background image

5

INSTALLER INFORMATION

IMPORTANT SAFETY INFORMATION

INSTALLER: Please read all instructions before servicing 
this equipment. Pay attention to all safety warnings and 
any other special notes highlighted in the manual. Safety 
markings are used frequently throughout this manual to 
designate a degree or level of seriousness and should not 
be ignored. WARNING indicates a potentially hazardous 
situation that if not avoided, could result in personal injury 
or death. CAUTION indicates a potentially hazardous 
situation that if not avoided, may result in minor or moderate 
injury or property damage.

 WARNING:

Shut off all electrical power to the unit before 
performing any maintenance or service on the 
system. Failure to comply may result in personal 
injury or death.

 WARNING:

Unless noted otherwise in these instructions, 
only factory authorized parts or accessory 
kits may be used with this product. Improper 
installation, service, adjustment, or maintenance 
may cause explosion, fire, electrical shock or 
other hazardous conditions which may result in 
personal injury or property damage

 WARNING:

T5BD split system heat pumps leave the factory 
with a nitrogen holding charge. Follow all charg-
ing instructions for maximum unit performance 
and efficiency. Some local codes require licensed 
installation/service personnel to service this type 
of equipment. Refrigerant charging must be done 
by qualified personnel familiar with safe and en-
vironmentally responsible refrigerant handling 
procedures. Under no circumstances should 
the owner attempt to install and/or service this 
equipment. Failure to comply with this warning 
could result in property damage, personal injury, 
or death.

 CAUTION:

This unit uses R-22 refrigerant. DO NOT use 
any other refrigerant in this unit. Use of another 
refrigerant will damage the unit.

 WARNING:

The information listed below must be followed 
during the installation, service, and operation 
of this unit. Unqualified individuals should 
not attempt to interpret these instructions or 
install this equipment. Failure to follow safety 
recommendations could result in possible 
damage to the equipment, serious per

sonal 

injury or death.

•  The  installer  must  comply  with  all  local  codes  and 

regulations which govern the installation of this type 
of equipment. Local codes and regulations take 
precedence over any recommendations contained in 
these instructions. Consult local building codes and 
the National Electrical Code (ANSI CI) for special 
installation requirements.

•  All electrical wiring must be completed in accordance 

with local, state and national codes and regulations 
and with the National Electric Code (ANSI/NFPA 70) 
or in Canada the Canadian Electric Code Part 1 CSA 
C.22.1.

•  This equipment contains liquid and gaseous refrigerant 

under high pressure. DO NOT USE ANY PORTION OF 
THE CHARGE FOR PURGING OR LEAK TESTING.
Installation or servicing should only be performed by 
qualified trained personnel thoroughly familiar with this 
type equipment.

•  Fully annealed, refrigerant grade copper tubing should 

be used when installing the system. Refrigerant suction 
line tubing should be fully insulated.

•  Installation  of  equipment  may  require  brazing 

operations. Installer must comply with safety codes 
and wear appropriate safety equipment (safety glasses, 
work gloves, fire extinguisher, etc.) when performing 
brazing operations.

•  This unit is designed for outdoor installations only and 

should be located as descibed on page 6.

•  Follow all precautions in the literature, on tags, and 

on labels provided with the equipment. Read and 
thoroughly understand the instructions provided with 
the equipment prior to performing the installation and 
operational checkout of the equipment.

Содержание T5BD Series

Страница 1: ...eliminate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalco...

Страница 2: ...nits 18 Refrigerant Charging Tables Heating Mode 19 Table 10 T5BD 018K 1 5 Ton Units 19 Table 11 T5BD 024KA 2 Ton Units 19 Table 12 T5BD 030KA 2 5 Ton Units 20 Table 13 T5BD 036K 3 Ton Units 20 Table...

Страница 3: ...system mode to COOL or AUTO and change the fan mode to AUTO See Figure 1 2 Setthetemperatureselectortothedesiredtemperature level Theoutdoorfan compressor andblowermotorwill all cycle on and off to ma...

