016
16 x Output to valve island
-
2 bytes
82
hex
01
hex
DD
hex
4B
hex
♦
Table 5-1 : Profibus identifications of I/O modules
*
preconfigured module versions (see Chapter 5.4.2)