Страница 4: ...e aluminum fins Check and remove any obstructions such as twigs sticks etc TROUBLESHOOTING If the unit fails to operate check the following The thermostat is properly set See Cooling Operation for air...

Страница 5: ...erant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individu...

Страница 6: ...ility of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine the best location for mounting the outdoor unit See Figur...

Страница 7: ...be in compliance with all applicable local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and groun...

Страница 8: ...marked 208V Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC ANSI NFPA 70 applicable local codes and the instructions provided wit...

Страница 9: ...oom temperature and verify the outdoor unit and indoor blower energize 2 Verify blower wheel is spinning in direction indicated by arrow Feel the air being circulated by the indoor blower and verify t...

Страница 10: ...he required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged Heat Pump MAINT...

Страница 11: ...4 060K 43 30 3 4 30 3 4 D W H DO NOT OBSTRUCT TOP OF UNIT Allow adequate clearance for airflow reffrigerant Charging Charts Figure 5 Charging Chart for 1 5 Ton Units 125 150 175 200 225 250 275 300 32...

Страница 12: ...perature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units T5BD 030KA Charging Chart 150 175 200 225 250 275 300 325...

Страница 13: ...perature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units T5BD 042K Charging Chart 150 175 200 225 250 275 300 325...

Страница 14: ...g Add refrigerant when below curve Remove refrigerant when above curve T5BD 048K Charging Chart Figure 11 Charging Chart for 5 Ton Units 150 170 190 210 230 250 270 290 310 330 350 75 80 85 90 95 100...

Страница 15: ...Liq Press Dis Temp Liq Press Dis Temp 73 140 135 75 143 140 155 137 77 145 146 157 143 170 140 79 147 150 160 148 172 145 185 142 81 151 153 162 152 175 150 187 147 200 144 83 166 155 177 154 189 151...

Страница 16: ...ss Dis Temp Liq Press Dis Temp 71 148 144 73 150 149 164 147 75 152 155 166 152 179 149 77 155 158 168 157 181 154 195 152 79 159 161 171 161 183 159 197 156 210 154 81 174 164 187 163 199 161 212 158...

Страница 17: ...ss Dis Temp Liq Press Dis Temp 69 132 130 71 134 136 149 135 73 136 141 151 140 166 140 75 137 149 153 145 168 145 183 145 77 140 152 154 152 170 150 185 149 200 149 79 158 155 172 155 188 154 203 153...

Страница 18: ...7 84 222 178 235 176 248 174 260 171 86 238 180 252 178 265 176 88 255 182 268 180 90 271 185 92 Shaded boxes indicate flooded conditions Rated design values The suction pressure will vary from design...

Страница 19: ...ress Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 12 120 107 21 135 119 29 150 131 37 165 142 46 169 158 56 184 177 66...

Страница 20: ...ss Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 13 116 120 22 136 125 31 156 130 40 176 136 49 183 151 59 201 175 68 21...

Страница 21: ...ess Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 23 129 118 27 140 124 31 151 130 35 162 136 44 173 149 58 206 168 72 2...

Страница 22: ...159 139 31 182 143 39 206 147 48 230 158 58 257 175 68 283 193 16 142 133 24 165 137 32 187 141 40 209 145 49 237 155 59 264 171 69 290 187 17 149 131 25 171 135 33 192 139 41 213 143 50 244 152 60 27...

Страница 23: ...avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 volt a la terre Single Phase OPTIONAL HARD START KIT Start Capacitor 2 5 Sta...

Страница 24: ...8 1 4 1 4 1 4 1 4 1 4 Fan Blade Dia Blades 24 3 SCFM 2370 2370 3000 3000 3000 4000 4000 Compressor Data RLA 8 3 10 8 13 4 15 3 19 2 19 8 25 3 LRA 40 3 56 68 87 112 105 146 Refrigerant suction line Le...

Отзывы: